PROGRAMMING FIELDS  

 Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults. 

Field  Function 

Data Entries 

Programmable Values 

 

SYSTEM SETUP (

20–

29) 

20

  INSTALLER CODE

 

    |    |    |  

 

  [6321]

 

4 digits, 0000–9999  
(the factory default installer code should be changed)

 

21

  QUICK ARM ENABLE

 

 

 

  

 

 

 

  

   

 [1,1] 

Part. 1  Part.2

 

0 = no; 1 = yes

 

22

  RF JAM OPTION

 

 

 

  

  [0]

 

0 = no RF Jam detection; 1 = send RF Jam report 

 UL: must be 1 if wireless devices are used

 

 

23

  QUICK (FORCED) BYPASS

 

 

 

  

 

 

 

  

   

[1,1] 

Part. 1  Part. 2

 

0 = no quick bypass  UL: must be “0” 
1 = allow quick bypass (code + [6] + [#] )

 

 24

  RF HOUSE ID CODE

 

   |          |         |      

Part. 1   Part. 2   Common

 

00 = disable all wireless touchpad usage 
01–31 = using 5827, 5827BD or 5804BD touchpad 
[00,00,00]

 

 

26

  CHIME BY ZONE / KP SOUND  

 

ENABLES

 

 

 

  

 

 

 

  

 

[6,7]

 

  1 

2

 

 

 

For each entry, enter the sum of the desired options. 
Example Entry 1: for Chime by Zone and System Low 
Battery sounding, enter 5. To enable all options, enter 7. 

 

Entry 1 

0 =  no Entry 1 touchpad trouble sounds AND no chime 

by zone (touchpad chimes on fault of any entry/exit 
or perimeter zone when chime mode is on) 

1 =  Chime by Zone enabled (select zones to chime on 

zone list 3, using *81 Menu mode) 

2 =  Long Range Radio Trouble sounding enabled (for 

communication devices such as GSMV-ADT) 

4 =  System Low Battery sounding enabled 
7 =  select all entry 1 options 

 

Entry 2 

0 =  no Entry 2 touchpad trouble sounds  
1 =  RF Supervision sounding enabled 
2 =  RF Low Battery sounding enabled 
4 =  RF Jam sounding enabled 
7 =  select all entry 2 options

 

 

27 

POWERLINE CARRIER DEVICE (X-10) 
HOUSE CODE

 

 

 

  

 

[0]

 

0 = A, 1 = B, 2 = C, 3  = D, 4 = E, 5  = F, 6 = G,  
7 = H, 8 = I, 9 = J, #10 = K, #11 = L, #12 = M, #13 = N, 
 #14 = O, #15 = P UL: not for fire or UL installations

 

 

28

  ACCESS CODE FOR 

 

PHONE MODULE

 

   |      [00] 

(Partition 1 only)

 

00 = disable; 1st digit: enter 1–9; 2nd digit: enter # + 11 
for "

", or # + 12 for "#". 

 UL: must be “00” for UL Commercial Burg. installations

 

 

29

 Enable IP/GSM? – Communication Device Menu Mode (pass-through programming)  

This is a Menu Mode command, not a data 

field, for programming IP/GSM communication device options. See 

29 Menu Mode section in the Installation and Setup Guide for 

procedures.  

ZONE SOUNDS AND TIMING (

31 – 

39)

 

31

  SINGLE ALARM SOUNDING per ZONE

 

 

 

  

   [0]

 

0 = unlimited sounding; 1 = one sounding per zone 

SIA NOTE: If “0” selected, “alarm sounding per zone” will be the 
same as the “number of reports in armed period” set in field *93 
(1 if one report, 2 if 2 reports, unlimited for zones in zone list 7). 

 

 

32

  FIRE ALARM SOUNDER TIMEOUT

 

 

 

  

    [0]

 

0 = sounder stops at timeout;  
1 = no sounder timeout UL: must be “1” for fire install.

 

 

33

  ALARM SOUNDER (BELL) TIMEOUT

 

 

 

  

   [1]

 

0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4  = 16 min; 

UL: For residential fire alarm installation, must be set for a 
minimum of 4 min (option 1); for UL Commercial Burglary 
installations, must be minimum 16 min (option 4)

 

 

34

  EXIT DELAY

 

   |          |      [60,60] 

Part. 1  Part. 2     
(entries less than 45 will result 
in a 45-second delay)

 

45 - 96 = 45 - 96 seconds; 97 = 120 seconds

 

 

SIA Installations: minimum exit delay is 45 seconds 

UL: see inst. instr. for requirements. 

Common zones use same delay as partition 1.

 

 

35 

ENTRY DELAY 1 (zone type 01)

 

   |         |      [30,30] 

Part. 1  Part. 2   

 

Common zones use same 
delay as partition 1. 

 

(entries less than 30 will result 
in a 30-second delay)

 

30 - 96 = 30 - 96 seconds 
97 = 120 seconds 

SIA Installations:

  

98 = 180 seconds 

minimum entry delay is

 

99 = 240 seconds 

30 seconds

 

For UL Residential Burglary Alarm installations, must be set for 
a maximum of 30 seconds; entry delay plus dial delay should not 
exceed 1 min. For UL Commercial Burglar Alarm, total entry 
delay may not exceed 45 seconds.

 

 

36 

ENTRY DELAY 2 (zone type 02)

 

   |          |      [30,30] 

Part. 1  Part. 2     

 

See *35 Entry Delay 1 above for entries.

 

38

  CONFIRMATION OF ARMING DING

 

 

 

  

  

 

 

  

  [0,0] 

Part. 1  Part. 2 

 

0 = no; 1 = yes (wired touchpads and RF)  
2 = yes, RF only (except 5827, 5827BD) 

UL: must be “1” for UL Commercial Burglar Alarm inst.

 

 

Содержание Entrepreneur 3000EN

Страница 1: ...and System Installation Notes For full installation and programming information please refer to the Installation and Setup Guide K5305V8 or higher ARMED READY 1 2 3 4 5 6 7 8 9 0 STAY BYPASS CHIME IN...

Страница 2: ...ories 25 Recommendations for Proper Protection 27 FCC Industry Canada 27 UL Notices 28 Uploading Downloading via the Internet 29 The Limitations of This Alarm System 30 Summary of Connections 31 Atten...

Страница 3: ...mming Press 80 4229 or 4204 Relay modules powerline carrier devices or on board triggers Zone List Programming Press 81 Zone Lists for relay powerline carrier activation chime zones pager zones etc Al...

Страница 4: ...be 00 for UL Commercial Burg installations 29 Enable IP GSM Communication Device Menu Mode pass through programming This is a Menu Mode command not a data field for programming IP GSM communication de...

Страница 5: ...Open Close Test 3 Alarms Restore Cancel All 4 All except Open Close Test All 5 All All 50 BURGLARY DIAL DELAY 2 0 Delay Time Delay Disable values other than those stated will give unpredictable result...

Страница 6: ...ORE RPT CODE 1 Any non zero entry enables report 71 TROUBLE RESTORE RPT CODE 10 Any non zero entry in first digit enables report 72 BYPASS RESTORE RPT CODE 00 Any non zero entry in first digit enables...

Страница 7: ...use zone list 7 to enter those zones that require unlimited reporting these zones ignore the setting in entry 1 DOWNLOAD INFORMATION 94 95 94 DOWNLOAD PHONE No Enter up to 20 digits 0 9 11 for 12 for...

Страница 8: ...able 1 enabled 181 50 60 HERTZ AC OPERATION 0 0 60 Hz 1 50 Hz CONFIGURABLE ZONE TYPE OPTIONS 183 181 182 CONFIGURABLE ZONE TYPE 90 IMPORTANT Be careful when selecting combinations of options for confi...

Страница 9: ...e Refer to the communication device s installation instructions for details on enabling the Remote Services feature TOUCHPAD OPTIONS 190 196 NOTE Options for touchpad 1 address 16 are set by the facto...

Страница 10: ...6 Short dial delay fault delay ENTRY 7 ENTRY 8 Display Faults Power Reset Verification Use Entry Delay 1 2 Use Exit Delay Respond as Interior Type 0 show alarms when armed disarmed 1 don t show alarm...

Страница 11: ...1 57 1 BR 1 58 1 BR 1 59 1 BR 1 60 1 BR 1 61 1 BR 1 62 1 BR 1 63 1 BR 1 64 1 BR 1 95 09 N A N A N A touchpad 1 96 N A N A N A touchpad 3 99 07 N A N A N A touchpad NOTES Zone Type see chart on page 12...

Страница 12: ...10 MAPPING Must program before using 80 OUTPUT TYPE OUTPUT TYPE Relay X10 Relay X10 Output No Module Addr Pos 1 4 Unit No Description Output No Module Addr Pos 1 4 Unit No Description 01 09 02 10 03 1...

Страница 13: ...or Zone Types are 00 Not Used 05 Trouble Day Alarm Night 10 Interior w Delay 24 Silent Burglary 01 Entry Exit 1 06 24 Hr Silent 12 Monitor Zone 25 24 Hr Non Alarm 02 Entry Exit 2 07 24 Hr Audible 14 C...

Страница 14: ...07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Events Master Installer Installer Only 00 clear event 04 forced STAY arm 10 display custom words 8 10 01 device on off 05...

Страница 15: ...has an emergency button Sends a report to the central station and provides an alarm sound at the touchpad and an audible external alarm Type 08 24 hour Auxiliary Alarm Assign to a zone containing an e...

Страница 16: ...may not be used as fire or burglary zones in fire or UL burglar alarm installations The system can still be armed when these zone types are in a faulted condition Table of Device Addresses This Device...

Страница 17: ...L 153 POWER R 155 RADIO 156 REAR 157 RECREATION 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF S 164 SAFE 165 SCREEN 166 SENSOR 167 SERVICE 168 SHED 169 SHOCK 170 SHOP 171 SHORT 173 SIDE 174 SKY...

Страница 18: ...that the board rests on the correct row see Detail A b Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws see Detail B Notes Before in...

Страница 19: ...resistance to damage from generally expected levels of lightning and electrical discharge and does not normally require an earth ground If an earth ground is desired for additional protection in area...

Страница 20: ...For additional information regarding the 5800TM refer to the 5800TM s instructions Transmitters ULC Note for Canadian Units In accordance with ULC standards the RF supervision period for this control...

Страница 21: ...ENROLL AS RF 5801 ENROLL AS UR OR RF 5800SS1 ENROLL AS RF LOOP 3 LOOP 1 LOOP 2 LOOP 4 YOU MUST ENROLL THIS BUTTON 5894PI ENROLL AS RF 5802 MN2 ENROLL AS UR OR RF LOOP 1 LOOP 1 LOOPS 1 3 LOOP 1 LOOP 1...

Страница 22: ...keyswitch zone must be programmed to send opening and closing signals a UL commercial burglar alarm installation the keyswitch s tamper switch must be connected in to the alarm system This tamper swit...

Страница 23: ...h aabout a twice per minute beeping at the touchpad indicates that a low battery condition exists in the wireless sensor displayed zone 00 indicates a wireless touchpad If the battery is not replaced...

Страница 24: ...rn on and a LOW BATTERY report will be transmitted with a TEST report The touchpad will beep once about every 30 seconds as a reminder that the system is in the Test mode NOTE Wireless motion detector...

Страница 25: ...es not confirm report transmissions 1 DIAL 0 WALK no special display on English Display Touchpads displays DISARMED READY TO ARM The following will be displayed accompanied by 2 beeps if test is succe...

Страница 26: ...ers 6150RFADT 6160RF 6270ADT Touch Screen Touchpad iCenter Advanced User Interface RF Receivers 5881L 5882L accepts up to 8 transmitters 5881M 5882M accepts up to 16 transmitters 5881H 5882H accepts u...

Страница 27: ...in any room where an alarm control is located or in any room where alarm control connections to an AC source or phone lines are made If detectors are not so located a fire within the room could preven...

Страница 28: ...radation du service dans certaines situations Les r parations de mat riel nomologu doivent tre coordonn es par un repr sentant d sign par le fournisseur L entreprise de t l communications peut demande...

Страница 29: ...nt 7845GSMADT System Requirements Internet Communication At the Installation Site Appropriate Internet Communication Module 7720P Programmer Broadband Internet Access for wired modules Broadband Cable...

Страница 30: ...s closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their detec...

Страница 31: ...MINALS SEE INSTRUCTIONS REMOTE TOUCHPADS EACH PARTITION CAN USE 6150ADT OR 6160ADT TOUCHPADS SEE INSTRUCTIONS PROVIDED WITH TOUCHPAD LOCAL PROGRAMMING MUST BE DONE WITH A 6160ADT BUT NEED NOT REMAIN I...

Страница 32: ...ORMATION For the latest warranty information please go to www honeywell com security hsc resources wa ADT Security Services Inc One Town Center Rd Boca Raton FL 33486 Copyright 2003 K9287V6 K9287V6 8...

Отзывы: