CAUTION
Use aNH-plug safety handle to test fuse functionality to protect yourself from electrical shock.
Figure 67:
NH-plug safety handle
example
Table 22: Error messages regulator
Problem / error message
Possible cause
Corrective action / required check
"I = 0" (no current / voltage flows) Broken cable (FLYCY cable )
Measure loop impedance, find and replace broken cable (open-circuit
between the slots or cable from regulator to transformer)
"ISO: no communication"
No connection to IME(Insulation
measurement device for series
circuits)
Check configuration and physical connection to IME
"No communication"
No remote connection (CAN bus,
Mod bus or Profi bus)
Reestablish remote bus connection; change voltage transformer
Voltage transformer (NGU001
broken
Display not working
Fuse broken
Consult fuse position in the map (look up circuit number shown on
the upper regulator screen) → check fuse using an NH fuse handle (if
red dot is out, it is broken)
No supply voltage incoming
Measure supply voltage with a volt meter and check power supply,
check external circuit (measure ISO values, check FLYCY cable,
impedance of external circuit and loop impedance)
Error message appears after
switching on
Regulator defective
Check fuse → if fuse ok, set in new regulator for testing if problem
persists → if persisting, send regulator to ADB SAFEGATE service
team; check connectors in the regulator
Contact pins of female connector
bent
Replace individual parts like controller module for testing → if
problem persists, send regulator to ADB SAFEGATE or contact the
ADB SAFEGATE service team
Fuses of switches inside of
regulator broken
Send regulator to ADB SAFEGATE service team
If regulator and its parts ok,
external circuit architecture might
be damaged
Measure ISO values (if in k Ω, corrective actions are required, M Ω is
perfect); check external cables, measure external impedance and
loop value (8 Ω is default; infinity symbol is displayed if defective as it
indicates broken cable); measure values of FLYCY cable (might be
damaged by heavy machines crossing the airfield)
Transfomer broken
Check if cable connections have firm hold and of screws are properly
tightened
"Connect sensor cable"
Sensor cable is not connected
Reconnect the sensor, press X button and tighten the screw
UM-5005, Rev. 004, 2020/08/06
91
Copyright
©
ADB SAFEGATE, All Rights Reserved
Содержание RELIANCE Intelligent Lighting Platform III
Страница 1: ...RELIANCE Intelligent Lighting Platform III User Manual UM 5005 Rev 004 2020 08 06 ...
Страница 2: ......
Страница 10: ...RELIANCE Intelligent Lighting List of Figures x Copyright ADB SAFEGATE All Rights Reserved ...
Страница 12: ...RELIANCE Intelligent Lighting List of Tables xii Copyright ADB SAFEGATE All Rights Reserved ...
Страница 18: ...RELIANCE Intelligent Lighting Safety 6 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 52: ...RELIANCE Intelligent Lighting Introduction 40 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 56: ...RELIANCE Intelligent Lighting Installation 44 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 118: ......