9 - REGOLAZIONE ELETTRONICA
9 - ELECTRONIC CONTROL
Variabili analogiche / Analog Variables
Indirizzo
Address
Nome / Name
UM Default Range Accesso
Access
Descrizione / Description
1
Sonda temperatura esterna / External Probe
temperature
°C
R
Temperatura misurata sonda aria esterna / Temperature
measured by external air probe
2
Sonda temperatura ripresa (se presente) / Room
Probe temperature (if present)
°C
R
Temperatura misurata sonda aria ripresa / Temperature
measured by room probe
3
Sonda temperatura mandata (se presente) / Supply
Probe temperature (if present)
°C
R
Temperatura misurata sonda aria mandata / Temperature
measured by supply air probe
4
Sonda temperatura dopo recupero / After heat
exchanger Probe temperature
°C
R
Temperatura misurata dopo recupero / Temperature
measured after heat exchanger
5
Sonda CO2 / CO2 Probe value
ppm
R
Valore letto sonda CO2 / CO2 probe value
6
Set Point / Set Point
°C
20
R/W
Set point temperatura / Temperature set point
7
Valore A0 / A0 value
°C
2
R/W
Valore A0 / A0 value
8
Valore A1 / A1 value
°C
1
R/W
Valore A0 / A1 value
9
Minimo Set Point / Min value set point
°C
15
R/W
Min value set point
10
Massimo Set Point / Max value set point
°C
35
R/W
Max value set point
11
Valore uscita analogica 1 / Analog Output 1 value
%
R
Actual value of AO1 (supply fan)
12
Valore uscita analogica 2 / Analog Output 2 value
%
R
Actual value of AO2 (return fan)
13
Valore uscita analogica 3 / Analog Output 3 value
%
R
Actual value of AO3 (not used)
14
Valore uscita analogica 4 / Analog Output 4 value
%
R
Actual value of AO4 (not present)
15
Set point inizio Antigelo / Set Point Antifreeze start
bar
-2
R/W
Antifreeze Set Point
16
Set point fine antigelo antigelo /Set Point Antifreeze
stop
bar
3
R/W
Antifreeze Histeresys
17
Set point CO2 / CO2 Setpoint
ppm 800
R/W
CO2 set point, used when CO2 option probe is installaed
18
Set point manuale Freddo / Cooling manual setpoint °C
26
R/W
Cooling manual setpoint
19
Set Pont manuale Caldo/ Heating Manual setpoint
°C
20
R/W
Heating manual setpoint
20
Max Temp Aria esterna / Max external air
temperature
°C
38
R/W
Threshold max external air temperature for inverter run
21
Min Temp Aria esterna / Min external air temperature °C
-10
R/W
Threshold min external air temperature for inverter run
22
Differenziale arie esterna /Histeresys external air
threshold
°C
2
R/W
Histeresys for external temperature threshold
23
-
-
-
-
24
-
-
-
-
25
-
-
-
-
26
-
-
-
-
27
-
-
-
Variabili intere / integer Variables
Indirizzo
Address
Nome / Name
UM Default Range Accesso
Access
Descrizione / Description
209
Stato unità / Unit status
R
Unit status
210
Modo controllo temperatura / Temperature control
mode
0
R/W
0=Automatic, 1=Only heating, 2=Only cooling, 3=Only
fan
211
Minima velocità ventilatore mandata / Min Supply
speed
10
R/W
Min supply fan speed value (analog fan)
212
Massima velocità ventilatore mandata / Max supply
speed
90
R/W
Max supply fan speed value (analog fan)
213
Minima velocità ventilatore ripresa / Min exhaust
speed
10
R/W
Min exhaust fan speed value (analog fan)
214
Massima velocità ventilatore ripresa / Max exhaust
speed
90
R/W
Max exhaust fan speed value (analog fan)
215
Velocità ventilatore mandata (EC) / Analog supply fan
speed (EC)
50
R/W
supply fan speed (analog fan)
216
Velocità ventilatore ripresa (EC) / Analog exhaust fan
speed (EC)
50
R/W
exhaust fan speed (analog fan)
217
Ritardo accensione ventilatori / Delay fan activation
0
R/W
Delay fan start (for damper opening) in second
218
Codice Errore Inverter (105) / Inverter errror code
-
R
Inverter alarm code
219
Stato Inverter (104) /Inverter status code
-
R
Inverter status code
220
Codice Errore circuito sicurezza / Safety circuit alarm
code
-
R
Inverter safety circuit alarm code
221
-
-
-
-
222
-
-
-
-
223
-
-
-
-
224
-
-
-
-
225
-
-
-
-
226
-
-
-
-
pag.36 - Manuale di installazione, Uso e Manutenzione -
Installation, Use and Maintenance Manual