67
Current direction adjustment
Under normal circumstances, current flows from input terminal 1 to terminal
2 (i.e. from I11 to I12 for phase A current); however, current may flow in the
opposite direction due to incorrect wiring setup. Instead of rewiring the system,
the meter provides users an option to reverse the polarity of the current. By
default, current direction is set as "positive", to reverse the current polarity by
180 degrees, user can set current direction as "negative". Refer to Fig 4.7 for
more details.