43
SM01P
P48
PROGRAM SELECTION
P48 is used to select whether the drive will operate according to the user settings or the
optional OEM default settings, and to reset the parameters to default settings . Refer to
Section 13 .2 .
01 OPERATE WITH USER SETTINGS: The drive will operate according to the user
settings . Operation in USER mode allows the parameter values to be changed to
suit any application .
02 OPERATE WITH OEM DEFAULTS: The drive will operate according to the optional
OEM default settings, which configure the drive for a specific application . When
operating in OEM mode, the parameter values can be viewed, but not changed . If
an attempt is made to change a parameter setting, the display will flash “GE” . If the
drive is not programmed with OEM default settings, the display will flash “GF” if this
option is selected .
03 RESET OEM: Resets the user parameters to the OEM default settings . If the drive
is not programmed with OEM default settings, the display will flash “GF” if this option
is selected .
04 RESET 60: Resets the user parameters to the factory defaults for a 60 Hz base
frequency . Parameters 24, 27, and 46 will reset to 60 .0 Hz .
05 RESET 50: Resets the user parameters to the factory defaults for a 50 Hz base
frequency . Parameters 24, 27, and 46 will reset to 50 .0 Hz .
06 TRANSLATE: If an EPM from a drive with a previous (but compatible) parameter
version is installed in a new drive, the new drive will function like the previous version
drive, but none of the parameter settings can be changed ("cE" will be displayed if this
is attempted) . The TRANSLATE function converts the EPM to the new parameter
version so that the parameters can be changed, but it also retains the old parameter
settings so the new drive will operate like the old drive without having to re-program
all of the parameters . Once the EPM is "translated", it will no longer work in the old
drive .
NOTE
•
If the user parameters are reset to the OEM defaults (using the RESET OEM
option), and then OPERATE WITH USER SETTINGS is selected, the USER
settings will be the same as the OEM default settings . This allows the drive to
operate as if it was in OEM mode, but the parameter values can be changed .
This is useful if some of the OEM default settings need to be fine-tuned for proper
operation . The new parameter values are not actually stored as new OEM default
settings however; they are simply stored as new USER settings . Therefore, if
the parameters are reset to the OEM defaults again, the parameters that were
changed will be reset to their “old” value . The optional EPM Programmer is
required to change OEM default settings . Refer to Section 13 .2 .
•
Only the TRANSLATE (06) function can be performed while the drive is running .
The display will flash "Er" if an attempt is made to select any other function while
the drive is running .
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]