– 32 –
Compatible 5800 Series Transmitters
Enter As Input
Model
Product
Device Type
Description
5801
Wireless Panic
UR or RF
• Has four pushbuttons, each with a
Transmitter
unique input (loop) code.
• Programmable
responses (e.g.,
Panic, Arm–Stay, Arm–Away,
Disarm, etc.
5802 Pendant
BR
Only
• Has single pushbutton.
(Personal Emergency
• Usually programmed for response
Transmitter)
type of 24-Hr Audible or 24-Hr Silent
(other zone responses are possible).
• Contains a non-replaceable battery.
At the end of the battery's life, the
entire unit must be replaced.
5802CP
Belt Clip
BR Only
Same as 5802.
(Personal Emergency)
5802MN
Miniature
UR or RF
• Has single pushbutton.
(Personal Emergency
• Usually programmed for a response
Transmitter)
type of 24-Hr. Audible or 24-Hr.
Silent (other zone responses are
possible).
5804
Wireless Key
BR Only
• Has four pushbuttons, each with a
Transmitter
unique input (loop) code.
• Programmable responses (e.g.,
Arm–Stay, Arm–Away, Disarm, etc.).
5806 Wireless
Photoelectric
RF
• One-piece smoke detectors with a
5807
Smoke Detectors
built in transmitter.
5808
Wireless Photoelectric
RF
• One-piece smoke detectors with a
Smoke Detector
built in transmitter.
• Has built-in thermal circuitry to
detect temperatures above 135
°
F,
and tamper switch on base.
5816
Door/Window RF
• Has two unique input (loop) codes:
Transmitter :
one for a wired closed circuit
contact loop; the other for a built-in
reed switch (used in conjunction
with a magnet).
5816
Low Temperature
RF
• Transmits a fault condition when
TEMP
Sensor
temperature drops below 45
°
F.
5817 Multi-Point
RF
• Has three unique input (loop)
Universal Transmitter
codes: one for a "Primary" contact
loop with programmable options;
the others for two "Auxiliary" closed
circuit contact loops.
UL
The 5816 and 5817 do not supervise their loop wiring for shorts. Therefore, for
UL Household Burglary installations, the loop wiring may not exceed 3 feet.