KNX control elements and application parameters
Control element: "Dimmer slider"
Product manual 2CKA001473B5343
│
131
Notice
The parameter can only be set when parameter "Icon type" is set on "User-
defined".
10.4.7 Status control element (icon) is operated via a separate object
Options: Deactivated
Activated
An additional 1-bit communication object "Switch status" is enabled via the parameter.
When the object has been enabled, the status display of the control element indicates the
current status of the object. The feedback object can ensure that the correct status is always
displayed.
If an actuator has a separate feedback object, this additional object can check whether the
actuator has switched. For this the feedback object of the actuator must be connected with the
feedback object of the button via a common group address (Action).
If the status display is not activated via a feedback object, the control element always changes
to the other status when actuated.
10.4.8 Display value in control element
Options: Deactivated
Activated
The parameter is used to specify whether the dimming value is displayed in the control element.
–
No
: No display. No additional parameters available.
–
Yes
: The following parameters are displayed:
Status of dimming value is controlled by a separate object:
Options: Deactivated
Activated
The brightness value signalled by the dimmer slider can be displayed via a separate object.
An additional 1-bit communication object "Status value" is enabled. The displayed value
does not originate from the control element. The value is received via a separate feedback
object.
Unit
:
Options: <Text>
The parameter is used to enter the unit or the unit sign with which the value is displayed in
the control element.
The length of the text is limited to 20 characters.
Содержание SmartTouch B/graphite
Страница 57: ...Commissioning via ABB free home Product manual 2CKA001473B5343 57 ...
Страница 59: ...Commissioning via ABB free home Product manual 2CKA001473B5343 59 Abb 33 Other settings Part 2 ...
Страница 84: ...Commissioning of the KNX function via ABB DCA SmartTouch 10 from ETS5 Product manual 2CKA001473B5343 84 ...
Страница 121: ...KNX control elements and application parameters Switch control element Product manual 2CKA001473B5343 121 ...
Страница 302: ...KNX communication objects Application Internal RTC Product manual 2CKA001473B5343 302 Pa ...
Страница 309: ...Operation Product manual 2CKA001473B5343 309 12 2 2 Additional basic principles Fig 46 Basic principles ...