Appendix E: Points List
AV-132
30179(2)
Active Temperature Setpoint
AV-201
30473(2)
Chilled Water 1 Valve Position %
AV-205
30481(2)
Condenser Ramp 1 %
AV-206
30483(2)
Condenser Ramp 2 %
AV-221
30513(2)
Electric Heater Output %
AV-229
30517(2)
Energy Recovery Output %
AV-231
30521(2)
Exhaust Fan Speed %
AV-235
30523(2)
Hot Gas Reheat Valve Position %
AV-236
30525(2)
Hot Water Valve Position %
AV-242
30537(2)
Mod Gas Furnace Output %
AV-250
30541(2)
Outside Air Damper Position
AV-264
30557(2)
Supply Fan Speed %
AV-285
30585(2)
Modulating Compressor Speed %
AV-286
30587(2)
Circuit A Saturated Discharge Temperature
AV-287
30589(2)
Circuit B Saturated Discharge Temperature
AV-294
30603(2)
Circuit A Saturated Suction Temperature
AV-295
30605(2)
Circuit B Saturated Suction Temperature
AV-312
30653(2)
Calculated Coil Leaving Setpoint
Binary Inputs - Read COV/No Write - Modbus Discrete Inputs
BI-3
10052
Circuit A High Pressure Switch (1=Active; 0=Inactive)
BI-4
10053
Circuit A Low Pressure Switch (1=Active; 0=Inactive)
BI-5
10054
Circuit B High Pressure Switch (1=Active; 0=Inactive)
BI-6
10055
Circuit B Low Pressure Switch (1=Active; 0=Inactive)
BI-21
10070
Drain Pan Alarm Status (1=Active; 0=Inactive)
BI-23
10072
Exhaust Fan 1 Status (1=Active; 0=Inactive)
BI-28
10077
Freeze Stat Alarm Status (1=Active; 0=Inactive)
BI-52
10101
OAD End Switch Status (1=Active; 0=Inactive)
BI-53
10102
Occupancy Status (1=Active; 0=Inactive)
BI-54
10103
Filter Alarm Status (1=Active; 0=Inactive)
BI-75
10124
Shutdown Alarm Status (1=Active; 0=Inactive)
BI-78
10127
Supply Fan 1 Status (1=Active; 0=Inactive)
BI-82
10131
Remote Unit Enable Status (1=Active; 0=Inactive)
BI-83
10132
Heat Wheel Status (1=Active; 0=Inactive)
Binary Values - Read/Commandable - Modbus Coil
BV-1
2
BMS Watchdog Command
Write a 1 to the watchdog within the timeout delay to establish
communication from BMS to the controller. (1=Active; 0=Inactive)
BV-2
3
Master System Enable (1=Enable; 0=Disable)
BV-3
4
Occupancy Command (1=Unoccupied; 0=Occupied)
BV-4
5
Alarm Reset Command (1=Reset; 0=Normal)
BV-5
6
Outside RH Source Selection (1=BMS; 0=Local) (AV-21 Analog Value)
BV-6
7
Outside Temp Source Selection (1=BMS; 0=Local) (AV-22 Analog Value)
BV-7
8
Return RH Source Selection (1=BMS; 0=Local) (AV-23 Analog Value)