V6.230 20131017
20
3.5
Cooling Control and Condition Alarm Connections
Figures 3.13 a&b illustrate the connections of the form C dry relay contacts for
both NEMA and panel mount models. Figure 3.13b shows these connections on
panel mount models and 3.13a for NEMA models, Each relay is capable of
carrying 10 Amps at 230 VAC. Configure these contacts for cooling control, high
temperature alarms, or LTC condition alarm. Programming these contacts will be
discussed in Section 4.9.
NOTE: The ability for these contacts to break its load is based on a number
of factors including voltage applied and the type of load. In general, there is
a higher tendency for contacts to become welded shut at higher voltages.
Therefore, protection devices, such as MOVs are highly recommended if
these contacts will be required to break more load current than that shown
in the Specifications.
Figure 3.13a: Relay
Outputs – NEMA
Note that all terminations
may not be present
depending on the options
purchased.
Figure 3.13b: Relay
Outputs – Panel
Note that all terminations
may not be present
depending on the options
purchased.
1
2
POWER
3
4
AuxCT
C
O
M
T
M
P
R
E
F
GROUND
SHIELD
TB3
TB2
TB1B
C
O
M
T
M
P
R
E
F
ANALOG OUT
+
-
A1
+
-
A2
ALARM
N
C
OUT4
C
N
O
N
C
OUT3
C
N
O
N
C
OUT2
C
N
O
N
C
OUT1
C
N
O
N
C
OUT5
C
N
O
N
C
OUT6
C
N
O
TB1A
C
O
M
T
M
P
R
E
F
A
B
RS485
Rx
Tx
G
N
D
Rpt
Tx
Rx
5
6
7
1
2
3
4
IN1
IN2
TB4
TB5
+
-
A3
BUSY
OK
1
2
3
4
IN4
IN3
9
10
11
12
IN14
IN13
5
6
7
8
IN12
IN11
3
4
IN10
1
2
IN9
5
6
7
8
IN6
IN5
9
10
11
12
IN8
IN7
16 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
CT1
CT2
CT3
CT4
CT5
CT6
CT7
CT8
TB6
TB7
TB8
1
2
3
4
TB3
TB2
Aux CT
Power
TB1
OUT5
OUT6
OUT4
OUT2
OUT3
OUT1
TB1A
TB5
IN2
IN1
2
1
Probe 1
Probe 2
Alarm
10
11
12
7
8
9
5
6
4
Probe 3
3
IN 3
IN 4
IN 5
IN 6
IN 7
IN 8
TB7
IN 9
IN 10
IN 11
IN 12
IN 13
IN 14
TB6
Содержание TTC-1000
Страница 11: ...Warranty V6 230 20131017 x PAGE INTENTIONALLY BLANK ...
Страница 41: ...V6 230 20131017 30 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 121: ...V6 230 20131017 110 PAGE INTENTIONALLY BLANK ...
Страница 133: ...V6 230 20131017 122 PAGE INTENTIONALLY BLANK ...
Страница 152: ...V6 230 20131017 141 6 After closing the import wizard the text data will display The data is now ready for graphing ...
Страница 153: ...V6 230 20131017 142 PAGE INTENTIONALLY BLANK ...
Страница 157: ...V6 230 20131017 146 PAGE INTENTIONALLY BLANK ...
Страница 199: ...V6 230 20131017 188 PAGE INTENTIONALLY BLANK ...
Страница 247: ...V6 230 20131017 236 PAGE INTENTIONALLY LEFT BLANK ...