Microprocessor Controller for DOAS
45
Appendix E: Points List
BV-8
9
Return Temp Source Selection (1=BMS; 0=Local) (AV-24 Analog Value)
BV-9
10
Space 1 CO2 Source Selection (1=BMS; 0=Local) (AV-25 Analog Value)
BV-11
12
Return CO2 Source Selection (1=BMS; 0=Local) (AV-27 Analog Value)
BV-12
13
Space RH Source Selection (1=BMS; 0=Local) (AV-28 Analog Value)
BV-13
14
Space Static Source Selection (1=BMS; 0=Local) (AV-29 Analog Value)
BV-14
15
Space Temp Source Selection (1=BMS; 0=Local) (AV-30 Analog Value)
BV-56
19
SF Control Source Selection (1=BMS; 0=Local) (AV-133 Analog Value)
BV-57
20
EF Control Source Selection (1=BMS; 0=Local) (AV-134 Analog Value)
BV-59
22
OAD Control Source Selection (1=BMS; 0=Local) (AV-136 Analog Value)
BV-207
24
BMS Commanded auxiliary digital output (1=Active; 0=Inactive)
BV-208
25
BMS Commanded auxiliary digital output (1=Active; 0=Inactive)
BV-209
26
BMS Commanded auxiliary digital output (1=Active; 0=Inactive)
BV-210
27
BMS Commanded auxiliary digital output (1=Active; 0=Inactive)
BV-211
28
BMS Commanded auxiliary digital output (1=Active; 0=Inactive)
BV-212
29
BMS Commanded auxiliary digital output (1=Active; 0=Inactive)
Binary Values - Read COV/No Write - Modbus Discrete Inputs
BV-16
10002
Occupied Status (1=Occupied; 0=Unoccupied)
BV-18
10004
Unoccupied Cooling Call Status (1=Active; 0=Inactive)
BV-19
10005
Unoccupied Dehumidification Call Status (1=Active; 0=Inactive)
BV-20
10006
Unoccupied Heating Call Status (1=Active; 0=Inactive)
BV-24
10010
General Alarm Status
Optionally set to indicate any alarm is active, or a shutdown alarm is active.
(1=Alarm; 0=Normal)
BV-25
10011
Shutdown Alarm Status
When in alarm, the System Enable is set to false and the unit will remain off.
(1=Shutdown; 0=Normal)
BV-27
10013
Unit Cooling (1=Active; 0=Inactive)
BV-28
10014
Unit Economizing (1=Active; 0=Inactive)
BV-29
10015
Unit Heating (1=Active; 0=Inactive)
BV-31
10017
Unit Dehumidifying (1=Active; 0=Inactive)
BV-32
10018
Manual Overrides Active (1=Override; 0=Normal)
BV-33
10019
Cooling Allowed (1=Allowed; 0=Locked_Out)
BV-34
10020
Heating Allowed (1=Allowed; 0=Locked_Out)
BV-36
10022
PreHeat Allowed (1=Allowed; 0=Locked_Out)
BV-37
10023
Hot Gas Reheat Purge Cycle (1=Active; 0=Inactive)
BV-43
10029
Dampers Opening Startup Sequence (1=Yes; 0=No)
BV-44
10030
Exhaust Fan Startup Sequence (1=Yes; 0=No)
BV-48
10034
Supply Fan Startup Sequence (1=Yes; 0=No)
BV-49
10035
BMS Watchdog Ping Active (1=Active; 0=Inactive)
BV-50
10036
BMS Occupancy Command (1=Occupied; 0=Unoccupied)
BV-60
10042
Condenser Water Pump Required (1=Yes; 0=No)
BV-100
10153
Damper Actuator Power (1=Active; 0=Inactive)
BV-111
10164
Compressor 1 Enable (1=Active; 0=Inactive)