5.9 RELIANCE IL Parameters to be checked in lucDMC
For a regulator with RELIANCE IL CU the following regulator parameters have to be checked in the lucDMC user interface:
•
Is the symmetric corrective factor to be found under CCR settings > advanced settings still ok (as it was set at
commissioning)? — The symmetric corrective factor should not vary to much (variations between - 30 and + 30 are
acceptable)
Note
The regulator must be switched on before checking the symmetric corrective factor.
•
The Trigger angle to be found under Status on the right side of the CCR with SCROLL (tab) should be between 5 and 5.5
milliseconds.
Tip
Compare the settings to the settings documented in your commissioning protocol.
•
Is the lamp symbol on or off? — The feedback is correct if a check mark is shown.
•
Is the remote and the lamp symbol red? — click on administration (magic wand icon) and select "feedback from all
remotes". A green check mark appears if the remotes are working. Light bulb icon is greyed out, if the light is blown.
Note
Symmetric corrective factor is not correct and does vary a lot, if the remote is defective. No more feedback from
the regulator will be received.
Follow the steps indicated in the testing section and the self test section of the manual to check if remote are broken.
•
Is Automatic feedback from all remotes after giving a switching command activated?
•
Is Cyclic feedback from all lamps activated during segment test phase?
•
Are all the green lamp symbols in the SCROLL Quality tab located above the threshold?— If the regulator stays ON, but
all segments are OFF, the shown feedback (marked by a dot) should be below the threshold.
Remember
Wait a few minutes after starting the test as values need to level off.
•
Is the ignition angle setpoint within a normalized range between 5 and 5.5 milliseconds? — The ignition angle can be
checked in lucDMC in the CCR with SCROLL tab in the menu point on the right.
UM-5005, Rev. 004, 2020/08/06
101
Copyright
©
ADB SAFEGATE, All Rights Reserved
Содержание RELIANCE Intelligent Lighting Platform III
Страница 1: ...RELIANCE Intelligent Lighting Platform III User Manual UM 5005 Rev 004 2020 08 06 ...
Страница 2: ......
Страница 10: ...RELIANCE Intelligent Lighting List of Figures x Copyright ADB SAFEGATE All Rights Reserved ...
Страница 12: ...RELIANCE Intelligent Lighting List of Tables xii Copyright ADB SAFEGATE All Rights Reserved ...
Страница 18: ...RELIANCE Intelligent Lighting Safety 6 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 52: ...RELIANCE Intelligent Lighting Introduction 40 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 56: ...RELIANCE Intelligent Lighting Installation 44 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 118: ......