300/600W Mini Inverter

INSTALLATION       

a.   Remove the front cover of the Mini Inverter by removing the two screws at the top of the cover.

b. Extend the unswitched, properly-rated voltage AC supply and remote fixture wires to the installation area.

c. Use keyhole slots at the rear of the unit and mount the Mini Inverter securely to the wall.   

d. Connect the conduit containing the AC supply and remote fixture leads to the Mini Inverter. Use the provided knock-outs on the 

side of the Mini Inverter for connecting the incoming wires.

e. Install the batteries at this time, but do not connect the battery leads until other wiring is completed.        

a.   For 120V supply, connect the AC Line wire to the 120V (UN-SWT) position of the INPUT POWER section of the terminal block. 

For 277V or 347V supply, connect the AC Line wire to the 277V or 347V (UN-SWT) position of the INPUT POWER section of the 

terminal block.

b. Connect the NEUTRAL wire to the NEUTRAL position of the INPUT POWER section of the terminal block.
c. Connect the ground wire in accordance with local and national codes.  

d. For Nexus wired (option): Refer to the “WIRING FOR NEXUS

®

” on the page 4.

 

a.   Connect the remote emergency fixtures to the correct position of the LOAD terminal block, respecting the operating voltage. All 

remote circuitry is to be wired in accordance with Article 700 of the National Electric Code. 

Do not exceed the total rating of the 

Mini Inverter. Unit is rated at maximum Watt and maximum VA, where Max.W = Max.VA. Total load (W) must be derated 
when load power factor (PF) is less than 0.9 (for maximum rating).

 Special attention shall be taken when load consists of LED 

lamps with no built-in power factor correction. Example: most of the single LED lamps (Screw-on, GU-10, etc.) have a power 
factor of less than 0.6. This translates to a derating close to 50%.

b.

NORMALLY-OFF FIXTURES (only come on during power failure)

 - Connect the AC Line input wire of the fixtures to the 

appropriate position of the LOAD terminal block (120V OR 277V OR 347V). Connect the fixture Neutral to the Neutral position of 
the LOAD terminal block. Refer to Figure 2B.

c.

UN-SWITCHED NORMALLY-ON FIXTURES

 - Connect the AC Line input wire of the fixtures to the appropriate position of the 

LOAD terminal block (120V OR 277V OR 347V). Connect the fixture Neutral to the Neutral position of the LOAD terminal block. 
Refer to Figure 2C.

d.

SWITCHED NORMALLY-ON LOAD

 (fixtures may be turned on and off locally, but will come on during power failure regardless of 

switch position) - Follow Step 3B above. Connect the Line side of the switch to the (UN-SWT) position of the INPUT POWER 
terminal block, respecting the operating voltage (120V OR 277V OR 347V). Connect the load side of the switch to the (SWT) 
position on the INPUT POWER terminal block, respecting the operating voltage (120V OR 277V OR 347V). Refer to Figure 2A.  

e.  Connect the Fixture Supply Ground to the Mini Inverter Ground.   

a.   Position the battery(s) in the unit. 

b. Refer to figures 1A or 1B. Connect the RED wire to the positive (+) post of the battery. Connect the BLUE wire to the negative (-) 

post of the battery. Tighten all bolts to a recommended torque of 

78 lbf-in ± 4 lbf-in

.  

NOTE: THE EMERGENCY LIGHT AND INDICATORS WILL NOT TURN ON AT THIS TIME.   

a.   Energize the AC supply. The Status Indicator will illuminate. Refer to the operation information below for more information about 

the Status Indicator.

b. Normally-ON fixtures shall be ON, Normally-OFF shall be OFF. Switched Emergency Fixtures shall be ON only when the switch is 

in the ON position.

c. Manually test the unit by pressing the test switch for 1 second and then release it. (Refer to “MANUAL TEST”  for more details).

d. If status LED is not green, reset the system. (Refer to “SYSTEM RESET”). 

e. Properly re-install the cover of the Mini Inverter using all the original hardware.

 

STEP 1: MOUNTING THE MINI INVERTER TO THE WALL

STEP 2: CONNECT THE NORMAL AC INPUT (SEE FIGURE 2A, 2B, 2C OR 2D)

STEP 3: CONNECT THE REMOTE EMERGENCY FIXTURES (SEE FIGURE 2A, 2B, 2C OR 2D)

STEP 4: CONNECT THE BATTERY(S)

STEP 5: SWITCH ON THE INVERTER MODULE (SWITCH IS LOCATED ON THE RIGHT SIDE OF 
               THE INVERTER MODULE).

STEP 6: COMPLETE THE INSTALLATION

Содержание Thomas & Betts 300W

Страница 1: ...rical Code and local regulations 12 The Mini Inverter contains potentially hazardous voltages Installation maintenance and service work should be performed by qualified and trained personnel 13 Electricians and end users need to ensure product system compatibility before final installation 14 Units to be installed only as per configuration described in this instruction manual IMPORTANT Do not exce...

Страница 2: ...BATTERY CAUTION BEFORE INSTALLING MAKE CERTAIN THE A C POWER IS OFF NOTE THE BATTERY S ARE SHIPPED SEPARATELY PLACE THEM IN A LOCATION AWAY FROM THE WORK AREA TO AVOID DAMAGE UNTIL THEY ARE TO BE INSTALLED CAUTION ONLY ONE VOLTAGE IS ALLOWED 120V OR 277V OR 347V CONNECTION TO MORE THAN ONE VOLTAGE MAY RESULT IN EQUIPMENT FAILURE AND VOID THE WARRANTY CAUTION FOR NORMALLY ON UN SWITCHED UNITS THE J...

Страница 3: ...ppropriate position of the LOAD terminal block 120V OR 277V OR 347V Connect the fixture Neutral to the Neutral position of the LOAD terminal block Refer to Figure 2B c UN SWITCHED NORMALLY ON FIXTURES Connect the AC Line input wire of the fixtures to the appropriate position of the LOAD terminal block 120V OR 277V OR 347V Connect the fixture Neutral to the Neutral position of the LOAD terminal blo...

Страница 4: ...itch is pressed for 1 second and then released The Status Indicator will start flashing green The designated fixtures will either illuminate if they were off or will stay on if they were normally illuminated Test duration is fixed at 1 minute At the end of the 1 minute test the unit will revert to recharge mode The status indicator will be steady ON green if no fault has been detected If a fault i...

Страница 5: ...30 C 68 to 86 F their life expectancy is 8 to 10 years The equipment must be tested for a minimum of 30 minutes once per year When the batteries will no longer operate the load for 30 minutes for they must be replaced Replace only with manufacturer supplied parts Properly dispose of or recycle the Lead Acid battery NOTE THE FOLLOWING WIRING DIAGRAMS HAVE BEEN SIMPLIFIED FOR CLARITY FIGURE 1A 300W ...

Страница 6: ...20Vac Neutral see note 3 347Vac Primary Un Switched AC Input Normally ON Lighting Load Neutral see note 3 Ground Ground 347Vac Neutral see note 3 120Vac Neutral see note 3 Ground Neutral Line Switched Line Un Switched Line Neutral FIGURE 2B WIRING DIAGRAM NORMALLY OFF LOAD Lighting Load Fluorescent LED Incandescent Notes 1 Connect fixture supply and unit ground in accordance with local and nationa...

Страница 7: ...tched Line Neutral see note 4 Un Switched see note 3 120Vac Neutral 120V Neutral Primary Un Switched AC Input Normally ON Lighting Load see note 4 see note 4 Ground Ground Lighting Load Fluorescent LED Incandescent 347Vac Neutral 347V Neutral Primary Un Switched AC Input Normally ON Lighting Load see note 4 see note 4 120Vac Neutral 120V Neutral 120Vac Ground 0 10V FIGURE 2D WIRING DIAGRAM UN SWIT...

Страница 8: ...system This is done by holding the TEST switch for at least 6 seconds The reset also initializes the main counter This renewal takes place to compensate for system variations when the unit ages Renewal is not allowed if there is a lighting load failure alarm e SERVER FAILURE The Nexus server controller or PC is no longer communicating with the RF unit s modem To solve this issue you need to verify...

Страница 9: ...mming control The dimming function must be disabled during a power failure in order for the load to provide a 100 level of lighting The circuit consists of a single pole dry contact relay that is normally closed in stand by operation In emergency mode power failure the relay contacts open and disconnect the dimming signal from the lighting load allowing the load to operate at 100 light level INSTA...

Страница 10: ...ed to the Nexus system Lamp load is OFF None if unit is in normally off mode Nexus option Unit is operating correctly Unit is not commissioned to the Nexus system LED flashing GREEN OFF Lamp load is ON None the unit is in test mode or is sampling load Unit is operating correctly Lamp load is OFF Inverter switched OFF Check the inverter ON OFF switch Turn it on Switch is located on the right side o...

Страница 11: ...eries LED Flashing RED 2 times every 6 seconds Charger Failure Error Charger not working Reset the unit see page 4 and if the same error is displayed replace the charger board LED Flashing RED 3 times every 6 seconds Lamp Failure Error Lost 10 or more if initial lamp loading is lost Replace the bad lamp and reset the unit LED AMBER ORANGE steady On Network server down The Nexus modem is no longer ...

Страница 12: ...ERVICE FOR REPLACEMENT PARTS SERVICING MUST BE PERFORMED BY QUALIFIED PERSONNEL Consult Customer Service for current warranty information All information and specifications contained in these instructions are subject to change due to engineer design errors and omissions 2014 Thomas Betts Limited All rights reserved ...

Страница 13: ...L ENTRETIEN DOIT ÊTRE EFFECTUÉ PAR UN PERSONNEL QUALIFIÉ Pour obtenir l information en vigueur sur la garantie veuillez vous adresser au service à la clientèle Toute l information et toutes les spécifications contenues dans ces instructions sont modifiables à cause de changements à la conception des erreurs et des omissions 2014 Thomas Betts Limitée Tous droits réservés ...

Страница 14: ...te 2 fois toutes les 6 secondes Erreur de défaillance du chargeur Erreur de défaillance du chargeur Réinitialiser l unité voir page 4 si la même erreur s affiche remplacer la carte du chargeur DEL ROUGE clignotant 3 fois toutes les 6 secondes Erreur de défaillance de lampe Perte de 10 ou plus si le chargement initial de lampe est perdu Remplacer la lampe défaillante et réinitialiser l unité DEL AM...

Страница 15: ...ne si l unité est en mode normalement inactif Option Nexus L unité fonctionne correctement L unité n est pas mise en service auprès du système Nexus DEL clignotante VERTE ÉTEINTE La charge de lampe est ACTIVE Aucune si l unité est en mode de test ou prend un échantillon de charges L unité fonctionne correctement La charge de lampe est INACTIVE Interrupteur d onduleur ÉTEINT Vérifier l interrupteur...

Страница 16: ...tème de contrôle d éclairage à basse tension par gradation Cette fonction doit être désactivée durant une panne de courant afin que la charge puisse fournir un niveau d intensité lumineuse de 100 Le circuit consiste d un relais unipolaire à contacts secs normalement fermés en mode de fonctionnement de veille En mode de secours panne de courant les contacts s ouvrent et coupent le signal de gradati...

Страница 17: ... ÉCLAIRAGE Le déclenchement de la séquence de capture exige la réinitialisation du système Pour réinitialiser appuyer sur l interrupteur d essai pendant au moins 6 secondes Ceci initialise également le compteur principal Suivant 12 périodes de 30 jours les données de capture de la charge d éclairage sont renouvelées Ceci est réalisé afin de compenser pour les variations du système avec le temps Le...

Страница 18: ...eutre Neutre Entrée ac primaire Normalement Charge d éclairage éteinte la terre 347Vca voir note 4 Mise á 347V voir note 4 Neutre Neutre Entrée ac primaire Normalement Charge d éclairage éteinte la terre 120Vca Commutée Neutre Non commutée Ligne Neutre Charge d éclairage Au fluorescent DEL à incandescence Mise á la terre Non commutée Cábles Sortie Cábles Entrée 0 10V FIGURE 2D SCHÉMA DE CÂBLAGE CH...

Страница 19: ...te Interrupteur Mural Interrupteur Mural Neutre Charge d éclairage Au fluorescent DEL à incandescence la terre Mise á la terre Mise á la terre Mise á la terre Cábles Sortie Cábles Entrée Commutée FIGURE 2B SCHÉMA DE CÂBLAGE CHARGE NORMALEMENT ÉTEINTE IMPORTANT POUR UN ÉCLAIRAGE NORMALEMENT ÉTEINT ENLEVER CE CAVALIER 120Vca voir note 3 voir note 3 120Vca voir note 3 347Vca voir note 3 Mise á 347V v...

Страница 20: ...e prévue est de 8 à 10 ans Équipement doit être testé une fois par année pendant au moins 30 minutes Lorsque les piles ne font plus fonctionner la charge pendant 30 minutes pour les unités il faut les remplacer Les pièces de rechange utilisées doivent être fournies exclusivement par le fabricant Veuillez éliminer ou recycler adéquatement les batteries au plomb acide NOTE LE SCHÉMA DE CÂBLAGE CI DE...

Страница 21: ...suite qu on le relâche L indicateur d état commencera à clignoter en vert Les appareils désignés s allumeront s ils étaient éteints ou resteront allumés s ils étaient allumés en mode normal La durée des essais est réglée à 1 minute À la fin de l essai d une minute l unité rétablira le mode de recharge L indicateur d état sera alors allumé en continu en vert si aucun défaut n a été détecté Si une d...

Страница 22: ...reil au Neutre sur le bloc de jonction SORTIE LOAD Se référerréférer à la Figure 2B c APPAREILS NORMALEMENT ALLUMÉS Connecter le fil d entrée LIGNE c a des appareils à la position appropriée sur le bloc de jonction SORTIE LOAD Connecter le fil Neutre de l appareil au Neutre sur le bloc de jonction SORTIE LOAD Se référer à la Figure 2C d COMMUTATION NORMALEMENT ALLUMÉ LOAD peuvent être allumés et é...

Страница 23: ...T COUPÉ NOTE LES BATTERIES SONT EXPÉDIÉES SÉPARÉMENT LES ENTREPOSER À L ÉCART DU LIEU DE TRAVAIL JUSQU AU MOMENT DE L INSTALLATION MISE EN GARDE UNE SEULE TENSION EST PERMISE 120V ou 277V ou 347V TOUTE CONNEXION À UNE TENSION AUTRE QUE CELLE SPÉCIFIÉE ENTRAÎNERA UNE DÉFAILLANCE DE L ÉQUIPEMENT ET ANNULER A LA GARANTIE MISE EN GARDE POUR LES LAMPES NORMALEMENT ALLUMÉES SUR UNE SORTIE DE 277VAC LE C...

Страница 24: ...el à un médecin 11 Installer conformément aux règlements du NEC et de tous les codes locaux applicables 12 Le Mini onduleur contient des tensions potentiellement dangereuses Tout travail d installation d entretien et de réparation doit être effectué par un personnel qualifié ayant suivi une formation adéquate 13 Les électriciens et les utilisateurs finals doivent confirmer la compatibilité du syst...

Отзывы: