Warning
Conditions for Trigger
Scrolled Message “Auto Reset” “Action on Outputs”
Pump Fail
Current Sense
Parameter = Y
Pump Activated
Current level below
125mA
Pump Fail
N
Pump – OFF
Buzzer – ON
LED Light – ON
Common Alarm – ON
Service
Interval
Alarm
Actual date beyond
Service Date (Control
will not clear error
until new service date
entered)
Filter Service
Required
N
Pump – ON
Buzzer – ON
LED Light – ON
Common Alarm – ON
Magnet-Only
Service
Warning*
Magnet-only service
requirement value has
been reached
Magnet-Only
Service Warning
- Hold MUTE for 5
secs to reset
N
Pump – ON
Buzzer – ON
LED Light – ON
Common Alarm – OFF
Pressure
Differential
Warning
Pressure Differential
Warning value has been
reached
Differential
Pressure Warning
- Check Cartridge
Y
Pump – ON
Buzzer – ON
LED Light – ON
Common Alarm – OFF
Pressure
Differential
Alarm
Pressure Differential
Alarm value has been
reached (Control will
not clear error until new
service date entered)
Filter Service
Required
N
Pump – OFF
Buzzer – ON
LED Light – ON
Common Alarm – ON
Low Flow
Warning
Low flow warning value
has been reached
Low Flow Warning
Y
Pump - ON
Buzzer - ON
LED Light - ON
Common Alarm - OFF
Low Flow
Alarm
Low flow alarm value
has been reached
Low Flow Alarm
Y
Pump - OFF
Buzzer - ON
LED Light - ON
Common Alarm - ON
Low
Temperature
Alarm
Low temperature alarm
value reached
Low Temperature
Warning
Y
Pump – ON
Buzzer – ON
LED Light – ON
Common Alarm – ON
High
Temperature
Alarm
High temperature alarm
value reached
High Temperature
Warning
Y
Pump – ON
Buzzer – ON
LED Light – ON
Common Alarm – ON
*NOTE:
When the
“Magnet-Only Service Warning”
alarm is activated, the alarm is a service reminder
only which can be reset by holding down the MUTE button for 5 seconds. When the alarm is reset
via the mute button, the alarm will reinstate the previous Parameter 2 & 3 values, e.g.
if Parameter 2
is set to
“Weekly”
the controller will provide another warning alarm
in 2 weeks
until/unless default
parameters are manually updated/changed.