Problem
Cause
Solution
Tablet has no display
Coms cable not plugged in.
Power cable not plugged into Control Box
Assembly.
Power point not switched on at Control
Box Assembly.
No power at power outlet.
Circuit breaker tripped.
Check Coms cable connections at Control
Box Assembly and back of Tablet.
Check power cable connection at Control
Box Assembly and 24V DC Power Supply.
Switch on the power point.
Check fuses, circuit breakers, call
electrician.
Re-set. If problem persists contact
Support.
Damper Motor Fault
Damper unplugged.
Faulty Damper.
Faulty Damper motor.
Faulty motor cable.
Check connections at Control Box
Assembly and at the Damper motor.
Replace Damper.
Replace Damper motor.
Replace motor cable.
Wireless Sensor
Fault/Wired Sensor
Fault
Flat sensor battery.
Insufficient signal strength.
Faulty sensor.
Sensor unplugged.
Faulty sensor cable.
Replace sensor battery.
Try alternate sensor position.
Replace sensor.
Check plug connections.
Replace sensor cable.
Duct Sensor Error
Faulty duct sensor.
Duct sensor unplugged.
Replace duct sensor.
Check plug connection at Control Box
Assembly.
No Damper Controls,
System Interfaces and
AC Modbuses found!
Communication from Control Box
Assembly unavailable.
Check Coms cable connections at Control
Box Assembly and back of Tablet.
Replace Coms cable.
Replace Control Box Assembly. If problem
persists contact Support.
Tablet is working but a
Zone is not regulating
the airflow
Broken Damper blade.
Blade is obstructed.
Duct not properly connected.
Replace Damper.
Remove obstruction.
Check duct connection.
WARRANTY
INSTALLATION MANUAL
42
TROUBLESHOOTING
43
TROUBLESHOOTING
27. Troubleshooting
All service to the Platinum Elite system must be carried out by an approved Air Diffusion
Agencies service technician, and must not be done by unqualified personnel. Repairs
carried out by unqualified personnel will void warranty.
For basic Troubleshooting information, refer to the Troubleshooting table. For additional
information, FAQ’s and other helpful hints and tips, refer to the Support section on the
Platinum Elite Zone Control System website at:
www.platinumzoning.com
This can also be accessed directly from the Support tab on the Tablet or Mobile Device App.
Air Diffusion Agencies strive to implement continuous product improvement, therefore
specifications are subject to change without notice.
Содержание Platinum Elite
Страница 1: ...INSTALLATION MANUAL ZONE CONTROL SYSTEM...
Страница 2: ...2...
Страница 42: ...SYSTEM SET UP INSTALLATION MANUAL 40...
Страница 47: ......
Страница 48: ...ADAPEI0521 www platinumzoning com For the latest version of the Installation Manual scan the QR code...