02. Waste Electrical and Electronic Equipment Disposal Guideline
1.
Do not dispose off the waste electrical and electronic equipment with local council waste. These must be
disposed off through the council designated hazardous waste collection centre.
2. The equipment may contain hazardous substances, improper or incorrect disposal may have a negative
effect on human health and on the environment.
03. Maintenance
1.
Keep the control interface clean with the use of a soft dry cloth only. If a cleaning solution is needed, use a
very mild soap solution to dampen the cloth. Do not spray or squirt any liquid onto your control interface.
2. Do not use solvent base cleaner, which can cause damage to the control interface.
3. When cleaning, be careful not to accidentally press any Buttons, TURN-OFF the unit to ensure that no
adverse unit operation is initiated by accidentally pressing any Buttons.
4. Be careful not to press hard into the display screen, as it may get damaged.
5. Ensure that the temperature sensor is always clean and free of dust or dirt build-up to maintain sensor
accuracy.
6. Do not pull apart or attempt to service the control interface, should you need service to the device,
contact ActronAir Service Department on 1800 119 229.
04. Safety Precaution
1.
Read all instructions in this manual before operating the air conditioning unit. Failure to do so may result
in damage to the unit and void your warranty.
2. Turn-Off the power supply to the unit and follow sound Lock Out and Tag Out procedures to ensure that
power supply is not re-energised accidentally.
3. Beware of EC Motors with high power capacitors and which can have dangerous voltages at terminals for
up to 5 min. after main power has been isolated. Wait at least 5 minutes after power isolation and test for
high voltage before performing service work.
4. EC Plug fans have dual power supplies, i.e. 415V / 3Ph+N / 50Hz motor power supply plus 10VDC control
power supply. Care must be taken to ensure both are safely isolated to prevent personal injury and
damage to the equipment.
5. This control interface has power supply from indoor board controller via screwed terminals and 4 Core
Twisted Pair Data cable. Ensure that this unit is not installed on voltages other than specified.
6. Installation and/or servicing must be carried out by a qualified technician.
7. Ensure that the unit installation complies with relevant council regulations and building code standards.
All electrical wiring must be in accordance with current electrical authority regulations and all wiring
connections to be as per electrical diagram provided.
8. WH&S rules and regulations must be observed and will take precedence during installation process.
9. Only use this control interface with an ActronAir air conditioner as described in this operating manual.