– 23 –
TO DETERMINE TOTAL
STANDBY LOAD ON
BATTERY, ADD 100mA
TO TOTAL OFAUX.
POWER OUTPUT AND
REMOTE TOUCHPAD
CURRENTS.
USE UL LISTED LIMITED
ENERGY CABLE FOR
ALL CONNECTIONS
CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE
ALARM HEADQUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH THE PERMISSION
OF THE LOCAL AUTHORITY HAVING JURISDICTION.
THE BURGLAR ALARM SIGNAL SHALL NOT BE
CONNECTED TO A POLICE EMERGENCY NUMBER.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
LOCATED
AT LOWER
RIGHT OF
CIRCUIT
BOARD
EARTH
GROUND
TERMINAL
REMOTE TOUCHPADS
SYSTEM
MUST BE
PROGRAMMED WITH A
CUSTOM ENGLISH
TOUCHPAD, BUT NEED NOT
REMAIN IN THE SYSTEM.
AFTER PROGRAMMING, THE
SYSTEM CAN USE:
6128ADT (30mA) OR
6139ADT (100mA).
MULTIPLE TOUCHPADS MAY BE
USED, BUT USE MAX. OF 220 FT.
OF #22 WIRE OR 550 FT. OF #18.
BLACK: T
OUCHP
AD GROUND (–) RETURN
RED: T
OUCHP
AD PWR (+)
GREEN: DA
T
A
IN FROM T
OUCHP
AD
YELLOW
: DA
T
A
OUT T
O
T
OUCHP
AD
▲
▲
REMOTE
TOUCHPAD(S)
AUX. POWER
OUTPUT
10.5-13.8VDC
500mA MAX.
INTERRUPTS
FOR FIRE
ALARM RESET
NOTE:
TOUCHPAD
CURRENT
MUST BE
INCLUDED
IN AUX.
CURRENT
DRAIN
CALCULATIONS
}
GEL LEAD ACID TYPE.
BATTERY NORMALLY NEED NOT BE
REPLACED FOR AT LEAST 3 YRS.
BATTERY CAPACITY FOR EMERGENCY
STANDBY USE AT LEAST 4 HOURS.
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) IT MAY NOT CAUSE HARMFUL INTERFERENCE,
(2) IT MUST ACCEPT ANY INTERFERENCE THAT MAY CAUSE
UNDESIRED OPERATION.
COMPLIES WITH FCC RULES, PART 68
FCC REGISTRATION NO. AC398U-68192-AL-E
RINGER EQUIVALENCE: 0.7B.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL
FIRE
PROTECTION ASSOCIATION'S STANDARD 74
(NATIONAL
FIRE PROTECTION ASSOC.,
BATTERYMARCH PARK, QUINCY, MA 02269).
PRINTED INFORMATION DESCRIBING PROPER
INSTALLATION, OPERATION, TESTING,
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
CHARGING
VOLTAGE
13.8VDC
BATTERY
12V, 4AH
(e.g. ADEMCO
No. 467)
OR 12V, 1.2AH
–
+
–
+
BATTERY
CONNECTOR TABS
PLUG-IN
TRANSFORMER
16.5VAC, 25VA
(e.g. ADEMCO
No. 1321.
TO 110VAC
UNSWITCHED OUTLET
(24-HR)
–
+
ALARM OUTPUT
10.5–13.8VDC, 2A MAX.
(600mA MAX. FOR UL USAGE,
INCLUDING AUX. POWER)
STEADY FOR BURGLARY/PANIC,
TEMPORAL SOUNDING FOR FIRE (e.g.
USE ADEMCO No. 740 SOUNDER,
Nos. 702 OR 719 SIREN, OR 12V BELL)
BATTERY FUSE
(e.g. ADEMCO No. 90-12)
FOR REPLACEMENT
USE SAME VALUE
3A
BLK
RED
GRN
YEL
OPTIONAL
FOR UP TO 16 RF EXPANSION ZONES
1000
OHMS
EOLR
1000
OHMS
EOLR
ZONE 5
ZONE 6
HI
LO
HI
LO
WARNING:
OWNER'S INSTRUCTION
NOTICE NOT TO BE REMOVED. WEEKLY
TESTING IS REQUIRED ENSURE PROPER
OPERATION OF THIS SYSTEM.
TIP
(BROWN)
RING
(GRAY)
TIP
(GREEN)
RING
(RED)
}
}
INCOMING
PHONE
LINE
HANDSET
BLACK
RED
–
+
1000
OHMS
EOLR
1000
OHMS
EOLR
ZONE 1
ZONE 2
HI
LO
HI
LO
1000
OHMS
EOLR
1000
OHMS
EOLR
ZONE 3
ZONE 4
HI
LO
HI
LO
• MAXIMUM LOOP RESISTANCE (EACH ZONE): 300 OHMS (PLUS EOLR)
• RESPONSE, ZONES 1–6: 300–500MSEC
• ZONE 3 CAN BE PROGRAMMED FOR N.C. SENSOR FAST RESPONSE
TO AN OPEN: 10MSEC MAX
• ZONE 5 CAN BE PROGRAMMED FOR USE AS A FIRE ZONE.
ADEMCO 5881 Type
RF RECEIVER
WIRELESS ZONES
5881L: UP TO 8
5881M/5881H: UP TO 16
ADEMCO No. 4204
RELAY MODULE (180mA MAX)
(4 OUTPUT RELAYS)
SET UNIT’S DIP SWITCH
FOR DEVICE ADDRESS OF “0”
(See receiver’s instructions)
SET UNIT’S DIP SWITCH
FOR DEVICE ADDRESS OF “1”
(See unit’s instructions)
ADEMCO No. 5800TM
TRANSMITTER MODULE
(20mA)
(for No. 5827BD
Wireless Bidirectional Touchpad)
AND/OR
ADEMCO No. 4285
VOICE MODULE (160mA)
AND/OR
ADEMCO No. 7720PLUS
or 7820 LONG RANGE RADIO
OPTIONAL
THESE OPTIONAL ITEMS
MAY ALSO BE USED
SEE THEIR INSTRUCTIONS
PROPER
EARTH
GROUND
(SEE
INSTRUCTIONS)
TELEPHONE WIRING
(VIA RJ31X JACKAND
DIRECT CONNECT CORD)
RED
JUMPER
CUT FOR BELL SUPERVISION
ZONE 5
(IF PROGRAMMED FOR FIRE)
+
–
AUX PWR
OUTPUT
TERMS
+
-
+
-
-
+
EOL
POWER
SUPER-
VISION
RELAY
MODULE
A77-716B
•
•
5
4
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
1000
OHMS
EOLR
HEAT
DETECTOR
+
RED
BLK
–
VIOLET
WARNING: TO PREVENT RISK OF
SHOCK, DISCONNECT TELEPHONE
LINE AT TELCO JACK BEFORE
SERVICING THIS UNIT.
S
U
MMA
RY
O
F
CO
NNE
CTI
O
NS
DI
A
G
RA
M
Содержание SA10ADTEG
Страница 22: ... 22 NOTES ...