36
9 - REGOLAZIONE ELETTRONICA
9 - ELECTRONIC CONTROL
Variabili digitali / Digital variables
Indirizzo
Address
Nome / Name
UM Default Range Accesso
Access
Descrizione / Description
1
Stato uscita digitale 1 / DO1 status
R
Actual value of digital output 1 (inverter enable)
2
Stato uscita digitale 2 / DO2 status
R
Actual value of digital output 2 (addtional electric
post heater)
3
Stato uscita digitale 3 / DO3 status
R
Actual value of digital output 3 (fan on)
4
Stato uscita digitale 4 / DO4 status
R
Actual value of digital output 4 (electric pre heater)
5
Stato uscita digitale 5 / DO5 status
R
Actual value of digital output 5 (reverse valve)
6
Stato uscita digitale 6 / DO6 status
R
Actual value of digital output 6 (alarm)
7
Stato uscita digitale 7 / DO7 status
R
Actual value of digital output 7 (on/off I/O dampers)
8
Stato unità / Unit status
R
0= off, 1=on
9
Allarme / Alarm
R
Alarm summary
10
On/Off da supervisore /Supervisor on/off
R/W
Unit on from supervisor
11
On/off remoto / Remote On/Off
R
Status of Remote on/off digital input
12
Pressostato filtri / Filter Pressure switch
R
Status of filter pressure switch digital input
13
Allarme sonda su AI1 / Probe alarm AI1
R
Probe broken or disconnected AI1(external
temperature)
14
Allarme sonda su AI2 / Probe alarm AI2
R
Probe broken or disconnected AI2 (room/return
temperature)
15
Allarme sonda su AI3 / Probe alarm AI3
R
Probe broken or disconnected AI3(evaporation
temperature)
16
Allarme sonda su AI4 / Probe alarm AI4
R
Probe broken or disconnected AI4(supply
temperature)
17
Allarme sonda su AI5 / Probe alarm AI5
R
Probe broken or disconnected AI5(CO2 probe)
18
Allarme sonda su AI6 / Probe alarm AI6
R
Probe broken or disconnected AI6 (evaporation
pressure)
19
Allarme sonda su AI7 / Probe alarm AI7
R
Probe broken or disconnected AI7 (condensation
pressure)
20
Stato DI1 / DI1 Status
R
Actual Value of digital input 1 (filter switch)
21
Stato DI2 / DI2 Status
R
Actual Value of digital input 2 (remote on/off)
22
Stato DI3 / DI3 Status
R
Actual Value of digital input 3 (compressor klixon)
23
Stato DI4 / DI4 Status
R
Actual Value of digital input 4(not used)
24
Stato DI5 / DI5 Status
R
Actual Value of digital input 5 (not connected)
25
Stato DI6 / DI6 Status
R
Actual Value of digital input 6 (low pressure switch)
26
Stato DI7 / DI7 Status
R
Actual Value of digital input 7 (external alarm)
27
Reset allarmi Alarm / Reset alarm command
-
R/W
-
28
Cumulativo Allarme Inverter / Inverter Alarm
R
Inverter alarm summary
29
Allarme Inverter Offline /Inverter offline Alarm
R
30
Allarme Alta pressione/ High pressure alarm
R
31
Allarme Bassa pressione/ Low oressure alarm
-
R
-
32
Allarme valvola espansione elettronica / EVD Alarm
-
R
-
33
Allarme Klixon / Klixon Alarm
R
34
Allarme Inverter / Generic Inverter Alarm
R
Generic Inverter Alarm
35
Allarme da DI / Alarm from external device (DI)
R
36
Allarme Massima temperatura Driver / Inverter high
temperature alarm
R
37
Allarme Aria esterna troppo alta /External air temperature
too high
R
38
Allarme Aria esterna troppo Bessa /External air
temperature too low
R
39
Abilita Allarme massima aria esterna /Enable External air
temperature Alarm
R/W
If selected when external air temperature is too
high compressor is stopped
40
Abilita Allarme minima aria esterna /Enable External air
temperature too low
R/W
If selected when external air temperature is too low
compressor is stopped
41
Abilita Allarme Sovratemperatura Driver /Enable high
inverter temperature alarm
R/W
If selected when inverter temperature is too high
compressor is stopped
42
Warning temperatura aria esterna massima /Warning
external air temperature too high
R
43
Warning temperatura aria esterna minima /Warning
external air temperature too low
R
-
-
-
-
pag.37 - Manuale di installazione, Uso e Manutenzione -