*57 Function Key Programming Worksheet 

 

Option

 

 
Function 

 

P1  P2 

com 

P1  P2 

com 

P1  P2 

com 

P1  P2 

com 

Comments

 

01

 

Paging 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02

 

Time Display 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03

 

Arm AWAY 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

 

Arm STAY 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05

 

Arm NIGHT-STAY 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

 

Step Arming  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

07

 

Device Activation 

 

 

 

 

 

 

 

 

 

 

 

 

 

Device:

 

08

 

Comm. Test

 

 

 

 

 

 

 

 

 

 

 

 

 

 

09

 

Macro Key 1 

 

 

 

 

 

 

 

 

 

 

 

 

 

Assign each macro key to only a single partition.

 

 

10

 

Macro Key 2 

 

 

 

 

 

 

 

 

 

 

 

 

 

Assign each macro key to only a single partition.

 †

 

11

 

Macro Key 3 

 

 

 

 

 

 

 

 

 

 

 

 

 

Assign each macro key to only a single partition.

 †

 

12

 

Macro Key 4 

 

 

 

 

 

 

 

 

 

 

 

 

 

Assign each macro key to only a single partition.

 †

 

00

 

Emergency Keys:

 

zone 95 

zone 99 

zone 96 

paging 

 

 

Personal Emergency

 

 

 

 

 

 

 

 

 

 

n/a 

 

 

Silent Alarm 

 

 

 

 

 

 

 

 

 

 

n/a 

 

 

Audible Alarm 

 

 

 

 

 

 

 

 

 

 

n/a 

 

 

Fire

 

 

 

 

 

 

 

 

 

 

n/a 

 

 

Emergency Keys:  

A = paired keys [1] / [

] (zone 95); B = paired keys [

] / [#] (zone 99); C = paired keys [3] / [#] (zone 96) 

† There are only four macros system-wide. 

 

 

Output Relays/Powerline Carrier Devices (X-10) Worksheet For 

79, 

80 and 

81.

 

Applicable only if Relays and/or Powerline Carrier Devices are to be used. 

 

 

79 RELAY/POWERLINE CARRIER DEVICE (X-10) MAPPING (Must program before using *80) 

 

OUTPUT TYPE

 

 

 

OUTPUT TYPE

 

 

Relay

 

X10

 

 

 

 

Relay

 

X10

 

 

Output 
No.

 

Module 
Addr.

 

Pos 

(1-4)

 

Unit 
No.

 

 

Description

 

 

Output
No.

 

Module 
Addr.

 

Pos 

(1-4)

 

Unit 
No.

 

 

Description

 

01

 

 

 

 

 

 

09

 

 

 

 

 

02

 

 

 

 

 

 

10

 

 

 

 

 

03

 

 

 

 

 

 

11

 

 

 

 

 

04

 

 

 

 

 

 

12

 

 

 

 

 

05

 

 

 

 

 

 

13

 

 

 

 

 

06

 

 

 

 

 

 

14

 

 

 

 

 

07

 

 

 

 

 

 

15

 

 

 

 

 

08

 

 

 

 

 

 

16

 

 

 

 

 

 

 

 

 

 

 

17

 

On-Board Trigger 1

 

norm output = 

 

 

 

 

 

 

 

18

 

On-Board Trigger 2

 

norm output = 

 

 

 

81

 

ZONE LISTS FOR OUTPUT DEVICES

 

 

Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the 
data during the displays and prompts that appear in sequence. 

Note:

 

Record desired zone numbers below, noting that a list may include 

any

 or 

all

 of system's zone numbers. 

 

List No.  Used For… 

Contains These Zones… 

  01 

General Purpose (GP)

 

  02 

General Purpose

 

  03 

Chime-by-Zone or GP  

(see field *26 for chime by zone option)

 

  04 

Cross Zones or GP  

(see field *85 for cross zone timer setting)

 

  05 

Night-Stay Zones or GP 

 

  06 

Dial Delay Disable or GP 

(see field *50 for dial delay disable option)

 

  07 

Unlimited Reports or GP 

(see field *93 for unlimited reports option)

 

  08 

General Purpose 

  09 

Zones activating pager 1

 

  10 

Zones activating pager 2 

  11 

Zones activating pager 3 

  12 

Zones activating pager 4 

 

Содержание Entrepreneur 3000EN

Страница 1: ...and System Installation Notes For full installation and programming information please refer to the Installation and Setup Guide K5305V8 or higher ARMED READY 1 2 3 4 5 6 7 8 9 0 STAY BYPASS CHIME IN...

Страница 2: ...ories 25 Recommendations for Proper Protection 27 FCC Industry Canada 27 UL Notices 28 Uploading Downloading via the Internet 29 The Limitations of This Alarm System 30 Summary of Connections 31 Atten...

Страница 3: ...mming Press 80 4229 or 4204 Relay modules powerline carrier devices or on board triggers Zone List Programming Press 81 Zone Lists for relay powerline carrier activation chime zones pager zones etc Al...

Страница 4: ...be 00 for UL Commercial Burg installations 29 Enable IP GSM Communication Device Menu Mode pass through programming This is a Menu Mode command not a data field for programming IP GSM communication de...

Страница 5: ...Open Close Test 3 Alarms Restore Cancel All 4 All except Open Close Test All 5 All All 50 BURGLARY DIAL DELAY 2 0 Delay Time Delay Disable values other than those stated will give unpredictable result...

Страница 6: ...ORE RPT CODE 1 Any non zero entry enables report 71 TROUBLE RESTORE RPT CODE 10 Any non zero entry in first digit enables report 72 BYPASS RESTORE RPT CODE 00 Any non zero entry in first digit enables...

Страница 7: ...use zone list 7 to enter those zones that require unlimited reporting these zones ignore the setting in entry 1 DOWNLOAD INFORMATION 94 95 94 DOWNLOAD PHONE No Enter up to 20 digits 0 9 11 for 12 for...

Страница 8: ...able 1 enabled 181 50 60 HERTZ AC OPERATION 0 0 60 Hz 1 50 Hz CONFIGURABLE ZONE TYPE OPTIONS 183 181 182 CONFIGURABLE ZONE TYPE 90 IMPORTANT Be careful when selecting combinations of options for confi...

Страница 9: ...e Refer to the communication device s installation instructions for details on enabling the Remote Services feature TOUCHPAD OPTIONS 190 196 NOTE Options for touchpad 1 address 16 are set by the facto...

Страница 10: ...6 Short dial delay fault delay ENTRY 7 ENTRY 8 Display Faults Power Reset Verification Use Entry Delay 1 2 Use Exit Delay Respond as Interior Type 0 show alarms when armed disarmed 1 don t show alarm...

Страница 11: ...1 57 1 BR 1 58 1 BR 1 59 1 BR 1 60 1 BR 1 61 1 BR 1 62 1 BR 1 63 1 BR 1 64 1 BR 1 95 09 N A N A N A touchpad 1 96 N A N A N A touchpad 3 99 07 N A N A N A touchpad NOTES Zone Type see chart on page 12...

Страница 12: ...10 MAPPING Must program before using 80 OUTPUT TYPE OUTPUT TYPE Relay X10 Relay X10 Output No Module Addr Pos 1 4 Unit No Description Output No Module Addr Pos 1 4 Unit No Description 01 09 02 10 03 1...

Страница 13: ...or Zone Types are 00 Not Used 05 Trouble Day Alarm Night 10 Interior w Delay 24 Silent Burglary 01 Entry Exit 1 06 24 Hr Silent 12 Monitor Zone 25 24 Hr Non Alarm 02 Entry Exit 2 07 24 Hr Audible 14 C...

Страница 14: ...07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Events Master Installer Installer Only 00 clear event 04 forced STAY arm 10 display custom words 8 10 01 device on off 05...

Страница 15: ...has an emergency button Sends a report to the central station and provides an alarm sound at the touchpad and an audible external alarm Type 08 24 hour Auxiliary Alarm Assign to a zone containing an e...

Страница 16: ...may not be used as fire or burglary zones in fire or UL burglar alarm installations The system can still be armed when these zone types are in a faulted condition Table of Device Addresses This Device...

Страница 17: ...L 153 POWER R 155 RADIO 156 REAR 157 RECREATION 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF S 164 SAFE 165 SCREEN 166 SENSOR 167 SERVICE 168 SHED 169 SHOCK 170 SHOP 171 SHORT 173 SIDE 174 SKY...

Страница 18: ...that the board rests on the correct row see Detail A b Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws see Detail B Notes Before in...

Страница 19: ...resistance to damage from generally expected levels of lightning and electrical discharge and does not normally require an earth ground If an earth ground is desired for additional protection in area...

Страница 20: ...For additional information regarding the 5800TM refer to the 5800TM s instructions Transmitters ULC Note for Canadian Units In accordance with ULC standards the RF supervision period for this control...

Страница 21: ...ENROLL AS RF 5801 ENROLL AS UR OR RF 5800SS1 ENROLL AS RF LOOP 3 LOOP 1 LOOP 2 LOOP 4 YOU MUST ENROLL THIS BUTTON 5894PI ENROLL AS RF 5802 MN2 ENROLL AS UR OR RF LOOP 1 LOOP 1 LOOPS 1 3 LOOP 1 LOOP 1...

Страница 22: ...keyswitch zone must be programmed to send opening and closing signals a UL commercial burglar alarm installation the keyswitch s tamper switch must be connected in to the alarm system This tamper swit...

Страница 23: ...h aabout a twice per minute beeping at the touchpad indicates that a low battery condition exists in the wireless sensor displayed zone 00 indicates a wireless touchpad If the battery is not replaced...

Страница 24: ...rn on and a LOW BATTERY report will be transmitted with a TEST report The touchpad will beep once about every 30 seconds as a reminder that the system is in the Test mode NOTE Wireless motion detector...

Страница 25: ...es not confirm report transmissions 1 DIAL 0 WALK no special display on English Display Touchpads displays DISARMED READY TO ARM The following will be displayed accompanied by 2 beeps if test is succe...

Страница 26: ...ers 6150RFADT 6160RF 6270ADT Touch Screen Touchpad iCenter Advanced User Interface RF Receivers 5881L 5882L accepts up to 8 transmitters 5881M 5882M accepts up to 16 transmitters 5881H 5882H accepts u...

Страница 27: ...in any room where an alarm control is located or in any room where alarm control connections to an AC source or phone lines are made If detectors are not so located a fire within the room could preven...

Страница 28: ...radation du service dans certaines situations Les r parations de mat riel nomologu doivent tre coordonn es par un repr sentant d sign par le fournisseur L entreprise de t l communications peut demande...

Страница 29: ...nt 7845GSMADT System Requirements Internet Communication At the Installation Site Appropriate Internet Communication Module 7720P Programmer Broadband Internet Access for wired modules Broadband Cable...

Страница 30: ...s closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their detec...

Страница 31: ...MINALS SEE INSTRUCTIONS REMOTE TOUCHPADS EACH PARTITION CAN USE 6150ADT OR 6160ADT TOUCHPADS SEE INSTRUCTIONS PROVIDED WITH TOUCHPAD LOCAL PROGRAMMING MUST BE DONE WITH A 6160ADT BUT NEED NOT REMAIN I...

Страница 32: ...ORMATION For the latest warranty information please go to www honeywell com security hsc resources wa ADT Security Services Inc One Town Center Rd Boca Raton FL 33486 Copyright 2003 K9287V6 K9287V6 8...