XIO USER MANUAL | 2106424MNAB |
195
and connected to other field devices on any of the other available Ethernet interfaces.
an example of this scenario.
Figure 9-12: Use of a port forwarding XIO to securely isolate field LAN from WAN
The XIO connection to the corporate network (2) is considered the uplink connection (also referred to as
the enterprise connection in PCCU). The connections to field devices (on XIO port B2) are local
connections. In the example in
, devices (RMC, XIO-1, XIO-2) are daisy-chained. For security,
the port forwarding XIO can be configured to keep the uplink connection to the corporate network isolated
from the connections to the field while still allowing access to specific devices and their enabled services.
That is, the Enterprise (A-Network) is separated from the Industrial (B-Networks).
IMPORTANT NOTE:
The term “uplink” in port forwarding refers to the interface used for the
connection to the wide area network. The Port Forwarding tab uses the term “enterprise” for the
interface for this connection. Note that any of the Ethernet interfaces that are active and enabled
can be selected as the enterprise interface from the Enterprise Interface drop-down menu on the
Port Forwarding tab. Therefore, any A-Network or B-Network interface can be selected, not just A
interfaces (which are the ones referred to as Enterprise interfaces on the Networking tab). The
choice depends on the customer requirements for field connections.
9.7.1
Configuration overview
Port forwarding requires careful selection and configuration of the Ethernet interfaces used for WAN and
LAN connections. Review sections
9.7.2 Ethernet interface IP addressing guidelines
to determine configuration requirements for your field conditions. Sections
Network ports for field LAN connections
9.7.5 Use A-Network ports for WAN (uplink) connection
provide two example scenarios.
Sections
9.7.7 Define port forwarding rules
forwarding and configure forwarding rules on the XIO. These procedures assume that the devices for
Содержание XIO-00
Страница 54: ...54 XIO USER MANUAL 2106424MNAB Figure 4 24 Default XIO Interface configuration ...
Страница 115: ...XIO USER MANUAL 2106424MNAB 115 Figure 6 17 Configure attached device type Figure 6 18 Configure COM port ...
Страница 131: ...XIO USER MANUAL 2106424MNAB 131 Figure 7 7 RBAC select XIO Figure 7 8 RBAC confirm XIO selection ...
Страница 132: ...132 XIO USER MANUAL 2106424MNAB Figure 7 9 Add User in Security Editor Figure 7 10 Type user name and password ...
Страница 140: ...140 XIO USER MANUAL 2106424MNAB Figure 7 18 PuTTYgen Key Generator Key blank field Figure 7 19 New public key ...
Страница 146: ...146 XIO USER MANUAL 2106424MNAB Figure 7 28 Type private key passphrase password Figure 7 29 Unknown host key warning ...
Страница 147: ...XIO USER MANUAL 2106424MNAB 147 Figure 7 30 FileZilla New Site window ...
Страница 148: ...148 XIO USER MANUAL 2106424MNAB Figure 7 31 Open the Flash AppData ssh directory ...
Страница 149: ...XIO USER MANUAL 2106424MNAB 149 Figure 7 32 Upload public key from laptop to device ...
Страница 150: ...150 XIO USER MANUAL 2106424MNAB Figure 7 33 Verify public key upload is complete ...