14. Alarm Matrix
INDOOR BOARD FAULT ERROR CODES
Alarm Code
Description
Type
Alarm Condition
Reset Condition
E1
Auxiliary Sensor Error (OC/SC)
Alarm
No Sensor, Sensor OC/SC
Sensor OK
E2
Indoor Coil Sensor Error (OC/SC)
Alarm
Coil Sensor OC/SC
Sensor OK
E3
Over Current
Alarm
Input out of Range
Normal Operation
Under Current
Indoor Fan not running
Normal Operation
E4
Wrong Dip switch Error
Alarm
Wrong Dipswitch Settings
Correct Settings
E5
Communication Error
Alarm
No communication with OD
NOTE:
Wait for 30 sec. before E5 is displayed.
Communication OK
E6
Indoor Fan Fault
Alarm
Not Operating
Normal Operation
E7
0-10VDC No Input
Alarm
Input is less than 0.1V when 3rd Party
voltage control is selected on ID
Correct 0-10VDC Input
E8
Reserved for Other Errors
Alarm
---
---
E9
Reserved for Other Errors
Alarm
---
---
Содержание CL01-2G