– 10 –
Optional Output Relays
• Up to 4 relays using one 4204 Relay Module.
• Actions programmable to respond to zone activity or manual keypad entries.
Optional Phone module
• Supports the Ademco 4285 Phone module .
• Provides access to the system via on premises or off-premises phones for
arming, disarming, etc., plus control of relay outputs.
Optional Long Range
Radio
• Allows all messages that have been programmed to go to the primary
telephone number to be reported additionally to a 7720 PLUS or 7820 radio.
Alarm Output
• Provides a 12VDC, 2 AMP output that can drive the compatible sounders
listed in the EXTERNAL SOUNDERS section (assumes a fully charged
battery is connected).
• Steady output for Burglary/Panic, or temporal pulse sounding output for Fire
notification, as required by UL.
• Uses current limiting circuitry for protection.
Auxiliary Power Output
• Provides 12VDC, 500mA maximum. Uses current limiting circuitry for
protection.
• This output interrupts for smoke detector reset if 4-wire smoke detectors are
used.
Programming
• Programmed options are stored in electrically erasable, non-volatile EEROM
memory (information can be reprogrammed at any time and will not be lost in
the event of a power loss).
• The system can be uploaded, downloaded, or controlled via an IBM
compatible computer, using either Ademco’s V-Link® downloading software
(Rev. 4 or higher) or Ademco’s
Compass Windows downloading software,
and a HAYES modem specified by Ademco.
Keypad programming consists of:
•
Data field programming.
•
Interactive (menu) mode programming.
For programming from a keypad, a 5137AD or 6139 2-line Alpha keypad
must be connected (but need not necessarily stay in the system).
Communication Formats
Supported
• Ademco Low Speed (Standard or Expanded).
• Sescoa/Radionics (Standard or Expanded).
• Ademco Express.
• Ademco Contact ID.
Zone Descriptors
You can assign Alpha descriptors to all zones (useful only when using Alpha
keypads and/or the 4285 Phone module).
AC Power Supply
Uses No. 1321, 120VAC plug-in transformer with 16.5VAC 25VA output.
(1321CN in Canada)
Back-Up Battery
• Rechargeable (Gel type) 12VDC, 4AH minimum.