KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5343
│
241
10.24.31 Additional heating stage - Hysteresis
Options:
Setting option between 0.3 - 25
The hysteresis of the two-point controller specifies the fluctuation range of the controller around
the setpoint value. The lower switching point is located at "Setpoint value minus hysteresis" and
the upper point is at "Setpoint value plus hysteresis".
Notice
This parameter is only available when the "Control value type" parameter is set
either on "2-point 1 Bit, Off/On" or "2-point 1 Byte, 0/100%".