Setting #
Setting
Purpose
Setting Range or Values
Program to
55
RAISE INPUT
Specifies the Input #
that is going to get
assigned an RAISE
function of Tap
Position Monitoring.
55/nn
where nn = 0 to 14
0: NONE (not defined)
1: IN1
2: IN2
…
14: IN14
56
LOWER INPUT
Specifies the Input #
that is going to get
assigned an
LOWER function of
Tap Position
Monitoring.
56/nn
where nn = 0 to 14
0: NONE (not defined)
1: IN1
2: IN2
…
14: IN14
57
UPPER LIMIT
INPUT
Specifies the Input #
that is going to force
Tap Position Monitor
to the UPPER LIMIT
position when
picked up.
57/nn
where nn = 0 to 14
0: NONE (not defined)
1: IN1
2: IN2
…
14: IN14
58
LOWER LIMIT
INPUT
Specifies the Input #
that is going to force
Tap Position Monitor
to the LOWER
LIMIT position when
picked up.
58/nn
where nn = 0 to 14
0: NONE (not defined)
1: IN1
2: IN2
…
14: IN14
59
RESET INPUT
Specifies the Input #
that is going to force
Tap Position Monitor
to the NEUTRAL
position when
picked up.
59/nn
where nn = 0 to 14
0: NONE (not defined)
1: IN1
2: IN2
…
14: IN14
Содержание TTC-1000
Страница 11: ...Warranty V6 230 20131017 x PAGE INTENTIONALLY BLANK ...
Страница 41: ...V6 230 20131017 30 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 121: ...V6 230 20131017 110 PAGE INTENTIONALLY BLANK ...
Страница 133: ...V6 230 20131017 122 PAGE INTENTIONALLY BLANK ...
Страница 152: ...V6 230 20131017 141 6 After closing the import wizard the text data will display The data is now ready for graphing ...
Страница 153: ...V6 230 20131017 142 PAGE INTENTIONALLY BLANK ...
Страница 157: ...V6 230 20131017 146 PAGE INTENTIONALLY BLANK ...
Страница 199: ...V6 230 20131017 188 PAGE INTENTIONALLY BLANK ...
Страница 247: ...V6 230 20131017 236 PAGE INTENTIONALLY LEFT BLANK ...