AC CONTROL - DAIKIN
11. AC Control - Daikin
Wiring Diagram
INSTALLATION MANUAL
12
13
Commissioning Notes
Advanced Installation
Ÿ
Wire Platinum Elite Zone Control System, Gateway and AC Indoor Unit as shown ensuring
all wires are securely connected. Unless otherwise specified, leave DIP switches in their
default position.
NOTE: In early models, the Daikin Gateway was supplied with SW1.4 ON as default - this
must be changed to OFF as shown by Default Gateway Setting above.
Ÿ
Initialise the AC Unit with the Daikin AC Wall Controller connected.
Ÿ
The Wall Controller
can be wired in parallel with the Gateway.
Ensure the AC control temperature is set to be
measured from the AC return air sensor.
Ÿ
After commissioning, SW1.1 is left OFF. Gateway is in Slave mode.
Ÿ
Follow the Platinum Elite onscreen prompts to complete the AC setup.
The Platinum Elite system is capable of providing an external reference temperature to
compatible AC Units from either the temperature sensor in the Tablet or one of the
connected Temperature Sensors. Utilising this feature will potentially modify the control
loop for the AC Unit and as such requires precise configuration of the AC Unit, the Platinum
Elite Gateway and the Platinum Elite Tablet software to ensure the system functions
correctly.
For detailed information on Daikin AC Unit system compatibility utilising external reference
temperatures and related Advanced Installation options, please visit the Platinum Elite Zone
Control System website www.platinumzoning.com or contact your ADA distributor.
AC Unit, Gateway and Platinum Elite Zone Control System can be powered up at the same
time, but if powered up separately, ensure AC unit and Gateway are on before the
Platinum Elite Zone Control System.
Tablet
Cat6 cable
24VDC
Power
Supply
AC Indoor Unit PCB
Platinum Elite
Gateway
PEGD
SW1
SW3
SW4
SW1
Slave
Master
ON
ON
Gateway Master/Slave Setting
A+ B-
P1 P2
P1 P2
2-core cable (PETCW)
supplied with Platinum
Elite Cable Kit
2-core cable (PETCW)
supplied with Platinum
Elite Cable Kit
(P1P2 connection has
no specific polarity)
Down/OFF
Up/ON
DAIKIN
Wall Controller
P1 P2
SW1
ON
Default Gateway Setting
Down/OFF
Up/ON