Microprocessor Controller for DOAS
42
Appendix E: Points List
AV-7
40013(2)
Indoor Dewpoint Dehumidification Trigger Setpoint
AV-9
40017(2)
Unoccupied Indoor Dewpoint Dehumidification Trigger Setpoint
AV-10
40019(2)
Unoccupied Cooling Setpoint
AV-11
40021(2)
Unoccupied Dehumidification %RH Setpoint
AV-12
40023(2)
Unoccupied Heating Setpoint
AV-16
40031(2)
Economizer Ambient Temp Enable Setpoint
Allow Econ when OAT<Spt
AV-17
40033(2)
Economizer Enthalpy Enable Setpoint
Allow Econ when OA Enthalpy<Spt
AV-21
40041(2)
Outside RH from BMS (BV-5 set to 1 for BMS Control)
AV-22
40043(2)
Outside Temp from BMS (BV-6 set to 1 for BMS Control)
AV-23
40045(2)
Return RH from BMS (BV-7 set to 1 for BMS Control)
AV-24
40047(2)
Return Temp from BMS (BV-8 set to 1 for BMS Control)
AV-25
40049(2)
Space 1 CO2 from BMS (BV-9 set to 1 for BMS Control)
AV-27
40053(2)
Return CO2 from BMS (BV-11 set to 1 for BMS Control)
AV-28
40055(2)
Space RH from BMS (BV-12 set to 1 for BMS Control)
AV-29
40057(2)
Space Static from BMS (BV-13 set to 1 for BMS Control)
AV-30
40059(2)
Space Temp from BMS (BV-14 set to 1 for BMS Control)
AV-31
40061(2)
Cooling Ambient Lockout Setpoint
AV-32
40063(2)
Heating Ambient Lockout Setpoint
AV-33
40065(2)
Preheat Ambient Lockout Setpoint
AV-36
40071(2)
Return Duct Static Pressure Setpoint
AV-37
40073(2)
Space Static Pressure Setpoint
AV-38
40075(2)
Supply Duct Static Pressure Setpoint
AV-39
40077(2)
Space CO2 Setpoint
AV-133
40083(2)
Supply Fan Speed Control Signal from BMS
(BV-56 set to 1 for BMS Control)
AV-134
40085(2)
Exhaust Fan Speed Control Signal from BMS
(BV-57 set to 1 for BMS Control)
AV-136
40089(2)
OA Damper Position Control Signal from BMS
(BV-59 set to 1 for BMS Control)
AV-137
40091(2)
Outside Air Damper Minimum Setpoint
AV-138
40093(2)
BMS Commanded auxiliary analog output
AV-139
40095(2)
BMS Commanded auxiliary analog output
AV-140
40097(2)
BMS Commanded auxiliary analog output
AV-141
40103(2)
BMS Commanded auxiliary analog output
AV-313
40101(2)
Cooling Coil Leaving Air Setpoint Maximum