1.8 SPECIFICATIONS
1.8.1 Specifications
Voltage Class
220 3-phase
JNTABDCB JK---
Inverter Model
R500 0001 0002
0003 0005 7R50 0010
Max. Applicable Motor
Output HP (KW) *1
0.5(0.4)
1(0.75)
2(1.5) 3(2.2) 5(3.7) 7.5(5.5)
10(7.5)
Inverter Capacity KVA
1.4 2.1 2.7 4.1 6.9 10.3
13.7
Rated Output current A
3.2 4.8 6.5 9.6 16 24 32
Max. Output Voltage V
3-phase 200 to 230V , 50/60 Hz (proportional to input voltage)
Out
put
characteristics
Max. Output Frequency
400 Hz (available with constant setting)
Rated Input Voltage and Freq.
3-phase 200 to 230V , 50/60 Hz
Allowable Volt. Fluctuation
± 10
%
Power
Su
ppl
y
Allowable Freq. Fluctuation
± 5
%
Control Method
Sine wave PWM
Freq. Control Range
0.1 to 400 Hz
Frequency Accuracy
Digital command: 0.01%, Analog command : 0.1%
Freq. Setting Resolution
Digital : 0.1 Hz , Analog : 0.06/60Hz
Output freq. Resolution
0.1 Hz
Overload Capacity
150% rated output current for one minute
Freq. Setting Signal
0 to 10v (20k
Ω
), 4 to 20 mA (250
Ω
)
Accel/Decel. Time
0.1 to 600 sec (accel/decel time setting independently)
Braking Torque
Approx. 20%(up to 150% possible with optional braking resistor)
V/F Characteristic
Possible to set any program of v/f pattern
Control Cha
racte
ris
tic
s
Stall prevention level
Possible to set operating current
Instantaneous OC
Motor coasts to stop at approx. 200% rated current
Overload
Motor coasts to stop for 1 minute at approx. 150% rated output current
Motor overload
Electronic thermal overload relay
Overvoltage
Motor coasts to stop if main circuit voltage exceeds 410v
Undervoltage
Stop when main circuit DC voltage is approx. 210v or less
Momentary Power loss
15ms or longer *2
Cooling Fin Overheat
Protected by thermoswitch (only for forced cooling method)
Protection F
unction
Power Charge Indication
Charge lamp stays on until main circuit DC voltage drops below 50v
*1. TECO standard 4-pole motor is used for max. applicable motor output
*2. To select “automatic restart after momentary power loss “ set the 1
st
digit of constant (Pn-46) to “1”