Microprocessor Controller for DOAS
16
h
eaTing
r
amp
This screen displays the active set point, supply air temperature, status of the
heating control ramp, and heating ramp being sent from the controller.
d
ehumidiFicaTion
This screen will display the overall dehumidification status and selected
dehumidification control mode.
The following dehumidification modes are available when the space is in occupied
mode:
• Cold coil set point plus offset (10ºF)
• Inside RH*
• Inside dew point*
• Outside dew point
• Inside RH or inside dew point*
• Inside RH or inside dew point or outside dew point
• Inside RH and inside dew point*
• Inside RH and inside dew point or outside dew point
*Available during unoccupied mode.
hgrh r
amp
This screen will display the status of the hot gas reheat ramp. The screen includes
the active set point, supply air discharge temperature, the ramp status, and hot
gas reheat valve request being sent from the controller.
s
upply
s
pace
s
TaTic
This screen displays status points if the unit is configured for space static
pressure control. Status points include controller output ramp, static pressure
in the space, and the space static pressure set point. Similar status screen will
appear for the exhaust fan if the unit is configured for exhaust fan space static
control.
s
upply
/r
eTurn
d
ucT
s
TaTic
This screen displays status points if the unit is configured for duct static pressure
control. Status points include controller output ramp, static pressure in the duct,
and the duct static pressure set point. Similar status screen will appear for the
exhaust fan if the unit is configured for exhaust fan duct static control.
r
eFrigeranT
c
ircuiT
s
TaTus
The refrigerant circuit status screen is active when the unit is equipped with
active head pressure control. This screen provides temperatures and pressures
for suction, discharge, and liquid line sensors when installed. Superheat is also
displayed when suction temperature and pressure sensors are installed.
c
ondiTions
The condition screens are active when both temperature and humidity sensors
for the location are installed in the unit. The enthalpy and dew point are calculated
based on the temperature and humidity readings. The unit altitude is used for the
enthalpy calculation.