DC Inverter
X-Series
for R410A Unitary Split Air Conditioner
32
and to the correct specification. At all times the manufacturer’s maintenance and
service guidelines shall be followed. If in doubt consult the manufacturer’s technical
department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
(1) The ventilation machinery and outlets are operating adequately and are not
obstructed.
(2) If an indirect refrigerating circuit is being used, the secondary circuit shall be
checked for the presence of refrigerant.
(3) Marking to the equipment continues to be visible and legible. Markings and
signs that are illegible shall be corrected.
(4) Refrigeration pipe or components are installed in a position where they are
unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials
which are inherently resistant to being corroded or are suitably protected
against being so corroded.
4.4.1.4 Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks
and component inspection procedures. If a fault exists that could compromise safety,
then no electrical supply shall be connected to the circuit until it is satisfactorily dealt
with. If the fault cannot be corrected immediately but it is necessary to continue
operation, an adequate temporary solution shall be used. This shall be reported to the
owner of the equipment so all parties are advised.
Initial safety checks shall include:
(1) That capacitors are discharged: this shall be done in a safe manner to avoid
possibility of sparking.
(2) That no live electrical components and wiring are exposed while charging,
recovering or purging the system.
(3) That there is continuity of earth bonding.
4.4.2 Repairs to Sealed Components
4.4.2.1 Electrical Safety
From the equipment being worked upon prior to any removal of sealed covers, etc.
If it is absolutely necessary to have an electrical supply to equipment during servicing,