Adey FL1-03-06631 Скачать руководство пользователя страница 2

2

Contents

Checklist 

        

3

Location 

        

4

Key 

Features 

       

5

Unit 

Installation 

       

6

Electrical 

Installation/Earthing 

      

8

Controller Wiring Diagrams 

10 

Operation 

        

11

Controller 

Programming 

Parameters 

     

12

Filtration & Pressure Differential Monitoring 

 

 

 

 

19

Flow & Temperature Measurement 

20 

Maintenance 

Servicing 

      

21

Environment 

Protection 

      

23

Technical 

Specification 

      

24

Troubleshooting 

Guide 

      

26

UK 

Declaration 

of 

Conformity 

     

28

Product Description

Heating & chilled system sidestream and pumped sidestream filtration units with integrated 

MagnaClean 

CMX Midi

 filter; automated control system with BMS connectivity options providing connected system/

filtration monitoring via constant system flow, pressure differential and temperature sensing.

Application

The 

MagnaClean CMX Midi Pro 

Midi Pro Assist

 Sidestream filters provide high performance, 

sidestream filtration for all heating & chilled systems. Featuring a high performance 

MagnaClean CMX 

Midi 

filter, the option of an integrated Grundfos UPM3 Flex AS pump for pumped, assisted filtration 

and the security of system flow, pressure differential and temperature sensing with full BMS alarm 
connectivity, these solutions are designed to actively monitor the system and the active filtration of 
any heating or chilled system in a sidestream configuration for 24 hours a day.

Transport/Storage 

These units are heavy - care should be taken during lifting & handling. During transportation, 
secure the units properly to prevent any damage. If this product is not being installed immediately, 
ensure it is stored in a dry, frost & vibration-free location in its original packaging.

The WEEE symbol on this product indicates that the product must not be disposed of with normal 
household waste. Instead such marked waste equipment must be disposed of by arranging to return 
to a designated collection point for the recycling of waste electrical and electronic equipment.
This 

MagnaClean CMX

 

Midi

 filter contains a strong magnet.  

Keep away from all electrical devices, bank cards and other magnetic devices.
This 

MagnaClean CMX

 

Midi

 filter contains a strong magnet.  

Caution should be taken at all times when handling if you have a pacemaker fitted.
This 

MagnaClean CMX

 

Midi

 filter is a pressurised device. 

Always release pressure before servicing. 
The filter unit may be hot in operation.  
Handle with care.

THIS PRODUCT COMPLIES WITH ALL CURRENT UK and EU PRODUCT LEGISLATION. 

Содержание FL1-03-06631

Страница 1: ...1 MIDI PRO ASSIST MIDI PRO Sidestream Monitored Filtration Installation and servicing MagnaClean CMX Commercial...

Страница 2: ...sing with full BMS alarm connectivity these solutions are designed to actively monitor the system and the active filtration of any heating or chilled system in a sidestream configuration for 24 hours...

Страница 3: ...Children should be supervised to ensure that they do not play with the appliance Please read installation details carefully as they are intended to ensure this product provides long trouble free servi...

Страница 4: ...se sidestream skid units should be installed on a solid level floor which is able to support the filled weight of the unit of c 41 44kg dependent on the model being installed Please also ensure that m...

Страница 5: ...flow and temperature sensor based on the principle of vortex shedding behind a bluff body The VFS sensor is fully compatible with wet aggressive liquids constantly monitoring system flow through the...

Страница 6: ...t IMPORTANT As this unit is driven by an integrated pump both the unit inlet outlet connections must both be connected to EITHER the main system flow OR the system return as indicated below in Fig 4 T...

Страница 7: ...f the unit No special equipment or tools are required for installation This unit can be connected to a heating or chilled system in any location in a sidestream configuration via the two 28mm compress...

Страница 8: ...cord Pipework Copper or metallic pipework must have supplementary earth bonding where the continuity has been broken by flexible hoses or plastic components Additional earthing Certain installations m...

Страница 9: ...nsure compliance with the electrical standard EN60335 1 It is essential that prior to any disturbance of this internal wiring all cable routing and securing details are carefully noted to ensure re as...

Страница 10: ...10 6 Controller Wiring Diagram MagnaClean CMX Midi Pro Assist FL1 03 06632 Fig 6 Controller Wiring Diagram MagnaClean CMX Midi Pro FL1 03 06631 Fig 7...

Страница 11: ...re differential across the inlet and outlet of the MagnaClean CMX Midi filter via the integrated Grundfos DPS Sensor providing warning alerts and alarms at two levels Grundfos VFS Flow Sensor a A warn...

Страница 12: ...E TIME DATE PROGRAMMING MODE a Press UP Button 1 to increase the value If held will cycle through menu options automatically release button when desired value is achieved b Press DOWN Button 3 to decr...

Страница 13: ...asurement Y Y N 7 Low Flow Warning Low Flow warning value 10 0 200L 8 Low Flow Alarm Low Flow alarm value 0 0 200L 9 Sensor Minimum Pressure Maximum pressure value of sensor The default value of 0 0 b...

Страница 14: ...on Default Range P1 Cartridge Present Monitors presence of a filter cartridge No Yes No P4 ID Number Address for ModBus 0 0 99 P5 Battery Activation Enable or disable the battery maintains date time s...

Страница 15: ...Hours Total pump operation time Auto Update 0 999 1 24 hrs DL4 Current water flow I min Flow rate through sensor at that point in time Auto Update DL5 Water Volume in last 24 hours Amount of water th...

Страница 16: ...X 10 Bar Parameter Minimum Pressure 6 0 Parameter Minimum Pressure 60 40011 Parameter Temperature Alarm Enable read write word 16 bits 4 No 5 Yes 44685 00 4 5 40012 Parameter Low Temperature Alarm rea...

Страница 17: ...lue X year 0 99 0 99 40043 Actual Hours read write word 16 bits Value X hours 0 23 0 23 40044 Actual Minutes read write word 16 bits Value X min 0 59 0 59 40045 Pump Status read word 16 bits 0 OFF 1 O...

Страница 18: ...ol will not clear error until new service date entered Filter Service Required N Pump OFF Buzzer ON LED Light ON Common Alarm ON Low Flow Warning Low flow warning value has been reached Low Flow Warni...

Страница 19: ...sure measurement across the filter as there is no distinguishable pressure drop across the filter without cartridges installed even when they are full of captured magnetic debris These time based alar...

Страница 20: ...n 3 4 2 Chemical dosing facilities BG29 2021 Section 2 3 8 and BG50 2021 Section 3 4 3 Corrosion monitoring technology and services BG 29 2021 Section 2 3 8 The additional features of these products a...

Страница 21: ...s at the top of the unit to isolate the filter from the main system 5 Undo the wing nut remove the compression plate Carefully remove the magnet assembly from the filter 8 Place the springs into the t...

Страница 22: ...ensuring that the lid gasket is positioned and installed correctly Re attach the lid clamp and tighten 11 Ensure filter drain port valve s are closed and then open both isolation valves at the top of...

Страница 23: ...ce free However it might be necessary to deblock or to open the pump for example if it is blocked by impurities De blocking is possible by opening the de blocking screw at the front 1 Unscrew the de b...

Страница 24: ...utlet 28mm compression Isolation Valves Pump Pump model Grundfos UPM3 FLEX AS 25 70 130 Pump type Circulation PWM A Pump head material Electrocoated Cast Iron Impeller material Composite PES 30 GF Min...

Страница 25: ...ture Min 2 C Max 40 C Min Max water temperature Min 2 C Max 100 C Connections Inlet outlet 28mm compression Isolation Valves System Monitoring Differential Pressure Sensor Grundfos DPS Sensor Vortex F...

Страница 26: ...ce interval date Pump is blocked with impurities Unblock the pump and remove impurities Pump is defective Replace pump contact ADEY Customer Services PUMP RUNS AT MAX SPEED CANNOT BE CONTROLLED No sig...

Страница 27: ...y is defined by the sequence of the table Operating Panel LED1 LED2 LED3 LED4 LED5 Indication Pump Operation Remedy Rotor is blocked Trying to start again every 1 33 seconds Wait or unblock the rotor...