300/600W Mini Inverter

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ THIS MANUAL AND FOLLOW ALL SAFETY INSTRUCTIONS 
THOROUGHLY BEFORE OPERATING THE  INVERTER SYSTEM

SAVE THESE INSTRUCTIONS

 

 

                                                           

1. DO NOT USE OUTDOORS.

2. All unused wires must be insulated to prevent shorting.

3. Do not mount near gas or electric heaters.

4. Do not let power supply cords touch hot surfaces.

5.

D

o not use this equipment for other than its intended use.

6. The Mini Inverter should be mounted securely and in locations and at heights where it will not be readily subjected to tampering by 

unauthorized personnel.

7. The use of accessory equipment and replacement parts not recommended by manufacturer may cause an unsafe condition and 

void the warranty.

8. The AC voltage rating of this equipment is specified on the product label. Do not connect the Mini Inverter equipment to any other 

voltage.

9. Replacement fuse is supplied.

10. The Mini Inverter uses sealed valve regulated lead acid batteries. Batteries can be punctured if not handled properly, therefore use 

caution when servicing batteries.  In the event battery acid comes in contact with eyes or skin, flush with fresh water and consult a 
physician immediately.

11. Install in accordance with the National Electrical Code and local regulations.

12. The Mini  Inverter  contains potentially hazardous voltages. Installation, maintenance  and service work should be performed by 

qualified and trained personnel.

13.

Electricians and end-users need to ensure product system compatibility before final installation.

14. Units to  be  installed only as per  configuration described in this instruction manual.        

IMPORTANT:

 

Do not exceed the total rating of the Mini Inverter. Unit is rated at maximum Watt and maximum VA, where Max.W 

= Max.VA. Total load (W) must be derated when load power factor (PF) is less than 0.9 (for maximum performance)

All Thomas & Betts inverter products receive 100% quality inspection before shipment to ensure proper and satisfactory operation.
When operated under normal conditions, Thomas & Betts inverter products will provide years of dependable service. This unit is backed 
by a 1-9 year warranty. The unit is covered by a complete 1-year warranty against defects in material or workmanship, and a 9-year pro-
rata battery warranty.

BEFORE CONTACTING TECHNICAL SUPPORT PLEASE REFER TO THE TROUBLESHOOTING GUIDE INCLUDED IN 
THIS MANUAL.

MODEL 

NUMBER

AC SPECS

EMERGENCY POWER AVAILABLE FOR LOAD

APPROX. 

WEIGHT 

30 MIN

1H

1H 30MIN

2H

4H

300

120 Vac, 60Hz

3.10 Amps

300W

240W

175W

140W

80W

70LBS.

600

120 Vac, 60Hz

6.00 Amps

600W

410W

300W

240W

125W

120LBS.

347 Vac, 60Hz

2.30 Amps

600W

410W

300W

240W

125W

120LBS.

WARRANTY

 300/600W Mini Inverter

INTERRUPTIBLE EMERGENCY LIGHTING

UNIT INVERTER INSTRUCTION MANUAL

THIS UNIT CONTAINS A 

RECHARGEABLE VALVE-REGULATED  

LEAD ACID BATTERY. PLEASE 

RECYCLE OR DISPOSE OF 

PROPERLY.

Содержание Thomas & Betts 300W

Страница 1: ...rical Code and local regulations 12 The Mini Inverter contains potentially hazardous voltages Installation maintenance and service work should be performed by qualified and trained personnel 13 Electricians and end users need to ensure product system compatibility before final installation 14 Units to be installed only as per configuration described in this instruction manual IMPORTANT Do not exce...

Страница 2: ...BATTERY CAUTION BEFORE INSTALLING MAKE CERTAIN THE A C POWER IS OFF NOTE THE BATTERY S ARE SHIPPED SEPARATELY PLACE THEM IN A LOCATION AWAY FROM THE WORK AREA TO AVOID DAMAGE UNTIL THEY ARE TO BE INSTALLED CAUTION ONLY ONE VOLTAGE IS ALLOWED 120V OR 277V OR 347V CONNECTION TO MORE THAN ONE VOLTAGE MAY RESULT IN EQUIPMENT FAILURE AND VOID THE WARRANTY CAUTION FOR NORMALLY ON UN SWITCHED UNITS THE J...

Страница 3: ...ppropriate position of the LOAD terminal block 120V OR 277V OR 347V Connect the fixture Neutral to the Neutral position of the LOAD terminal block Refer to Figure 2B c UN SWITCHED NORMALLY ON FIXTURES Connect the AC Line input wire of the fixtures to the appropriate position of the LOAD terminal block 120V OR 277V OR 347V Connect the fixture Neutral to the Neutral position of the LOAD terminal blo...

Страница 4: ...itch is pressed for 1 second and then released The Status Indicator will start flashing green The designated fixtures will either illuminate if they were off or will stay on if they were normally illuminated Test duration is fixed at 1 minute At the end of the 1 minute test the unit will revert to recharge mode The status indicator will be steady ON green if no fault has been detected If a fault i...

Страница 5: ...30 C 68 to 86 F their life expectancy is 8 to 10 years The equipment must be tested for a minimum of 30 minutes once per year When the batteries will no longer operate the load for 30 minutes for they must be replaced Replace only with manufacturer supplied parts Properly dispose of or recycle the Lead Acid battery NOTE THE FOLLOWING WIRING DIAGRAMS HAVE BEEN SIMPLIFIED FOR CLARITY FIGURE 1A 300W ...

Страница 6: ...20Vac Neutral see note 3 347Vac Primary Un Switched AC Input Normally ON Lighting Load Neutral see note 3 Ground Ground 347Vac Neutral see note 3 120Vac Neutral see note 3 Ground Neutral Line Switched Line Un Switched Line Neutral FIGURE 2B WIRING DIAGRAM NORMALLY OFF LOAD Lighting Load Fluorescent LED Incandescent Notes 1 Connect fixture supply and unit ground in accordance with local and nationa...

Страница 7: ...tched Line Neutral see note 4 Un Switched see note 3 120Vac Neutral 120V Neutral Primary Un Switched AC Input Normally ON Lighting Load see note 4 see note 4 Ground Ground Lighting Load Fluorescent LED Incandescent 347Vac Neutral 347V Neutral Primary Un Switched AC Input Normally ON Lighting Load see note 4 see note 4 120Vac Neutral 120V Neutral 120Vac Ground 0 10V FIGURE 2D WIRING DIAGRAM UN SWIT...

Страница 8: ...system This is done by holding the TEST switch for at least 6 seconds The reset also initializes the main counter This renewal takes place to compensate for system variations when the unit ages Renewal is not allowed if there is a lighting load failure alarm e SERVER FAILURE The Nexus server controller or PC is no longer communicating with the RF unit s modem To solve this issue you need to verify...

Страница 9: ...mming control The dimming function must be disabled during a power failure in order for the load to provide a 100 level of lighting The circuit consists of a single pole dry contact relay that is normally closed in stand by operation In emergency mode power failure the relay contacts open and disconnect the dimming signal from the lighting load allowing the load to operate at 100 light level INSTA...

Страница 10: ...ed to the Nexus system Lamp load is OFF None if unit is in normally off mode Nexus option Unit is operating correctly Unit is not commissioned to the Nexus system LED flashing GREEN OFF Lamp load is ON None the unit is in test mode or is sampling load Unit is operating correctly Lamp load is OFF Inverter switched OFF Check the inverter ON OFF switch Turn it on Switch is located on the right side o...

Страница 11: ...eries LED Flashing RED 2 times every 6 seconds Charger Failure Error Charger not working Reset the unit see page 4 and if the same error is displayed replace the charger board LED Flashing RED 3 times every 6 seconds Lamp Failure Error Lost 10 or more if initial lamp loading is lost Replace the bad lamp and reset the unit LED AMBER ORANGE steady On Network server down The Nexus modem is no longer ...

Страница 12: ...ERVICE FOR REPLACEMENT PARTS SERVICING MUST BE PERFORMED BY QUALIFIED PERSONNEL Consult Customer Service for current warranty information All information and specifications contained in these instructions are subject to change due to engineer design errors and omissions 2014 Thomas Betts Limited All rights reserved ...

Страница 13: ...L ENTRETIEN DOIT ÊTRE EFFECTUÉ PAR UN PERSONNEL QUALIFIÉ Pour obtenir l information en vigueur sur la garantie veuillez vous adresser au service à la clientèle Toute l information et toutes les spécifications contenues dans ces instructions sont modifiables à cause de changements à la conception des erreurs et des omissions 2014 Thomas Betts Limitée Tous droits réservés ...

Страница 14: ...te 2 fois toutes les 6 secondes Erreur de défaillance du chargeur Erreur de défaillance du chargeur Réinitialiser l unité voir page 4 si la même erreur s affiche remplacer la carte du chargeur DEL ROUGE clignotant 3 fois toutes les 6 secondes Erreur de défaillance de lampe Perte de 10 ou plus si le chargement initial de lampe est perdu Remplacer la lampe défaillante et réinitialiser l unité DEL AM...

Страница 15: ...ne si l unité est en mode normalement inactif Option Nexus L unité fonctionne correctement L unité n est pas mise en service auprès du système Nexus DEL clignotante VERTE ÉTEINTE La charge de lampe est ACTIVE Aucune si l unité est en mode de test ou prend un échantillon de charges L unité fonctionne correctement La charge de lampe est INACTIVE Interrupteur d onduleur ÉTEINT Vérifier l interrupteur...

Страница 16: ...tème de contrôle d éclairage à basse tension par gradation Cette fonction doit être désactivée durant une panne de courant afin que la charge puisse fournir un niveau d intensité lumineuse de 100 Le circuit consiste d un relais unipolaire à contacts secs normalement fermés en mode de fonctionnement de veille En mode de secours panne de courant les contacts s ouvrent et coupent le signal de gradati...

Страница 17: ... ÉCLAIRAGE Le déclenchement de la séquence de capture exige la réinitialisation du système Pour réinitialiser appuyer sur l interrupteur d essai pendant au moins 6 secondes Ceci initialise également le compteur principal Suivant 12 périodes de 30 jours les données de capture de la charge d éclairage sont renouvelées Ceci est réalisé afin de compenser pour les variations du système avec le temps Le...

Страница 18: ...eutre Neutre Entrée ac primaire Normalement Charge d éclairage éteinte la terre 347Vca voir note 4 Mise á 347V voir note 4 Neutre Neutre Entrée ac primaire Normalement Charge d éclairage éteinte la terre 120Vca Commutée Neutre Non commutée Ligne Neutre Charge d éclairage Au fluorescent DEL à incandescence Mise á la terre Non commutée Cábles Sortie Cábles Entrée 0 10V FIGURE 2D SCHÉMA DE CÂBLAGE CH...

Страница 19: ...te Interrupteur Mural Interrupteur Mural Neutre Charge d éclairage Au fluorescent DEL à incandescence la terre Mise á la terre Mise á la terre Mise á la terre Cábles Sortie Cábles Entrée Commutée FIGURE 2B SCHÉMA DE CÂBLAGE CHARGE NORMALEMENT ÉTEINTE IMPORTANT POUR UN ÉCLAIRAGE NORMALEMENT ÉTEINT ENLEVER CE CAVALIER 120Vca voir note 3 voir note 3 120Vca voir note 3 347Vca voir note 3 Mise á 347V v...

Страница 20: ...e prévue est de 8 à 10 ans Équipement doit être testé une fois par année pendant au moins 30 minutes Lorsque les piles ne font plus fonctionner la charge pendant 30 minutes pour les unités il faut les remplacer Les pièces de rechange utilisées doivent être fournies exclusivement par le fabricant Veuillez éliminer ou recycler adéquatement les batteries au plomb acide NOTE LE SCHÉMA DE CÂBLAGE CI DE...

Страница 21: ...suite qu on le relâche L indicateur d état commencera à clignoter en vert Les appareils désignés s allumeront s ils étaient éteints ou resteront allumés s ils étaient allumés en mode normal La durée des essais est réglée à 1 minute À la fin de l essai d une minute l unité rétablira le mode de recharge L indicateur d état sera alors allumé en continu en vert si aucun défaut n a été détecté Si une d...

Страница 22: ...reil au Neutre sur le bloc de jonction SORTIE LOAD Se référerréférer à la Figure 2B c APPAREILS NORMALEMENT ALLUMÉS Connecter le fil d entrée LIGNE c a des appareils à la position appropriée sur le bloc de jonction SORTIE LOAD Connecter le fil Neutre de l appareil au Neutre sur le bloc de jonction SORTIE LOAD Se référer à la Figure 2C d COMMUTATION NORMALEMENT ALLUMÉ LOAD peuvent être allumés et é...

Страница 23: ...T COUPÉ NOTE LES BATTERIES SONT EXPÉDIÉES SÉPARÉMENT LES ENTREPOSER À L ÉCART DU LIEU DE TRAVAIL JUSQU AU MOMENT DE L INSTALLATION MISE EN GARDE UNE SEULE TENSION EST PERMISE 120V ou 277V ou 347V TOUTE CONNEXION À UNE TENSION AUTRE QUE CELLE SPÉCIFIÉE ENTRAÎNERA UNE DÉFAILLANCE DE L ÉQUIPEMENT ET ANNULER A LA GARANTIE MISE EN GARDE POUR LES LAMPES NORMALEMENT ALLUMÉES SUR UNE SORTIE DE 277VAC LE C...

Страница 24: ...el à un médecin 11 Installer conformément aux règlements du NEC et de tous les codes locaux applicables 12 Le Mini onduleur contient des tensions potentiellement dangereuses Tout travail d installation d entretien et de réparation doit être effectué par un personnel qualifié ayant suivi une formation adéquate 13 Les électriciens et les utilisateurs finals doivent confirmer la compatibilité du syst...

Отзывы: