5.10 Setting the Parameters for a new RELIANCE IL SRU dual-channel
Refer to
Device Settings lucDMC — System Parameters
for detailed list of parameters.
Note
You should only change the first four lines. "Factory settings" can be restored by clicking the respective button if you
made a mistake.
1. Type in the new remote address.
2. Set RU with two loads for a SRU102 or SRU112.
3. Select 0 = 300 W or 1 = 230 W for High-power mode.
4. Select 2,2 A or 6,6 A for circuit topology.
5. Assign segments to lamp 1 and lamp 2 by dragging and dropping the lamps into the structure tree or by right-clicking on
the lamps and using the menu.
6. Hit the send button to save your changes.
5.11 Check List for the Circuit in Case of RELIANCE IL Failure
When you have checked all the parameters for the regulator concerning RELIANCE IL system operation and the settings are
fine, you should check the following:
If you have checked
•
Are the cables connected at the right place (check wiring diagram) after cable replacement? — After cable replacement
due to break is might happen that the wrong cables have been connected.
•
Are the same transformer types installed as before the transformer replacement? — This is important as RELIANCE IL
requires certain transformer types.
•
Is the FLYCY cable ok? — It sometimes happens that heavy construction machines destroy the circuit cables. An indicator
for cable break is if a series of remotes suddenly do not send their feedback any more.
•
Is the regulator controller module (Control and Communication Unit) fitted correctly into the regulator? — If the CU is not
connected properly to the regulator, the error message "
sensor line open
" is shown on the regulator display.
•
Is the regulator connected properly to the transformer in the internal circuit to which lights are connected to?
5.12 Replacing the Internal Components
Contact ADB SAFEGATE for information on replacing internal components which includes the PCBs.
Website:
ADB SAFEGATE Technical Service & Support (International): +49 621 8755 76 - 0
RELIANCE Intelligent Lighting
Maintenance
102
Copyright
©
ADB SAFEGATE, All Rights Reserved
Содержание RELIANCE Intelligent Lighting Platform III
Страница 1: ...RELIANCE Intelligent Lighting Platform III User Manual UM 5005 Rev 004 2020 08 06 ...
Страница 2: ......
Страница 10: ...RELIANCE Intelligent Lighting List of Figures x Copyright ADB SAFEGATE All Rights Reserved ...
Страница 12: ...RELIANCE Intelligent Lighting List of Tables xii Copyright ADB SAFEGATE All Rights Reserved ...
Страница 18: ...RELIANCE Intelligent Lighting Safety 6 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 52: ...RELIANCE Intelligent Lighting Introduction 40 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 56: ...RELIANCE Intelligent Lighting Installation 44 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 118: ......