ADEY DEK1002 MODBUS PROTOCOL - VARIABLE LIST
DEFAULT SETTINGS
BAUD RATE
9600
WORD LENGTH
8
PARITY
NO
STOP BITS
1
X Variable
Address
Denomination
Type
X Variable
Format
Data Conversion
Units
Equivalent
Range
Range of
X Variable
Notes
40001
Cartridge Present
read/write word 16 bits 4 = No 5 = Yes
6 = FastFast
4->6
4->6
40002
Magnet Only Service Warning
read/write word 16 bits 11 = Daily 12 = Weekly
13 = Monthly
11->13
11->13
40003
Magnet Only Service Warning
Duration
read/write word 16 bits Value = X
1->12
1->12
40004
Parameter Pressure Difference
Warning
read/write word 16 bits Value = X/10
Bar
0,1-0,6
1-6
40005
Parameter Pressure Difference
read/write word 16 bits Value = X/10
Bar
0,1-6,0
1-60
40006
Parameter Flow Monitoring
Enable
read/write word 16 bits 4 = No 5 = Yes
4-5
4-5
40007
Parameter Low Flow Warning
read/write word 16 bits Value = X
l/min
“0->
Parameter
Low Flow
Alarm”
“0->
Parameter
Low Flow
Alarm”
40008
Parameter Low Flow Alarm
read/write word 16 bits Value = X
l/min
Parameter
Low Flow
Warning ->
200
Parameter
Low Flow
Warning ->
200
40009
Parameter Minimum Pressure
read/write word 16 bits Value = X/10
Bar
“0 ->
Parameter
Maximum
Pressure”
“0 ->
Parameter
Maximum
Pressure”
40010
Parameter Maximum Pressure
read/write word 16 bits Value = X/10
Bar
“Parameter
Minimum
Pressure
>-6,0”
“Parameter
Minimum
Pressure
->60”
40011
Parameter Temperature Alarm
Enable
read/write word 16 bits 4 = No 5 = Yes
44685.00
4-5
40012
Parameter Low Temperature
Alarm
read/write word 16 bits Value = X
°C
“0->
Parameter
High Temp
Alarm”
“0->
Parameter
High Temp
Alarm”
40013
Parameter High Temperature
Alarm
read/write word 16 bits Value = X
°C
“Parameter
Low Temp
Alarm >120”
“Parameter
Low Temp
Alarm >120”
40014
Parameter Pump Required
read/write word 16 bits 4 = No 5 = Yes
4-5
4-5
40015
Parameter Current Sense Active read/write word 16 bits 4 = No 5 = Yes
4-5
4-5
40016
Parameter Alarm Relay Contact
Type
read/write word 16 bits 0 = Norm. Open
1 = Norm. Close
0-1
0-1
40017
Parameter ID Number
read/write word 16 bits Value = X
0-99
1-99
40018
Parameter Battery Activated
read/write word 16 bits 4 = No 5 = Yes
4-5
4-5
40019
Service Date Day
read/write word 16 bits Value = X
1-31
1-31
40020
Service Date Month
read/write word 16 bits Value = X
1-12
1-12
40021
Service Date Year
read/write word 16 bits Value = X
0-99
0-99
40022
Last Serviced Date Day
read
word 16 bits Value = X
1-31
1-31
40023
Last Serviced Date Month
read
word 16 bits Value = X
1-12
1-12
40024
Last Serviced Date Year
read
word 16 bits Value = X
0-99
0-99
40025
Magnet Only Service Day
read
word 16 bits Value = X
1-31
1-31
40026
Magnet Only Service Month
read
word 16 bits Value = X
1-12
1-12
40027
Magnet Only Service Year
read
word 16 bits Value = X
0-99
0-99