Page 1
–12
2104349 rev. AD
Component
Description
Analog Inputs
1 (0-10 VDC)
Digital Inputs
1 (State Change or Pulse to 20 kHz) operating at a 50% duty cycle
with (Selectable De-bounce enabled 100 Hz)
Digital Outputs
1 FETs, sink = 2.5 Amp Max.Open Drain PTC, with 1500 W Transient protection
I/O Module Interface
Optional plug-in I/O daughter card with 12 I/O (3 AI, 1 AO, 4 DI and 4 DO)
LCD Interface
Dedicated interface for Liquid Crystal Display (LCD)
Security Switch
On/Off Bi-level on-board Security (See Chapter 3 for details)
I/O Scan Rate
1 time per second
Time Base Stability
7.5 ppm (parts per million)
Pulse Input
Bandwidth
Up to 20 KHz (Linear flow meter only)
1.2.3 G4 EX termination board
The G4 EX termination board can be accessed by removing the rear end cap (see
). All user connections should be routed through the cable entry hubs
and should adhere to local codes.
Located on the termination board, the user will find connectors for two (2)
communication ports: RS-232, RS-422 or RS-485 (software selectable). The user
should also note that there is a dedicated port for RS-232 local communications.
This is a plug type port and will connect to an internal PCCU connector or an
explosion proof external PCCU connector.
For more information on the explosion proof PCCU connector, see the
corresponding section. Additionally, for the internal PCCU connector, see the
section under Optional Equipment in this chapter.
COM 1 Port
Remote communication wiring for Port 1 is handled using the
J19 connector and the SW1 communication switch.
Com 2 Port
Remote communication wiring for Port 2 is handled using the
J20 connector and the SW2 communication switch.
The XFC G4 6200/6201EX (G4 EX) is approved for installation
in classified/potential hazardous locations where an explosive
atmosphere may be present. Follow precautions and
requirements for installation of equipment according to the
certification drawing indicated on the device’s nametag and
national and local electrical codes.