background image

–  24 –

4

3

2

1

ON

OFF

MOUNTING
HOLES

INTERFERENCE 
INDICATOR
LED

CIRCUIT

BOARD

DIP SWITCH

PLUG
&
SOCKET

INSERT IN

RIGHT-HAND
TERMINALS

ANTENNAS

YELLOW
RED
BLACK
GREEN

}

TO CONTROL’S REMOTE
KEYPAD CONNECTION
POINTS. EACH RECEIVER
MUST BE ON INDIVIDUAL
HOME RUN.

WIRING
OPENING

KNOCKOUT
AREA FOR
SURFACE
WIRING

5882
LOCATION

@@@@@@@@e?

@@@@@@@@e?

@@h?

@@h?

@@h?

@@h?

@@h?

@@h?

@@@@@@@@e?

@@@@@@@@e?

@@@@@@@@

@@@@@@@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

?@@

?@@

?@@

?@@

?@@

?@@

?@@@@@@@@

?@@@@@@@@

?@@@@@@@@

?@@@@@@@@

@@g

@@g

@@g

@@g

@@g

@@g

@@@@@@@@

@@@@@@@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

@@

{

TO RELEASE CIRCUIT
BOARD, REMOVE
SCREWS (2) AND BEND
BACK TABS (S)

NOTE: WHEN CIRCUIT BOARD IS
MOUNTED IN CONTROL’S CABINET,
GROUNDING LUGS (2) PROVIDED
MUST BE INSERTED IN LEFT-HANDTER-
MINALS OF ANTENNA BLOCKS AND
SECURED TO CABINET (SEE RECEIV-
ER’S AND CONTROLS INSTRUCTIONS)

Figure 8.  4281, 5881, & 5882 Series Wireless Receivers (cover removed)

Installing the  5800TM Module

Installation of this module is necessary only if you are using one or more
5827BD Wireless Bi-directional keypads.

The 5800TM must be located between one and two feet from the 4281 or 5881
receiver's antennas. 

The 5800TM must not be installed within the control

cabinet.  Mount the unit using its accompanying mounting bracket.

5800TM Wiring

Connections

Connect the 5800TM to the control panel’s keypad connection terminals, using
the supplied connector with flying leads, as follows:

WIRE

TERMINAL ON CONTROL

RED (+12VDC)

Terminal 5

BLACK (Ground)

Terminal 4

GREEN (Data to Control)

Terminal 6

YELLOW (Data from Control)

Terminal 7

BLUE:  Not Used

Do not cut any of the jumpers on the 5800TM when using it with the
VISTA-10SE.

For additional information, refer to the 5800TM’s instructions.

5700 Series Transmitter  Setup

Each 5700 series transmitter has DIP switches to set both the transmitter's
zone number (Transmitter zone/ID) and the system House ID.  The House ID
will be the same for all transmitters and must match the House ID programmed
into the system (in data field 

24) for the wireless receiver.  This can be

likened to a family in which everyone has the same last name (House ID), but
each person has a different first name (Transmitter zone/ID).  The zone/ID
number must then be programmed into the system using 

56 interactive

mode.

A variety of wireless transmitters can be used to make up the wireless zones.
These include window/door units, smoke detectors, PIRs, and panic buttons.
Zone/ID 

number  assignments can be from 10–63 .  Remember, the 5700

system supports up to 8 wireless 

zones, depending on the RF receiver used

(see Table 1 previously).

Содержание N7227V5

Страница 1: ...SE N7227V5 5 97 Installation Instructions Installation Instructions Installation Instructions Security System THIS ISSUE INCLUDES THE NEW QED QUICK ENROLLMENT OF DEVICES PROCEDURE FOR 5800 SERIES TRAN...

Страница 2: ...alarm in the hallway outside may not wake up the sleeper if the door is closed Install a smoke detector inside bedrooms where electrical appliances such as portable heaters air conditioners or humidif...

Страница 3: ...e Smoke Combustion Detectors 19 Programming Hard Wired Zones 19 Programming Panic Keys 20 Check Out Procedure for Hard Wired Zones 1 6 21 Section 5 WIRELESS RF ZONE EXPANSION 5700 5800 RF SYSTEMS 22 W...

Страница 4: ...For Phone Access 47 Checking the Operation of the 4285 Phone module 48 Section 8 EXTERNAL SOUNDERS 49 Compatible Sounders 49 Sounder Connections 50 Programming For External Sounders 50 Testing the Sou...

Страница 5: ...s 74 General Information 74 Arming Functions 74 Panic Keys 75 4285 Phone module if used 75 Relays Outputs if used 75 Exit Alarm Displays if programmed 75 Trouble Conditions 76 General Information 76 C...

Страница 6: ...tary Power Supply for Keypads 17 Figure 7 4 Wire Smoke Detector Connections to Zone 5 18 Figure 8 4281 5881 and 5882 Wireless Receivers cover removed 24 Figure 9 4204 Connections To Control 39 Figure...

Страница 7: ...system at a later time e g adding Wireless zones adding a 4285 Phone module etc Without an understanding of the programming method for this system you will not be able to successfully perform the requ...

Страница 8: ...tical information that if not observed could seriously affect the operation of the system or could cause damage to the system Please read each warning carefully This symbol also denotes warnings about...

Страница 9: ...s Up to 4 of any of the following keypads may be used Fixed Word Keypads 4127 4137AD 6127 6128 and 6137 These keypads cannot be used if the 4285 Phone module is being used Alpha Keypads 5137AD 6139 2...

Страница 10: ...rrupts for smoke detector reset if 4 wire smoke detectors are used Programming Programmed options are stored in electrically erasable non volatile EEROM memory information can be reprogrammed at any t...

Страница 11: ...and No N6277 1 Push On Clip Retainer Clip Note The cabinet can be closed and secured without a lock by using 2 screws in the cover s edge CABINET DOOR BOTTOM RETAINER CLIP RETAINER CLIP NOTE POSITION...

Страница 12: ...switch is set with its position 1 ON to the right as shown in its instructions The tampered cover is necessary for installations outside of the control s cabinet TAMPERE NOT TAMPERED DETAIL C 4219 422...

Страница 13: ...eceiver board and secure them to the cabinet top with the screws provided as shown in Detail D 7 Insert the receiver s antennas through the top of the cabinet into the blocks right hand terminals and...

Страница 14: ...Connections Diagram for location if necessary b Black to the negative battery tab on the control board These wires may have already been connected to the battery tabs on the control board If so disreg...

Страница 15: ...rent draw for all devices can be found in the SPECIFICATIONS AND ACCESSORIES section Note Refer to Auxiliary Device Current Draw Worksheet in the FINAL POWER UP section for current draw for all keypad...

Страница 16: ...f 4 and other devices from the auxiliary power output The backup battery will supply power to these keypads in the event that AC power is lost When the control s auxiliary power load for all devices e...

Страница 17: ...y plugging the AC transformer previously wired to the control into a 120VAC outlet 3 Busy Standby Alpha keypads or dI Fixed word keypads will be displayed After approximately 1 minute the green READY...

Страница 18: ...ces in parallel across the loop The 1 000 ohm EOLR must be connected across the loop wires at the last device If the EOLR is not at the end of the loop the zone will not be properly supervised and the...

Страница 19: ...field 22 a 2 entry the first screen prompt will be Program Tool 0 No 1 Yes Enter 0 No The next prompt will ask you to enter zone number Enter Zn Num 00 Quit 01 Zone Number Enter the first zone number...

Страница 20: ...for the zone that was just programmed If it is programmed satisfactorily press to continue Program Alpha 0 No 1 Yes 0 The next request is to enter Alpha descriptors for the zones The entry may be done...

Страница 21: ...m while No will disable it but retain all data except the original zone type You can then go back to this zone later and put back an active Zone Type to re enable it Check Out Procedure For Hard Wired...

Страница 22: ...ms must use 4281CN series receivers 4281CN L 4281CN M or 4281CN H with Canadian versions of 5700 type transmitters 5800 systems must use 5882 series receivers 5882L or 5882H Information in this manual...

Страница 23: ...itters e g 5802 5802CP 5804 should be periodically tested by the user for battery life Receiver Supervision The receiver itself is supervised A tamper report zone 9 will be generated a If communicatio...

Страница 24: ...the 5800TM to the control panel s keypad connection terminals using the supplied connector with flying leads as follows WIRE TERMINAL ON CONTROL RED 12VDC Terminal 5 BLACK Ground Terminal 4 GREEN Dat...

Страница 25: ...tain range of zone numbers Each range of zone ID numbers is shown below Zone Type Transmitter Zone ID Entry Exit Burg 10 through 47 Perimeter Burg 10 through 47 Interior Burg 10 through 47 32 through...

Страница 26: ...P 42 UP UP UP 43 UP UP 44 UP UP UP 45 UP UP 46 UP UP 47 UP 48 UP UP UP UP 49 U UP UP 50 UP UP UP 51 UP UP 52 UP UP UP 53 UP UP 54 UP UP 55 UP 56 UP UP UP 57 UP UP 58 UP UP 59 UP 60 UP UP 61 UP 62 UP 6...

Страница 27: ...63 Detects the sound and shock of Glassbreak Detector breaking glass and requires the presence of both to initiate an alarm condition 5775 PIR Detector 32 47 Dual element passive infrared detector wi...

Страница 28: ...1 series RF receivers respond only to 5700 transmitters and 5827BD wireless keypads set to the same House ID 01 31 programmed into the control panel This prevents system interference from transmitters...

Страница 29: ...nter another zone number if desired If the zone is not programmed or you want to change it press A prompt for Zone Type will appear Zone Number 20 Zone Type Perimeter 03 Entry for Zone Type 03 shown 7...

Страница 30: ...e first zone number to be viewed and press To view each zone press and the zone number will advance to the next programmed zone When the end of the list is reached press 0 0 to exit This method of exi...

Страница 31: ...The 5816 and 5817 do not supervise their loop wiring for shorts Therefore for UL Household Burglary installations the loop wiring may not exceed 3 ft Programming an RF House ID 01 31 in field 24 is n...

Страница 32: ...ch with a Transmitter unique input loop code Programmable responses e g Arm Stay Arm Away Disarm etc 5806 Wireless Photoelectric RF One piece smoke detectors with a 5807 Smoke Detectors built in trans...

Страница 33: ...ith 5800TM Can indicate system status via its 3 LEDs and sounder Includes 3 panic keys House ID must be set Requires 5800TM Transmitter Module 5850 Glass Break Detector RF Requires both sound and shoc...

Страница 34: ...m it as the tool Batteries can remain in the transmitters after the transmitters have been enrolled into the system However to prevent possible problems make sure these transmitters are not faulted wh...

Страница 35: ...P Rf Trans RF 1 8 Enter the transmitter input device type as follows 3 RF supervised RF transmitter 4 UR unsupervised RF transmitter 5 BR button type RF transmitter unsupervised Refer to the separate...

Страница 36: ...am tool a single short beep will verify the system is ready for enrolling and re activate the proper transmitter or transmitter loop input ZN ZT RC IN L 10 03 00 RF 1 s 13 The summary screen for the z...

Страница 37: ...ode 1 In the programming mode press 5 6 to enter Zone Programming mode 2 Then enter the zone number and press repeatedly until the cursor is under the RF Input Loop L position This is the specific inp...

Страница 38: ...Code 4 2 Once transmitters are placed in their desired locations and the approximate length of wire to be run to sensors is connected to the transmitter s screw terminals fault each transmitter Do no...

Страница 39: ...control panel The following steps should be taken to properly set up the 4204 1 Connect the 4204 to the control s remote keypad terminals 4 7 using the connector supplied with the 4204 Use standard 4...

Страница 40: ...LT Relay action begins upon any opening or short in an assigned zone in the zone list TROUBLE Relay action begins upon any trouble condition in an assigned zone in the zone list NOT USED Relay action...

Страница 41: ...the relay s for starting or stopping some action such as turning lights on or off etc These entries are Security Code 7 and Security Code 8 Note Whichever entry is used to start stop the action canno...

Страница 42: ...1 1 2 or 3 If not used enter 0 Press the key to continue 02 Start Zn Typ Not Used 00 If a zone type or system operation will be used to START the relay action enter the appropriate two digit code see...

Страница 43: ...Zone Lists for Output Relays This interactive mode is applicable only if you have programmed 80 mode Refer to the Programming Form worksheet for 81 Mode Zone List Displays Zone List No 00 Quit 01 Upon...

Страница 44: ...dialing switchable phones must be set for Touch tone temporarily before attempting phone access A Phone Access User s Guide for phone access to the security system is provided with the Phone module f...

Страница 45: ...short to reach their assigned terminals splice additional wires to them as required 4285 WIRING TABLE 4285 Terminal Connects to 1 Phone In Tip Terminal 17 on control 2 Phone In Ring Terminal 18 on con...

Страница 46: ...ELCO LINE NOT INSTALLER ADJUSTABLE UNUSED KEYED HEADER 4285 VOICE MODULE 1 2 3 4 5 6 7 YELLOW TO DATA OUT term 7 NO CONNECTION RED TO AUX term 5 BLACK TO AUX GROUND term 4 GREEN TO DATA IN term 6 CONN...

Страница 47: ...ich the answering machine is set Example if the machine is set for 4 rings use a value of 5 or higher This is recommended so that the Phone module can still be accessed if the answering machine is tur...

Страница 48: ...t phone code entered in field 26 VOICE PHONE MODULE ACCESS CODE If the premises phone system includes an answering machine the 2 digit phone code should be entered during a pause at the beginning of o...

Страница 49: ...watt speaker 1 3 amps current draw Ademco 745X3 Voice Siren Driver 12 volt voice siren driver with English Spanish and French voice messages Separate messages for Fire and Burglary Use with 8 ohm spe...

Страница 50: ...system 2 Enter the programming mode by keying the following on the Alpha keypad INSTALLER code 4 1 1 1 8 0 3 Press 28 Single Alarm Sounding per Zone Armed Period Enter 1 for yes 0 for no default 4 Pre...

Страница 51: ...7720 PLUS 7820 LONG RANGE RADIO BLACK RED GREEN YELLOW 4 5 6 7 CONTROL TERMINALS Figure 12 Long Range Radio Connections Programming for Long Range Radio 1 With at least one keypad connected to the ke...

Страница 52: ...hich signals the 685 receiver at the central station to hold the phone connection for 1 minute Once the digital message is kissed off the control will give up the phone line to the AAV module without...

Страница 53: ...ELAY 1 FOR ANY OTHER PURPOSE 21 Figure 13 Connection Of AAV Unit When Not Using A 4285 Phone module 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 ON MODEL EAGLE SECURITY 1241 GND VDC RING TIP REFER TO AAV MO...

Страница 54: ...on and also to the TROUBLESHOOTING GUIDE section Connecting The Back Up Battery In the event of an AC power loss the Control panel is supported by a back up rechargeable gel cell battery The minimum b...

Страница 55: ...end of the battery connector cable to the battery as follows a Red to the positive terminal on the battery b Black to the negative terminal on the battery AUXILIARY DEVICE CURRENT DRAW WORKSHEET DEVI...

Страница 56: ...f 3 selected from a vocabulary of words stored in memory see the list on a following page In addition up to 5 installer defined words can be added to those already in memory Thus when an alarm or trou...

Страница 57: ...the next zone number for which you wish to enter or check a descriptor A summary display for that zone will appear You must then press plus the same zone number again to gain access to the entry mode...

Страница 58: ...ntering the Zone Descriptors using this method the keypad keys perform the following functions 3 Scrolls both alphabet and actual words in ascending alphabetical order 1 Scrolls both alphabet and actu...

Страница 59: ...n the prompt CUSTOM WORD is displayed 2 Enter the number 1 5 of the custom word or word string to be created for example if you are creating the first custom word or word string enter 1 for the second...

Страница 60: ...NURSERY O 136 OFFICE 138 OPEN 139 OPENING 140 OUTSIDE 142 OVERHEAD P 143 PAINTING 144 PANIC 145 PASSIVE 146 PATIO 147 PERIMETER 148 PHONE 150 POINT 151 POLICE 152 POOL 153 POWER R 155 RADIO 156 REAR R...

Страница 61: ...de by pressing 83 The following prompt will be displayed Program Tool 0 No 1 Yes 0 2 If using a program tool enter 1 If not using a tool enter 0 If a tool has already been programmed this prompt will...

Страница 62: ...tem a single long beep will be heard from the keypad If this happens the system will not display the serial number but will wait for a transmission from another transmitter or transmitter loop input 6...

Страница 63: ...eless zones have been displayed whether enrolled or not the Enter Zn Num prompt will appear Enter 00 to exit the serial number Sequential mode and return to the data field programming mode When you ha...

Страница 64: ...t attempts to the secondary telephone number if programmed to get a valid message through If the panel is not successful after its numerous attempts the keypad will display Communication Failure Alpha...

Страница 65: ...in hex Z Typically Zone Number 2nd digit Gg Test Code 1st 2nd digits Tt Trouble Code 1st 2nd digits R Restore Code Alarm Bb Bypass Code 1st 2nd digits R Tt Restore Code Trbl 1st 2nd digits EAC AC Los...

Страница 66: ...tlet to power up the system 2 Enter the programming mode by keying the following on the Alpha keypad Installer code 4 1 1 1 8 0 Fields 40 41 42 Enter up to the number of digits shown Do not fill unuse...

Страница 67: ...her Reports 2 All except Open Close Test Open Close Test 3 Alarms Restore Cancel All reports 4 All except Open Close Test All reports 5 All reports All reports TO PRIMARY PHONE TO PAGING NUMBER 6 All...

Страница 68: ...ormat Enter a code in the first digit box 1 9 0 B C D E or F Enter 10 for 0 11 for B 12 for C 13 for D 14 for E 15 for F A 0 not 10 in the first digit box will disable a report A 0 not 10 in the secon...

Страница 69: ...the system is not disarmed before that entry delay ends a special message indicating Exit Alarm is sent to the central station and a zone indication and Exit Alarm or EA is displayed on the keypad Fo...

Страница 70: ...lue higher than the number of rings for which the answering machine is set Example if machine is set for 4 rings use value 5 or higher This is recommended so that the Phone module can still be accesse...

Страница 71: ...d units will send signals out only if they have been inactive for 3 minutes 5 Follow the manufacturer s instructions to test all smoke detectors to ensure that all are functioning properly The identif...

Страница 72: ...Checking in this mode not only assists in determining good mounting locations for the transmitters when the system is being installed but also verifies that the RF transmission has sufficient signal a...

Страница 73: ...ystem will emit a single beep when each secondary code has been suc cessfully entered To delete a Secondary security code enter via keypad Master Code CODE key User 3 6 Notes All Master and Secondary...

Страница 74: ...ys depending on keypad type see Panic Keys on next page for silent audible fire or personal emergency alarms These keys can notify the central station of an alarm condition if that service is connecte...

Страница 75: ...keypad Relay Outputs if used If relay outputs are used two keypad entries available to the user are included among the system operation choices 34 and 35 that may be programmed see the RELAY OUTPUTS...

Страница 76: ...e wireless sensor displayed zone 00 indicates a wireless keypad If the battery is not replaced within 30 days a CHECK display may occur Note Some wireless sensors contain a non replaceable long life b...

Страница 77: ...pad 3a Bat or System Lo Bat no zone Nos 3b Bat or Lo Bat 00 3c Bat or Lo Bat nn 3a System battery is low or missing 3b Remote RF keypad battery is low 3c Transmitter for zone nn has a low battery 4 Pe...

Страница 78: ...ght off or NO AC displayed 1a Interrupted AC power supply 1a Check transformer connection and power line circuit breaker 2 Digital communicator mes sage not being received 2a Control in TEST mode 2b T...

Страница 79: ...you quickly and effectively You may contact Technical Support via Toll Free FAX Please include your return FAX number You will receive a reply within 24 hours You may also contact Technical Support v...

Страница 80: ...400 2300Hz ACK 1400Hz KISSOFF Ademco Contact ID Reporting 10 characters sec DTMF Touch Tone Data Tones 1400 2300Hz ACK 1400Hz KISSOFF Ademco Low Speed 10 pulses sec 1900Hz Data Tone 1400Hz ACK KISSOFF...

Страница 81: ...ned with system in TEST mode 5 Zones With the Ademco VISTA 10SE 4281L 4281CN L accepts up to 4 transmitters 4281M 4281H 4281CN H accepts up to 8 transmitters 5881L 5882L accepts up to 8 transmitters 5...

Страница 82: ...nt UL Listed 85dB 10 feet 320mA current draw Ademco 744 Siren Driver 6 jumper selected sound outputs Rated at 119dB with use of an 8 ohm 30 watt speaker 1 3 amps current draw Ademco 745X3 Voice Siren...

Страница 83: ...the FCC rules On the front cover of this equipment is a label that contains among other information the FCC registration number and ringer equivalence number REN for this equipment If requested this i...

Страница 84: ...ded with a back up battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition followed by at least 4 minutes in the i...

Страница 85: ...e tiquette certifie que le mat riel est conforme certaines normes de protection d exploitation et de s curit des r seaux de t l communications Le minist re n assure toutefois pas que le mat riel fonct...

Страница 86: ...ors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their det...

Страница 87: ...WITH THIS EQUIPMENT CHARGING VOLTAGE 13 8VDC BATTERY 12V 4AH e g ADEMCO No 467 OR 12V 1 2AH BATTERY CONNECTOR TABS FOR COMPLETE INFORMATION SEE INSTRUCTIONS PLUG IN TRANSFORMER 16 5VAC 25VA e g ADEMCO...

Страница 88: ...SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR D...

Отзывы: