V6.230 20131017
108
Enter:68/7
This will set the node address to 7.
7.2.3 Setting Remote Blocking
Remote block is useful if it is necessary to block remote control of any of the
output relays. This is only necessary if Objects 10 and 12 have been
implemented to permit Supervisory and Control to command cooling remotely.
To change this setting, enter PROGRAM mode from the front panel as
discussed in Section 4.1. To set the node address from the front panel, enter the
Configuration menu and press the
or
arrow button until the setting 069 is
displayed:
Press the
YES
button. The first character will flash. Use the
or
arrow buttons
to scroll between DSABL (disable) and ENABL (enable).
Press
YES
when you have made the correct selection. Selecting ENABL will
block the remote control of the output relays.
For programming from a PC, enter PROGRAM through the main menu as
discussed in Section 0. Once in PROGRAM, type the setting for remote block on
the “Enter:” line as follows:
Enter:69/1
This will enable remote block. Type 0 to disable remote block.
7.3
Telemetry Via RS232
Asynchronous data communications is implemented through the front panel
mounted DB-9 connector at a fixed data rate of 9600 bits per second, 8 bits of
data, no parity, and one stop bit. We have verified operation of the interface with
HyperTerminal Private Edition and HyperAccess. It is recommended that the
terminal emulation be set for either ANSI or TTY. The pin out of this port is
designed to use a 9 pin female to 9 pin male null modem cable.
The TTC-1000 permits remote reporting of temperature or resetting of the time of
day by sending a forward slash ‘/’ followed by either the characters T
PRGM SETTING 069
REMOTE BLK=DSABL
PRGM SETTING 069
REMOTE BLK =ENABL
Содержание TTC-1000
Страница 11: ...Warranty V6 230 20131017 x PAGE INTENTIONALLY BLANK ...
Страница 41: ...V6 230 20131017 30 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 121: ...V6 230 20131017 110 PAGE INTENTIONALLY BLANK ...
Страница 133: ...V6 230 20131017 122 PAGE INTENTIONALLY BLANK ...
Страница 152: ...V6 230 20131017 141 6 After closing the import wizard the text data will display The data is now ready for graphing ...
Страница 153: ...V6 230 20131017 142 PAGE INTENTIONALLY BLANK ...
Страница 157: ...V6 230 20131017 146 PAGE INTENTIONALLY BLANK ...
Страница 199: ...V6 230 20131017 188 PAGE INTENTIONALLY BLANK ...
Страница 247: ...V6 230 20131017 236 PAGE INTENTIONALLY LEFT BLANK ...