3.6
Functions
3.6.1
Set Capacity Dip Switch
Set the capacity of the outdoor unit through the four dip switches of the outdoor
unit main control board. Specific dip switch definition, the first dip switch
distinguishes the capacity.
Indicates the position of switch in following example.
3.6.2
Set Defrost Mode
The second dip switch is selecting the defrost mode.
The second dip switch is used to change the defrost setting, factory default
setting is standard defrost. Under extremely low environment temperature, if
the standard defrost cannot have the condenser defrosted completely, please
set the second dip switch to be strong defrost. Under strong defrost, the
defrosting time will be longer, which enable the condenser to be defrosted
completely.