Regulation 

The water flow must be controlled: 
• by installing motorized valves supplied as an accessory or: 
• by installed motorized valves supplied by the installer. 

II. 2.5.6 Installation instructions for electro thermal valve with actuator 

The valve/actuator electrothermic set must be mounted on the unit after its installation, following the right schemas 
depending on the unit model. 

3V2C – Hydronic kit for HCA-HCA/B 22-50 
3V2CG – Hydronic kit for HCA-HCA/B 60-120 
Components part 

1) n°1 3-way valve body with ø 3/4", M-type connections. 
2) n°1 electrothermic actuator for on/off control, 230V. 
3) n°2 copper tubes with diameter ø18 mm. 
4) 2 3/4” nipple connections with MM-type threaded 
connections. 
5. n° 4 monoblock F-type connections with dia. of 3/4”.

 

2V2C – Hydronic kit for HCA-HCA/B 22-50 
2V2CG – Hydronic kit for HCA-HCA/B 60-120 
Components part 

1) n°1 2-way valve body with M-type 3/4" connections. 
2) n°1 electrothermic actuator for on/off control, 230V. 
3) n°1 copper tube with diamter of ø18 mm. 
4) n°1 3/4” nipple connection with MM-type threaded 
connections. 
5) set of 2 monoblock F-type 3/4" connections. 

3V4C – Hydronic kit for HCA/4-HCA/4B 22-50 
3V4CG – Hydronic kit for HCA/4-HCA/4B 60-120 
Components part 

1) n°1 3 way valve body, M-type threaded connections 
with diamter of ø 3/4". 
2)  2 nipple connections with MM-type 3/4" connections. 
3) set of 4 monoblock F-type connections with dia. 3/4". 
4) set of 2 copper pipes with diameter of ø 18 mm. 
5) One 3-way valve body with M-type ½” connections. 
6) set of 2 nipple MM-type connections with dia. of 1/2". 
7) set of 4 monoblock 1/2" connection. 
8)  2 copper pipes with diameter of ø 14 mm. 
9) 2 electrothermic actuator for on/off control, 230V. 

2V4C – Hydronic kit for HCA/4-HCA/4B 22-50 
2V4CG – Hydronic kit for HCA/4-HCA/4B 60-120 

Components part 

1) 1 2-way valve body with M-type connections and 
diameter of ø 3/4". 
2) 1 Nipple connections with MM-type threaded 
connections and diameter of 3/4". 
3)  2 F-type monoblock connections with dia. of 3/4"F. 
4) 1 copper pipe with diameter of ø 18 mm 
5) n°1 2-way valve body with M-type connections and 
with diamter of ø 1/2". 
6) n°1 nipple connection with MM-type threaded 
connections and diameter of 1/2". 
7) Set of 2 monoblock F-type connections. 
8) Copper pipe with diamter of ø 14 mm. 
9) 2 electrothermic actuators for on/off control, 230V 

3V4C HYDRONIC KIT INSTALLATION 
a) Pipes with diamter of ø 18 mm 

1) Screw the two nipple fittings with MM-type 3/4", 
threaded connections, please seal them with Teflon tape 
connections on-board unit or, alternatively, use aerobic 
adhesive sealant (Loctite ®, Loxeal ®) 
2) Insert the monoblock fitting to the ends of tubes. 
3) Install the the tube with vertical misalignment in the 
water outlet connection (see Fig. 1).

 

4) Make sure that the two tubes are in contact.

 

5) Connect the valve body to the free end of the pipes, 
please be sure that part of them enter in the valve body

 

6) tighten the four monoblock fittings. 
7) Screw the electrothermic actuator. 
8) Make the electrical connection of the electrothermic 
actuator. 
9) Connect the valve to the terminal block of the electric 
box respecting the proper wiring diagrams. 

 

 

Fig.1 

b) Pipes with diamter of 14 mm 

The procedure is quite similar to one for pipes with 18 
mm diameter. 
Pay particular attention when installing the valve body, 
the tubes must be inserted into the valve body with 
approximately 3 mm. 

c)

 Mount the auxiliary tray under the set valve inserting 

the drain pipe into the proper hole, then level it and fix it 
with three screws provided. 
Insulate the three screws and the bottom part of the 
water tray using insulating material. For the connection of 
steel tubes of the system, you must make sure that are 
aligned and supported avoiding to exercice abnormal 
strains on the unit. When the system is filled with water, 
please check the tightness of all fittings.

 

Notes:

 The valve body must be installed in the proper 

direction of the water flow towards the water outlet from 
the unit.

 

WARNING! KIT INSTALLATION: 3V2C, 2V2C, 2V4C 
(Fig. 2), 3V2CG, 2V2CG, 3V4CG (Fig. 3) e 2V4CG. 

The installation of these valves is operationally quite 
similar to that fulfilled for the 3V4C kit. 

 

 

 

Fig. 

   Fig. 

WARNING! For 2V2C

2V2CG, 2V4C and 2V4GC kit

Install the 2-way valve in the collectors inlet side 
from the unit and make sure that the arrow reported 
on the valve body is in the same direction as water 
flow towards water inlet of the unit

 

WARNING! 

The minimum water temperature sensor must be 
mounted upstream of the valves of water inlet side.

 

Содержание CVCX Series

Страница 1: ...USER S INSTALLER S MANUAL CVCX Hydronic Cassettes CVCX...

Страница 2: ...2...

Страница 3: ...41 II SECTION II INSTALLATION AND MAINTENANCE II 1 TRANSPORT INSTRUCTIONS 42 II 2 INSTALLATION INSTRUCTIONS 44 II 3 START UP INSTRUCTIONS 56 II 4 MAINTENANCE INSTRUCTIONS 59 II 5 INSTRUCTIONS FOR DISM...

Страница 4: ...of machinery Basic concepts general principles of design UNI EN 294 Safety of machinery Safety distances to prevent the achievement of hazardous areas with the upper limbs UNI EN 563 Safety of machine...

Страница 5: ...ve a serial number plate on the inside which can be viewed by opening the grille Freddo Cool A1 Caldo Heat A2 Freddo Cool B1 Caldo Heat B2 C1 C2 Freddo Cool Caldo Heat Alimenta zione Power supp ly 230...

Страница 6: ...y remaining risks in spite of the provisions adopted or if there are any potential or hidden risks stickers are attached to the machine in compliance with standard ISO 3864 I 2 ACCESSORIES AND SPARE P...

Страница 7: ...FOR USE The following operations can be carried out using the remote control and or the wire control see the instructions for use provided with the same Switching the unit on off Selection of the thr...

Страница 8: ...r when setting the various functions If the signals are received correctly the unit will emit a beep The remote control is able to transmit up to a distance of around 8 metres from the receiver Do not...

Страница 9: ...the ambient temperature When the fan programme FAN is selected the unit operates without temperature settings simply blowing air through the environment IMPORTANT The unit fan stops when the set temp...

Страница 10: ...MODE When the automatic programme AUTO is selected the unit may operate in COOLING or HEATING mode depending on the temperature difference in place between the ambient temperature and the temperature...

Страница 11: ...r long periods out of use When the ANTI HEATING function is active the red DEF FAN LED is on I 4 6 2 Anti Cooling The ANTI COOLING function is envisaged for the HEAT operating mode It prevents the fan...

Страница 12: ...F I 5 CLEANING THE UNIT DANGER Alwaysdisconnectfromthepowersupplybeforestartingcleaningormaintenancework Donotspraywaterontothe unit It is possible to clean the unit exterior To clean it use a soft cl...

Страница 13: ...iod may cause the water contained in the system to freeze During long periods out of use the unit should be disconnected from the electricity supply by opening the system main switch prepared by thein...

Страница 14: ...o obstacles or people blocking the route to avoid the danger of collision crushing or the lifting gear overturning Always use personal protective equipment All the above operations must be performed i...

Страница 15: ...545 575 W C C Condensation drain W Watter connections Avoid blocking the air outlet or inlet Avoid direct sunlight in cooling m od e draw the curtains if necessary Avoid installation nea r he at sou...

Страница 16: ...ilable installed power is sufficient for the operation of other domestic appliances connected to the same power lines Make sure that the power supply network corresponds to current national safety sta...

Страница 17: ...any way other than that illustrated in the figure II 2 1 BEFORE INSTALLATION Carry the packaged unit as close as possible to the installation spot It will be easier to install the unit using a lift I...

Страница 18: ...djusting the nuts an d lock nuts on the threade d braces kee ping a distances of 25 30 m m betwee n the bo dy of the un it an d the inne r surface of the false ceiling 3 25 30 m m 9 8 6 3 Threade d br...

Страница 19: ...LING THE FRAME GRILLE ASSEMBLY Unpack the frame grille assembly and make sure it is not damaged IMPORTANT Only use the screws provided to secure the frame II 2 3 1 Removing the grille from the frame f...

Страница 20: ...brace nuts and lock nuts again Replace the grille 45 II 2 3 3 Installing the frame in models HCA B 60 80 HCA 4 B 60 80 120 Remove the covers in place at the four corners of the frame Align the frame...

Страница 21: ...air inlet duct 5 and an air outlet duct in an adjacent room 6 If there is still a gap between the frame and the false ceiling it should be reduced by working on the brace nuts and lock nuts again Repl...

Страница 22: ...llation is completed the uninsulated surfaces of the ducts must be covered with anti condensation insulation for example expanded neoprene of 6 mm thick B mm 75 N HCA60 80 2 B 1 3 4 5 6 6 7 1 Access c...

Страница 23: ...should dedicate particular care to these operations II 2 5 1 Connection to the system The water connections are fixed to the structure of the unit so as to prevent breakage during the connection of t...

Страница 24: ...ess on the unit drain connection II 2 5 4 Checks Once installation has been completed you will need to Bleed the air out of the circuit Make sure that there are no water leaks Cover the valve if prese...

Страница 25: ...ions and diameter of 1 2 7 Set of 2 monoblock F type connections 8 Copper pipe with diamter of 14 mm 9 2 electrothermic actuators for on off control 230V 3V4C HYDRONIC KIT INSTALLATION a Pipes with di...

Страница 26: ...lled water side carefully in order to prevent condensation from forming on them and dripping onto the false ceiling Electrical connections connect the ambient control by following the instructions rel...

Страница 27: ...he electrical connections to the terminal board in keeping with the wiring diagram and lock the wires into place using suitable flexible couplings IMPORTANT Make the earth connection before the electr...

Страница 28: ...graph II 2 3 connect the paneling XP1 connector to the unit XS1 connector receiver board If using the wired control panel accessory connect the unit XS4 connector to the shielded wire XP4 connector pr...

Страница 29: ...ies from the finned surface which may obstruct the air flow Clean off the dust with a jet of compressed air Wash with water and brush gently Dry with a jet of compressed air Make sure that the condens...

Страница 30: ...rain tray carefully II 5 INSTRUCTIONS FOR DISMANTLING THE UNIT AND DISPOSING OF HAZARDOUS SUBSTANCES ENVIRONMENTAL PROTECTION The firm has always been aware of the importance of protecting the environ...

Страница 31: ...2...

Страница 32: ...Tel 071 723991 Fax 071 7133153 Web Site www accorroni it E mail a2b a 2 b it A2B Accorroni E G S r l Via d Ancona 37 60027 Osimo An...

Отзывы: