5
–
✱
39
POWER UP IN PREVIOUS STATE
N/A
Feature always enabled; field removed in this control.
DIALER PROGRAMMING (
✱
40 –
✱
42)
Enter the number of digits shown. Do not fill unused spaces. Enter 0–9; #+11 for '
✱
'; #+12 for '#'; #+13 for a 2-second pause.
IMPORTANT:
The
reporting format
for the Safewatch Pro 3000EN is factory-set as 4-digit Contact ID format for both primary and secondary
phone numbers and cannot be changed. Previous versions of this control panel used field *48 (now deleted) to select the reporting format.
✱
40
PABX ACCESS CODE or CALL
WAITING DISABLE
IMPORTANT:
Using Call Waiting Disable on a
non-call waiting line will prevent successful
communication to the central station.
| | | | | Enter up to 6 digits.
If fewer than 6 digits, exit by pressing [
∗
].
Clear entries by pressing
✱
40
✱
.
SIA Installations: If call waiting is used, enter call waiting disable digits “
∗
(#+11) 70”
plus “# + 13” (pause) and set call waiting disable option in field *91.
NOTE: The call waiting disable feature cannot be used on a PABX line.
✱
41
PRIMARY PHONE No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits; Do not fill unused spaces. If fewer than 20 digits entered, exit by pressing [
∗
]. To
clear entries, press
✱
41
✱
.
✱
42
SECONDARY PHONE No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits; Do not fill unused spaces. If fewer than 20 digits entered, exit by pressing [
∗
]. To clear
entries, press
✱
42
✱
.
NOTE:
Entry of a number other than one specified will give unpredictable results.
For fields *43 and *45:
Enter 0–9; #+11 for B; #+12 for C; #+13 for D; #+14 for E; #+15 for F. To clear entries from field, press *43* or *45*.
Examples: For Acct.
1234
, enter:
1 | 2 | 3 | 4
; For Acct.
B234
, enter:
#+11| 2 | 3 | 4
✱
43
SUBSCRIBER ID # (Part.1)
| | |
Enter only 4 digits (report format factory-set as 4-digit
Contact ID format). See box above for entries.
✱
45
SUBSCRIBER ID # (Part. 2)
| | |
Enter only 4 digits (report format factory-set as 4-digit
Contact ID format). See box above for entries.
✱
47
PHONE SYSTEM SELECT
[3]
If Cent. Sta. IS NOT on a WATS line:
0=Pulse Dial; 1=Tone Dial;
if Cent. Sta. IS
on
a WATS line:
2 = Pulse Dial; 3 = Tone Dial
✱
49
SPLIT/DUAL REPORTING
[0]
0 = Disable (Backup report only)
Primary Phone No.
Second Phone No.
1 = Alarms, Restore, Cancel
Others
2 = All except Open/Close, Test
Open/Close, Test
3 = Alarms, Restore, Cancel
All
4 = All except Open/Close, Test
All
5 = All
All
✱
50
BURGLARY DIAL DELAY
[2,0]
Delay Time
Delay Disable
(values other than those stated
will give unpredictable results)
UL: Dial delay plus entry delay
must not exceed one minute;
use zone list 6 to disable dial
delay from appropriate zones, if
necessary.
Entry 1 – Delay Time:
1 = 15 seconds
SIA Installations: delay
2 = 30 seconds
must be minimum of
3 = 45 seconds
15 seconds
Entry 2 – Delay Disable:
0 = use delay set in entry 1
1 = dial delay disabled for zones listed in zone list 6
(use zone list 6 to enter those zones that require
dial delay to be disabled; these zones ignore the
setting in entry 1)
✱
53
MISC. FAULT DELAY TIME
(Zone Type 25 or Configurable Zone Type)
[0]
UL: may only be used on non-
burglar alarm/ non-fire alarm
zones when used in fire and/or
UL burglar alarm installation
0 = 15 seconds
6 = 2-1/2 min
#+12 = 8 min
1 = 30 seconds
7 = 3 min
#+13 = 10 min
2 = 45 seconds
8 = 4 min
#+14 = 12 min
3 = 60 seconds
9 = 5 min
#+15 = 15 min
4 = 90 seconds
#+10 = 6 min
5 = 2 minutes
#+11 = 7 min
✱
54
DYNAMIC SIGNALING DELAY
[0]
Select delay from 0 to 225 secs, in 15-sec increments.
0 = no delay (both signals sent), 1 = 15 secs,
2 = 30 secs, 3 = 45 secs, etc.
UL: for installations with line security, must be “0.”
✱
55
DYNAMIC SIGNALING PRIORITY
(and AAV PATH SELECT)
[0]
0 = Primary Dialer first / AAV via phone line
1 = Communication Device (LRR) first / AAV via
communication device path
For UL Commercial Burglary installations that use a
DACT and LRR, this field must be “0”.
✱
56,
✱
57,
✱
58
MENU MODES
These are Menu Mode commands, not data fields, for Zone Programming, Function
Key Programming, and Expert Mode Zone Programming respectively. See their
respective sections in the Installation and Setup Guide for procedures.
SYSTEM STATUS, & RESTORE REPORT CODES (
∗
∗
∗
∗
59 –
∗
∗
∗
∗
68,
∗
∗
∗
∗
70 -
∗
∗
∗
∗
76, &
∗
∗
∗
∗
89) FOR CONTACT ID® REPORTING:
Enter any digit (other than "0") in the
first
box, to enable zone to report (entries in the
second
boxes will be ignored).
UL:
Also see installation instructions K5305V4 for requirements. † Required for UL commercial burglar alarm installations.
†† Required for UL commercial burglar alarm and residential fire alarm installations.
✱
59
EXIT ERROR ALARM REPORT CODE
[1]
SIA NOTE: Always enabled. Sends both exit error
and
zone
alarm reports in the event of an exit error condition. Also see
field *69.