AC CONTROL - PANASONIC
INSTALLATION MANUAL
20
21
15. AC Control - Panasonic
Wiring Diagram
Commissioning Notes
Advanced Installation
Ÿ
Wire Platinum Elite Zone Control System, Gateway and AC Indoor Unit as shown ensuring
all wires are securely connected. Unless otherwise specified, leave DIP switches in their
default position.
Ÿ
Initialise the AC Unit with the Panasonic Wall Controller connected.
The Wall Controller
can be wired in parallel with the Gateway.
NOTE: In some AC Indoor Unit models, the R1R2 connector is not available. In it’s place
there is a pair of cables to connect the Wall Controller. Use these cables to make the R1R2
connection. Check the unit User Manual for more information.
Ensure the AC control temperature is set to be
measured from the AC return air sensor.
Ÿ
Follow the Platinum Elite onscreen prompts to complete the AC setup.
The Platinum Elite system is capable of providing an external reference temperature to
compatible AC Units from either the temperature sensor in the Tablet or one of the
connected Temperature Sensors. Utilising this feature will potentially modify the control
loop for the AC Unit and as such requires precise configuration of the AC Unit, the Platinum
Elite Gateway and the Platinum Elite Tablet software to ensure the system functions
correctly.
For detailed information on Panasonic AC Unit system compatibility utilising external
reference temperatures and related Advanced Installation options, please visit the Platinum
Elite Zone Control System website www.platinumzoning.com or contact your ADA
distributor.
Ÿ
AC Unit, Gateway and Platinum Elite Zone Control System can be powered up at the same
time, but if powered up separately, ensure AC Unit and Gateway are on before the
Platinum Elite Zone Control System.
Tablet
Cat6 cable
24VDC
Power
Supply
AC Indoor Unit PCB
Platinum Elite
Gateway
PEGP
SW1
SW3
SW4
A+ B-
R1 R2
R1 R2
2-core cable (PETCW)
supplied with Platinum
Elite Cable Kit
2-core cable (PETCW)
supplied with Platinum
Elite Cable Kit
(R1R2 connection has
no specific polarity)
Wall Controller
R1 R2
SW1
ON
Default Gateway Setting
Down/OFF
Up/ON