64
Function
Pn-
Name
Description
Initial
Settin
g
User
Set
Valu
es
Ref.
Par.
13 Frequency
Reference 1
Setting unit:0.1 Hz,
Setting range:0.0 to 400.0 Hz
0.0Hz
14 Frequency
Reference 2
Setting unit:0.1 Hz,
Setting range:0.0 to 400.0 Hz
0.0Hz
15 Frequency
Reference 3
Setting unit:0.1 Hz,
Setting range:0.0 to 400.0 Hz
0.0Hz
16 Frequency
Reference 4
Setting unit:0.1 Hz,
Setting range:0.0 to 400.0 Hz
0.0Hz
2.7.5
Frequency
Reference
(Note 1)
17 Jog
Frequency
Reference
Setting unit:0.1 Hz,
Setting range:0.0 to 400.0 Hz
6.0Hz
2.7.6
4 3 2 1
- - - 0
Electronic thermal overload motor
protection provided
- - - 1
Electronic thermal overload motor
protection not provided
- - 0 -
Electronic thermal overload
characteristics is for standard
motor
- - 1 -
Electronic thermal overload
characteristics is for constant
torque motor
- 0 - -
Electronic thermal overload time
constant is of standard rating
- 1 - -
Electronic thermal overload time
constant is of short-term rating
0 - - -
Electronic
Thermal
Overload
Motor
Protection
18
Motor
Protection
Selection
1 - - -
Not used
0000
2.7.7
Electronic
Thermal
Overload
Reference
Current
19
Motor
Rated
Current
Setting unit :0.1A,
Setting range: 10 to 120% of inverter rated
current
3.3A
(Note
2)
2.7.7
Note:1 Can be changed even during run.
The maximum setting frequency to be set to frequency reference is the maximum frequency(Pn-02).
2. Initial setting differs according to the inverter capacity. The values in the above list are provided
when model JNTABDCB0001 JK--- and TECO standard motor 220V 60Hz 4 poles 1HP(0.75kw)
are combined.