![Acromag AXM-A75 Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/acromag/axm-a75/axm-a75_user-manual_2841159010.webp)
AXM-
A75 User’s Manual
Multifunction I/O Mezzanine Board
_____________________________________________________________________________________
- 9 -
Analog Inputs: Noise and Grounding Considerations
Differential inputs require two leads (+ and -) per channel, and
provide rejection of common mode voltages. This allows the desired
signal to be accurately measured. However, the signal being
measured cannot be floating. It must be referenced to analog
common on the AXM module and be within the normal input voltage
range. Shielded cable of the shortest length possible is strongly
recommended.
Non-Isolation Considerations
The board is non-isolated, since there is electrical continuity between
the logic and field I/O grounds. As such, the field I/O connections are
not isolated from the system. Care should be taken in designing
installations without isolation to avoid noise pickup and ground loops
caused by multiple ground connections.
3.0
PROGRAMMING INFORMATION
This Section provides the specific information necessary to program
and operate the mezzanine board.
This mezzanine board is intended only for use on specific Acromag
PMC/XMC FPGA modules. As such only a small portion of I/O
memory space is currently reserved for operation of the mezzanine
board. The remaining memory space is defined in the base board
’
s
User’s Manual.
AXM-A75 Memory Map
The AXM-A75 specific memory space address map for the board is
shown in Table 3-1. Note that the base address from the base
PMC/XMC module in memory space must be added to the addresses
shown to properly access the board registers. Register accesses as
32, 16, and 8-bits in memory space are permitted unless otherwise
indicated. A detailed description of each of the registers follows after
Table 3-1.
Table 3-1 Memory Map
P
(Hex)
D31 D16
D15 D00
P
(Hex)
0003
↓
7FFF
Reserved for base PMC/XMC Module
0000
↓
7FFC
8003
Board Status Register and Software Reset
8000
8007
↓
80FF
Reserved for base PMC/XMC Module
8004
↓
80FC
8103
8100