18
proximity to the equipment, within easy reach of the operator, and shall be
marked as the disconnecting device for the equipment.
Fig 2-7 Power supply
A fuse (typical 1A/250Vac) should be used in the auxillary power supply loop.
No. 13 terminal must be connected to the ground terminal of the switchgear.
An isolated transformer or EMC filter should be used in the control power supply
loop if there is a power quality problem in the power supply.
Fig
2-8
Power
supply
With
EMC
filter
Choice of wire of power supply is AWG22-16 or 0.6-1.5mm
2
.
Voltage Input
Maximum input voltage for the Acuvim II series meter shall not exceed
400LN/690LL VAC rms for three phase or 400LN VAC rms for single phase.
Potential Transformer (PT) must be used for high voltage systems. Typical
secondary output for PTs shall be 100V or 120V. Please make sure to select an
NOTE
A filter should be
used if there is
an EMI problem.
Shop for Power Metering products online at:
1.877.766.5412
www.
PowerMeterStore
.com
Содержание Acuvim II
Страница 2: ...Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Страница 8: ...VI Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Страница 16: ...8 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Страница 55: ...47 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Страница 60: ...52 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Страница 85: ...77 Fig 4 7 basic settings Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Страница 142: ...134 Fig 5 27 Fig 5 28 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Страница 167: ...159 Fig 5 46 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...
Страница 268: ...260 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore com...