Microprocessor Controller for DOAS
48
Appendix E: Points List
BV-610
10560
Low Suction Refrigerant Temperature (1=Alarm; 0=Normal)
BV-612
10562
EVD Max Operating Pressure Alarm (1=Alarm; 0=Normal)
BV-614
10564
EVD-S1 Suction Pressure Sensor Alarm (1=Alarm; 0=Normal)
BV-615
10565
EVD-S2 Suction Temperature Sensor Alarm (1=Alarm; 0=Normal)
BV-617
10567
EVD-S4 Discharge Temperature Sensor Alarm (1=Alarm; 0=Normal)
BV-618
10568
Compressor Envelope - High Suction Pressure (1=Alarm; 0=Normal)
BV-619
10569
Compressor Envelope - Low Suction Pressure (1=Alarm; 0=Normal)
BV-631
10579
Heat Pump Defrost Alarm (1=Alarm; 0=Normal)
BV-633
10581
Heat Pump Heating Locked Out (1=Alarm; 0=Normal)
BV-634
10582
Unexpected EEV Position - Preposition Failed (1=Alarm; 0=Normal)
BV-731
10679
Energy Recovery Wheel High Differential Pressure (1=Alarm; 0=Normal)
BV-733
10682
High Low Pressure Switch Alarm Circuit A (1=Alarm; 0=Normal) - Legacy
BV-734
10683
High Low Pressure Switch Alarm Circuit B (1=Alarm; 0=Normal) - Legacy
BV-735
10684
High Low Pressure Switch Alarm Circuit C (1=Alarm; 0=Normal) - Legacy
BV-736
10685
High Low Pressure Switch Alarm Circuit D (1=Alarm; 0=Normal) - Legacy
BV-737
10686
EF Greentrol Alarm (1=Alarm; 0=Normal) - Legacy
BV-738
10687
OAD Greentrol Alarm (1=Alarm; 0=Normal)
BV-739
10688
Greentrol Device 3 Alarm (1=Alarm; 0=Normal) - Legacy
BV-741
10690
OAD Feedback Error - Not Opening When Economizing (1=Alarm; 0=Normal)
BV-742
10692
OAD Feedback Error - OAD is Open (1=Alarm; 0=Normal)
BV-743
10694
OAD Feedback Error - OAD is Not Modulating (1=Alarm; 0=Normal)
BV-744
10696
OAD Feedback Error - OAD is Not Closing (1=Alarm; 0=Normal)
BV-745
10700
Space Thermostat 1 Offline (1=Alarm; 0=Normal)
BV-746
10702
Space Thermostat 2 Offline (1=Alarm; 0=Normal)
BV-747
10704
Space Thermostat 3 Offline (1=Alarm; 0=Normal)
BV-748
10706
Space Thermostat 4 Offline (1=Alarm; 0=Normal)
BV-749
10708
Inverter Scroll 1 Alarm (1=Alarm; 0=Normal)
BV-753
10716
IG Furnace Alarm (1=Alarm; 0=Normal)
BV-754
10718
SF VFD Alarm - Mini Platform (1=Alarm; 0=Normal)
BV-758
10726
Embedded EVD Alarm - Mini Platform (1=Alarm; 0=Normal)
BV-759
10728
Supply Fan VFD Offline - Mini Platform (1=Alarm; 0=Normal)
Integer Values - Read COV/No Write - Modbus Input Registers
IV-1
30181
Fan and Damper Startup Sequence Delay Timer
IV-2
30183
Supply Fan Startup Sequence Delay Timer
IV-3
30185
Exhaust Fan startup sequence time before starting the exhaust fan.
IV-7
30193(2)
Most Recent Alarm - Call Technical Support for current table
IV-9
30655
Active Temperature Reset Sequence
1. No Reset, Supply Control 2. Space 3. Return 4. Outside
Integer Values - Read COV/Commandable - Modbus Holding Register
IV-8
40105
Selected Temperature Reset Sequence
1. No Reset, Supply Control 2. Space 3. Return 4. Outside