MultiControl Mono
Ver. 1.1
23
1.0
Warning and safety notices for installing and commissioning the control system
1.1
Applications
The switchgear is designed for use in the disposal of waste water, untreated wastewater.
The following must be noted for actuating pumps that are being operated in an area with a potentially
explosive atmosphere: The switchgear itself must be installed outside of the area subject to a potentially
explosive atmosphere.
Components with the relevant approvals must be used when using external 4 - 20 mA level probes and float
switches that are installed in areas subject to potentially explosive atmospheres.
For the switching of three-phase A.C. motors, the following limit values for both the setting of the electronic
monitoring of the motor current and the settings of the mechanical motor protection switches must be
observed.
Standard design
Optional (only if specified on purchase order)
1.2
Personnel qualifications
The personnel installing, commissioning and maintaining the switchgear must have the appropriate
qualifications.
1.3
Safety notices for the operator
The existing regulations for accident prevention issued by the VDE (German Association of Electrical
Engineers) and the local power supply companies must be observed. When opening the switchgear (removing
the panel or terminal cover) or working on the pumps, it is imperative that the control system is always
disconnected from the power supply via the back-up fuse or a separate main switch.
1.4
Hazards if the safety notices are not observed
Failure to observe the safety notices may jeopardise the safety of persons and the product/system. Failure to
observe the safety notices may invalidate all claims to compensation.
1.5
Operating manual
The operating manual must be observed when installing, commissioning and maintaining the switchgear. It is
imperative that the limit values specified in this manual are observed.
A maximum of 3 16 A fuses must be fitted on the mains side.
4 kW contactors
Three-phase AC 400 V
Max. 9 A
Alternating current 230 V
Max. 11,5 A
5.5 kW contactors
Three phase AC 400 V
Max. 12 A
Alternating current 230 V
Max. 14,5 A
Содержание MultiControl Mono
Страница 1: ...MultiControl Mono Ver 1 1 1 Mikrocontroller Einzelpumpensteuerung...
Страница 17: ...MultiControl Mono Ver 1 1 17...
Страница 18: ...MultiControl Mono Ver 1 1 18 Achtung Bei Anschluss von 1 Motoren betr gt die maximale Anschlussleistung 4 KW...
Страница 19: ...MultiControl Mono Ver 1 1 19 Relaisausg nge Signaleing nge und Analogausg nge...
Страница 20: ...MultiControl Mono Ver 1 1 20 Notizen...
Страница 21: ...MultiControl Mono Ver 1 1 21 Microcontroller for single pump control...
Страница 37: ...MultiControl Mono Ver 1 1 37 Connection of 3 motors...
Страница 40: ...MultiControl Mono Ver 1 1 40 Microcontr leur Commande de pompe individuelle...
Страница 59: ...MultiControl Mono Ver 1 1 59 Raccordement de moteurs 3 en option...