Zone Type Definitions 

 

Type 00 

 

ZONE NOT USED. Use this zone type if the zone is not used. 

 

Type 01 

Entry/Exit Burglary #1

 

 

  Assign to zones that are used for primary entry and exit. 

  Provides entry delay if the control is armed in the Away or Stay modes.  

  No entry delay is provided when the panel is armed in the Instant mode.  

  Entry delay #1 is programmable for each partition. 

   Exit delay begins whenever the control is armed, regardless of the arming mode selected, and is 

independently programmable (field 

34).

 

Type 02 

Entry/Exit Burglary #2

 

  Assign to zones that are used for entry and exit and require more time than the primary entry/exit point.  

  Provides a secondary entry delay, in same manner as entry delay #1.  

  Entry delay #2 is programmable for each partition. 

  Exit delay is same as described for Type 01.

 

Type 03 

Perimeter Burglary

 

  Assign to all sensors or contacts on exterior doors and windows. 

  Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay, or Instant 

modes. 

 

Type 04 

Interior Follower

 

  Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon 

entry (to and from the touchpad). 

  Provides a delayed alarm (using the programmed entry/exit time) if the entry/exit zone is faulted first. 

Otherwise this zone type gives an instant alarm.  

  Active when the panel is armed in the Away mode.  

  Bypassed automatically when the panel is armed in the Stay or Instant modes. 

 

Type 05 

Trouble by Day/ 

Alarm by Night

 

  Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone covering a 

sensitive area such as a stock room, drug supply room, etc.  

  Can also be used on a sensor or contact in an area where immediate notification of an entry is desired. 

  Provides an instant alarm if faulted when armed in the Away, Stay, or Instant (night) modes.  

  During the disarmed state (day), the system will provide a latched trouble sounding from the touchpad (and 

a central station report, if desired). 

 

Type 06 

24-hour Silent Alarm

 

  Usually assigned to a zone containing an emergency button. 

  Sends a report to the central station but provides no touchpad display or sounding. 

 

Type 07 

24-hour Audible Alarm

 

  Assign to a zone that has an emergency button. 

  Sends a report to the central station, and provides an alarm sound at the touchpad, and an audible 

external alarm. 

 

Type 08 
24-hour  

Auxiliary Alarm

 

  Assign to a zone containing an emergency button, or to a zone containing monitoring devices such as water 

or temperature sensors. 

  Sends a report to the central station and provides an alarm sound at the touchpad. 

(No bell output is 

provided.)

 

 

Type 09 

Fire 

 

  Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm produces a 

pulsing bell output.  

  This zone type is always active and cannot be bypassed.

  

Note: 

Hardwired zone 1 should be used with 2-wire smoke detectors; zones 2-8 can be used with 4-wire 
smoke detectors; any wireless zone can be used as a fire zone.

 

Type 10 

Interior w/Delay

 

  Provides entry delay (using the programmed entry time), if tripped when the panel is armed in the Away 

mode.  

  Entry Delay begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit 

delay zone was tripped first.  

  Bypassed when the panel is armed in the Stay or Instant modes. 

 

Type 12 

Monitor Zone

 

  Works as a dynamic monitor of a zone fault/trouble. In the case of a short/open, the message, "

ALARM-

24 Hr. Non-Burg. -#XXX 

" (where XXX is the zone number) will be sent to the Central Station. The 

system touchpad will display a “check” message indicating the appropriate zone (but touchpad beeping 
does not occur). Upon restoral of the zone, the message, "

RESTORE-24 Hr. Non-Burg. -#XXX 

" will be 

sent to the Central Station.  

  The “check” message will automatically disappear from the touchpad dynamically when the zone restores; 

a user code + off sequence is not needed to reset the zone.  

  Faults of this zone type are independent of the system, and can exist at the time of arming without 

interference. 

  Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon “alarm.”

 

Type 14 

Carbon Monoxide

 

  Assigned to any zone with a carbon monoxide detector.   

  Produces touchpad and detector sounding (does not affect bell output) when this zone type is alarmed.  

  Always active and cannot be bypassed.

 

Type 16 

Fire w/Verification

 

  Provides a fire alarm when zone is shorted, but only after alarm verified.  

  System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent short circuit 

within 90 seconds triggers fire alarm. 

  Provides a trouble response when zone is open.

 

Содержание Entrepreneur 3000EN

Страница 1: ...and System Installation Notes For full installation and programming information please refer to the Installation and Setup Guide K5305V8 or higher ARMED READY 1 2 3 4 5 6 7 8 9 0 STAY BYPASS CHIME IN...

Страница 2: ...ories 25 Recommendations for Proper Protection 27 FCC Industry Canada 27 UL Notices 28 Uploading Downloading via the Internet 29 The Limitations of This Alarm System 30 Summary of Connections 31 Atten...

Страница 3: ...mming Press 80 4229 or 4204 Relay modules powerline carrier devices or on board triggers Zone List Programming Press 81 Zone Lists for relay powerline carrier activation chime zones pager zones etc Al...

Страница 4: ...be 00 for UL Commercial Burg installations 29 Enable IP GSM Communication Device Menu Mode pass through programming This is a Menu Mode command not a data field for programming IP GSM communication de...

Страница 5: ...Open Close Test 3 Alarms Restore Cancel All 4 All except Open Close Test All 5 All All 50 BURGLARY DIAL DELAY 2 0 Delay Time Delay Disable values other than those stated will give unpredictable result...

Страница 6: ...ORE RPT CODE 1 Any non zero entry enables report 71 TROUBLE RESTORE RPT CODE 10 Any non zero entry in first digit enables report 72 BYPASS RESTORE RPT CODE 00 Any non zero entry in first digit enables...

Страница 7: ...use zone list 7 to enter those zones that require unlimited reporting these zones ignore the setting in entry 1 DOWNLOAD INFORMATION 94 95 94 DOWNLOAD PHONE No Enter up to 20 digits 0 9 11 for 12 for...

Страница 8: ...able 1 enabled 181 50 60 HERTZ AC OPERATION 0 0 60 Hz 1 50 Hz CONFIGURABLE ZONE TYPE OPTIONS 183 181 182 CONFIGURABLE ZONE TYPE 90 IMPORTANT Be careful when selecting combinations of options for confi...

Страница 9: ...e Refer to the communication device s installation instructions for details on enabling the Remote Services feature TOUCHPAD OPTIONS 190 196 NOTE Options for touchpad 1 address 16 are set by the facto...

Страница 10: ...6 Short dial delay fault delay ENTRY 7 ENTRY 8 Display Faults Power Reset Verification Use Entry Delay 1 2 Use Exit Delay Respond as Interior Type 0 show alarms when armed disarmed 1 don t show alarm...

Страница 11: ...1 57 1 BR 1 58 1 BR 1 59 1 BR 1 60 1 BR 1 61 1 BR 1 62 1 BR 1 63 1 BR 1 64 1 BR 1 95 09 N A N A N A touchpad 1 96 N A N A N A touchpad 3 99 07 N A N A N A touchpad NOTES Zone Type see chart on page 12...

Страница 12: ...10 MAPPING Must program before using 80 OUTPUT TYPE OUTPUT TYPE Relay X10 Relay X10 Output No Module Addr Pos 1 4 Unit No Description Output No Module Addr Pos 1 4 Unit No Description 01 09 02 10 03 1...

Страница 13: ...or Zone Types are 00 Not Used 05 Trouble Day Alarm Night 10 Interior w Delay 24 Silent Burglary 01 Entry Exit 1 06 24 Hr Silent 12 Monitor Zone 25 24 Hr Non Alarm 02 Entry Exit 2 07 24 Hr Audible 14 C...

Страница 14: ...07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Events Master Installer Installer Only 00 clear event 04 forced STAY arm 10 display custom words 8 10 01 device on off 05...

Страница 15: ...has an emergency button Sends a report to the central station and provides an alarm sound at the touchpad and an audible external alarm Type 08 24 hour Auxiliary Alarm Assign to a zone containing an e...

Страница 16: ...may not be used as fire or burglary zones in fire or UL burglar alarm installations The system can still be armed when these zone types are in a faulted condition Table of Device Addresses This Device...

Страница 17: ...L 153 POWER R 155 RADIO 156 REAR 157 RECREATION 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF S 164 SAFE 165 SCREEN 166 SENSOR 167 SERVICE 168 SHED 169 SHOCK 170 SHOP 171 SHORT 173 SIDE 174 SKY...

Страница 18: ...that the board rests on the correct row see Detail A b Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws see Detail B Notes Before in...

Страница 19: ...resistance to damage from generally expected levels of lightning and electrical discharge and does not normally require an earth ground If an earth ground is desired for additional protection in area...

Страница 20: ...For additional information regarding the 5800TM refer to the 5800TM s instructions Transmitters ULC Note for Canadian Units In accordance with ULC standards the RF supervision period for this control...

Страница 21: ...ENROLL AS RF 5801 ENROLL AS UR OR RF 5800SS1 ENROLL AS RF LOOP 3 LOOP 1 LOOP 2 LOOP 4 YOU MUST ENROLL THIS BUTTON 5894PI ENROLL AS RF 5802 MN2 ENROLL AS UR OR RF LOOP 1 LOOP 1 LOOPS 1 3 LOOP 1 LOOP 1...

Страница 22: ...keyswitch zone must be programmed to send opening and closing signals a UL commercial burglar alarm installation the keyswitch s tamper switch must be connected in to the alarm system This tamper swit...

Страница 23: ...h aabout a twice per minute beeping at the touchpad indicates that a low battery condition exists in the wireless sensor displayed zone 00 indicates a wireless touchpad If the battery is not replaced...

Страница 24: ...rn on and a LOW BATTERY report will be transmitted with a TEST report The touchpad will beep once about every 30 seconds as a reminder that the system is in the Test mode NOTE Wireless motion detector...

Страница 25: ...es not confirm report transmissions 1 DIAL 0 WALK no special display on English Display Touchpads displays DISARMED READY TO ARM The following will be displayed accompanied by 2 beeps if test is succe...

Страница 26: ...ers 6150RFADT 6160RF 6270ADT Touch Screen Touchpad iCenter Advanced User Interface RF Receivers 5881L 5882L accepts up to 8 transmitters 5881M 5882M accepts up to 16 transmitters 5881H 5882H accepts u...

Страница 27: ...in any room where an alarm control is located or in any room where alarm control connections to an AC source or phone lines are made If detectors are not so located a fire within the room could preven...

Страница 28: ...radation du service dans certaines situations Les r parations de mat riel nomologu doivent tre coordonn es par un repr sentant d sign par le fournisseur L entreprise de t l communications peut demande...

Страница 29: ...nt 7845GSMADT System Requirements Internet Communication At the Installation Site Appropriate Internet Communication Module 7720P Programmer Broadband Internet Access for wired modules Broadband Cable...

Страница 30: ...s closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their detec...

Страница 31: ...MINALS SEE INSTRUCTIONS REMOTE TOUCHPADS EACH PARTITION CAN USE 6150ADT OR 6160ADT TOUCHPADS SEE INSTRUCTIONS PROVIDED WITH TOUCHPAD LOCAL PROGRAMMING MUST BE DONE WITH A 6160ADT BUT NEED NOT REMAIN I...

Страница 32: ...ORMATION For the latest warranty information please go to www honeywell com security hsc resources wa ADT Security Services Inc One Town Center Rd Boca Raton FL 33486 Copyright 2003 K9287V6 K9287V6 8...

Отзывы: