39

selected, the unit operates with a free temperature setting, progressively lowering the ambient temperature and 
humidity. When the dehumidification programme DRY is in operation, the FAN SPEED button cannot be used. 

I. 4.4 HEATING MODE 

To set the heating mode HEAT, proceed as follows: 
• Select the heating programme by pressing the MODE key (1); 
• Adjust the desired temperature by pressing the TEMP keys (2). The display shows values from 17 °C to 30 °C; 
• Adjust fan speed by pressing FAN SPEED key (3), choosing between AUTO and other speeds HIGH-MED-LOW; 
• Point the remote control at the unit receiver and press the ON/OFF key ON/OFF (4); 
• Adjust the airflow in keeping with requirements by using the SWING key (5) or AIR DIRECTION key (6). Once these 
adjustments have been made, they will be offered when the unit is switched back on. If received by the unit, every 
signal transmitted by the remote control is confirmed by a "beep”. 

I. 4.5 FAN MODE 

To set the fan mode FAN, proceed as follows: 
• Select the fan mode by pressing the MODE key (1); 
• Adjust fan speed by pressing FAN SPEED key (3), choosing between AUTO and other speeds HIGH-MED-LOW; 
• Point the remote control at the unit receiver and press the ON/OFF key ON/OFF (4); 
• Adjust the air flow in keeping with requirements by using the SWING key (5) or AIR DIRECTION key (6); Once these 
adjustments have been made, they will be offered when the unit is switched back on. If received by the unit, every 
signal transmitted by the remote control is confirmed by a "beep” sound. 

I. 4.6 COMFORT FUNCTIONS 

I. 4.6.1 Anti-Heating 

The ANTI-HEATING function is envisaged for COOL and DRY operating modes. It prevents the fan from starting up if 
the inlet water temperature at the exchanger is above 22°C for the minimum speed and 25°C for the medium and 
maximum speed, thus preventing unpleasant hot air flows. This situation could occur the first time the unit is started or 
after long periods out of use. When the ANTI-HEATING function is active, the red DEF./FAN LED is on. 

I. 4.6.2 Anti-Cooling 

The ANTI-COOLING function is envisaged for the HEAT operating mode. It prevents the fan from starting up if the 
inlet water temperature at the exchanger is below 28°C for the minimum speed and 32°C for the medium speed and 
maximum speed, thus preventing unpleasant cold air flows. This situation could occur the first time the unit is started 
or after long periods out of use. When the ANTI-COOLING function is active, the red DEF./FAN LED is on. 

 

IMPORTANT! 

The unit fan stops when the set temperature is reached and is then automatically reactivated at minimum speed to 
prevent air stratification phenomena in the vicinity of the appliance. 

I. 4.7 DESCRIPTION OF THE UNIT INDICATORS 

The indicators found on the unit panel provide information on the unit status or any alarm signals. Moreover, if it is 
temporarily not possible to use the remote control or the wire control, the MANUAL key can be used to operate the 
unit in manual mode. 

Indicators for models: HCA 22-29-35-42 

 

Indicators for models: HCA 60-80 

   HCA/4 

22-35-50     HCA/4 

60-80-120 

 

 

 

1. Infrared receiver. 
2. Manual operation key (MANUAL). 
3. OPERATION LED (green). Indicates that the unit is on. 
4. TIMER LED (yellow). Indicates that the TIMER has been set. 
5. DEF./FAN LED (red). Indicates that the ANTI-COOLING or ANTI-HEATING function is active. 
6. ALARM LED (red). Indicates that the "condensation water level" alarm is active. 
7. Temperature display (only for models 

HCA 60 - 80 

and

 HCA/4 60 - 80-120

). Indicates the set temp. in AUTO, 

COOL and HEAT mode. 

I. 4.7.1 Manual operation (without remote control or wire control) 

In the event of an emergency (for example, when the remote control or wire control are broken) the unit can be 
operated using the indicators envisaged on the panel of the unit itself. By pressing the MANUAL key several times, it is 
possible to change the unit operating mode in keeping with the following outline: 

OFF

AUTO

COOL

HEAT

 

 

OPERATION TIMER

DEF./FAN

ALARM

2

3

4

7

5

6

1

OPERATION TIMER DEF./FAN ALARM

MANUAL

1

3

4

2

5

6

Содержание CVCX Series

Страница 1: ...USER S INSTALLER S MANUAL CVCX Hydronic Cassettes CVCX...

Страница 2: ...2...

Страница 3: ...41 II SECTION II INSTALLATION AND MAINTENANCE II 1 TRANSPORT INSTRUCTIONS 42 II 2 INSTALLATION INSTRUCTIONS 44 II 3 START UP INSTRUCTIONS 56 II 4 MAINTENANCE INSTRUCTIONS 59 II 5 INSTRUCTIONS FOR DISM...

Страница 4: ...of machinery Basic concepts general principles of design UNI EN 294 Safety of machinery Safety distances to prevent the achievement of hazardous areas with the upper limbs UNI EN 563 Safety of machine...

Страница 5: ...ve a serial number plate on the inside which can be viewed by opening the grille Freddo Cool A1 Caldo Heat A2 Freddo Cool B1 Caldo Heat B2 C1 C2 Freddo Cool Caldo Heat Alimenta zione Power supp ly 230...

Страница 6: ...y remaining risks in spite of the provisions adopted or if there are any potential or hidden risks stickers are attached to the machine in compliance with standard ISO 3864 I 2 ACCESSORIES AND SPARE P...

Страница 7: ...FOR USE The following operations can be carried out using the remote control and or the wire control see the instructions for use provided with the same Switching the unit on off Selection of the thr...

Страница 8: ...r when setting the various functions If the signals are received correctly the unit will emit a beep The remote control is able to transmit up to a distance of around 8 metres from the receiver Do not...

Страница 9: ...the ambient temperature When the fan programme FAN is selected the unit operates without temperature settings simply blowing air through the environment IMPORTANT The unit fan stops when the set temp...

Страница 10: ...MODE When the automatic programme AUTO is selected the unit may operate in COOLING or HEATING mode depending on the temperature difference in place between the ambient temperature and the temperature...

Страница 11: ...r long periods out of use When the ANTI HEATING function is active the red DEF FAN LED is on I 4 6 2 Anti Cooling The ANTI COOLING function is envisaged for the HEAT operating mode It prevents the fan...

Страница 12: ...F I 5 CLEANING THE UNIT DANGER Alwaysdisconnectfromthepowersupplybeforestartingcleaningormaintenancework Donotspraywaterontothe unit It is possible to clean the unit exterior To clean it use a soft cl...

Страница 13: ...iod may cause the water contained in the system to freeze During long periods out of use the unit should be disconnected from the electricity supply by opening the system main switch prepared by thein...

Страница 14: ...o obstacles or people blocking the route to avoid the danger of collision crushing or the lifting gear overturning Always use personal protective equipment All the above operations must be performed i...

Страница 15: ...545 575 W C C Condensation drain W Watter connections Avoid blocking the air outlet or inlet Avoid direct sunlight in cooling m od e draw the curtains if necessary Avoid installation nea r he at sou...

Страница 16: ...ilable installed power is sufficient for the operation of other domestic appliances connected to the same power lines Make sure that the power supply network corresponds to current national safety sta...

Страница 17: ...any way other than that illustrated in the figure II 2 1 BEFORE INSTALLATION Carry the packaged unit as close as possible to the installation spot It will be easier to install the unit using a lift I...

Страница 18: ...djusting the nuts an d lock nuts on the threade d braces kee ping a distances of 25 30 m m betwee n the bo dy of the un it an d the inne r surface of the false ceiling 3 25 30 m m 9 8 6 3 Threade d br...

Страница 19: ...LING THE FRAME GRILLE ASSEMBLY Unpack the frame grille assembly and make sure it is not damaged IMPORTANT Only use the screws provided to secure the frame II 2 3 1 Removing the grille from the frame f...

Страница 20: ...brace nuts and lock nuts again Replace the grille 45 II 2 3 3 Installing the frame in models HCA B 60 80 HCA 4 B 60 80 120 Remove the covers in place at the four corners of the frame Align the frame...

Страница 21: ...air inlet duct 5 and an air outlet duct in an adjacent room 6 If there is still a gap between the frame and the false ceiling it should be reduced by working on the brace nuts and lock nuts again Repl...

Страница 22: ...llation is completed the uninsulated surfaces of the ducts must be covered with anti condensation insulation for example expanded neoprene of 6 mm thick B mm 75 N HCA60 80 2 B 1 3 4 5 6 6 7 1 Access c...

Страница 23: ...should dedicate particular care to these operations II 2 5 1 Connection to the system The water connections are fixed to the structure of the unit so as to prevent breakage during the connection of t...

Страница 24: ...ess on the unit drain connection II 2 5 4 Checks Once installation has been completed you will need to Bleed the air out of the circuit Make sure that there are no water leaks Cover the valve if prese...

Страница 25: ...ions and diameter of 1 2 7 Set of 2 monoblock F type connections 8 Copper pipe with diamter of 14 mm 9 2 electrothermic actuators for on off control 230V 3V4C HYDRONIC KIT INSTALLATION a Pipes with di...

Страница 26: ...lled water side carefully in order to prevent condensation from forming on them and dripping onto the false ceiling Electrical connections connect the ambient control by following the instructions rel...

Страница 27: ...he electrical connections to the terminal board in keeping with the wiring diagram and lock the wires into place using suitable flexible couplings IMPORTANT Make the earth connection before the electr...

Страница 28: ...graph II 2 3 connect the paneling XP1 connector to the unit XS1 connector receiver board If using the wired control panel accessory connect the unit XS4 connector to the shielded wire XP4 connector pr...

Страница 29: ...ies from the finned surface which may obstruct the air flow Clean off the dust with a jet of compressed air Wash with water and brush gently Dry with a jet of compressed air Make sure that the condens...

Страница 30: ...rain tray carefully II 5 INSTRUCTIONS FOR DISMANTLING THE UNIT AND DISPOSING OF HAZARDOUS SUBSTANCES ENVIRONMENTAL PROTECTION The firm has always been aware of the importance of protecting the environ...

Страница 31: ...2...

Страница 32: ...Tel 071 723991 Fax 071 7133153 Web Site www accorroni it E mail a2b a 2 b it A2B Accorroni E G S r l Via d Ancona 37 60027 Osimo An...

Отзывы: