![ADB Safegate RELIANCE Intelligent Lighting Platform III Скачать руководство пользователя страница 72](http://html1.mh-extra.com/html/adb-safegate/reliance-intelligent-lighting-platform-iii/reliance-intelligent-lighting-platform-iii_user-manual_2847416072.webp)
4.8 CCRE Interrelations
4.8.1 Constant Current Regulator Type E — Interface
The CCRE
®
interface is structured in the following way:
Figure 45: CCR display
4.8.2 Constant Current Regulator type E — nominal Current
The Constant Current Regulator must at series circuit nominal current (6.6 A) be set to the correct current flow duration of the
thyristor.
•
The correct working point guarantees sufficient control reserves and low harmonic distortion.
•
By choosing the correct output voltage tap of the transformer, the following conducting time should be achieved:
~ 6.1 ms without RELIANCE remotes,
~ 5.8 ms when using the ADB SAFEGATE RELIANCE IL
RELIANCE Intelligent Lighting
Operation
60
Copyright
©
ADB SAFEGATE, All Rights Reserved
Содержание RELIANCE Intelligent Lighting Platform III
Страница 1: ...RELIANCE Intelligent Lighting Platform III User Manual UM 5005 Rev 004 2020 08 06 ...
Страница 2: ......
Страница 10: ...RELIANCE Intelligent Lighting List of Figures x Copyright ADB SAFEGATE All Rights Reserved ...
Страница 12: ...RELIANCE Intelligent Lighting List of Tables xii Copyright ADB SAFEGATE All Rights Reserved ...
Страница 18: ...RELIANCE Intelligent Lighting Safety 6 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 52: ...RELIANCE Intelligent Lighting Introduction 40 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 56: ...RELIANCE Intelligent Lighting Installation 44 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 118: ......