less than the minmum output
frequency Pn-07.
˙
DC injection braking at start
Starts a coasting motor without tripping even when the direction of rotation is unknown. When the run
command is input, DC injection brake is applied for the time set by , and the motor stops. Then the motor
starts operation.
˙
DC braking current
DC injection braking current 100% equals the inverter rated current. It is set to 50% at factory prior to
shipping.
2.7.13
FULL-RANGE AUTOMATIC TORQUE BOOST
Item Name
Constant to be set
Factory Preset
Torque Compensation Gain
29
1.0
Automatic control of V/f ratio according to the load torque ensures tripless operation and optimum output
current. Therefore, tripless operation with excellent energy-saving effect is available. When the wiring
distance between the inverter and motor is long (normally approx. 100m) and when the motor torque is a
little short, increase torque compensation gain gradually, checking the motor current. Normally, no
adjustment is necessary.