KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5343
│
237
available to the user.
– If the required heating type is not available, individual parameters can be specified in the
free configuration.
Note
This parameter is only available when "Control value type" parameter for the
additional stage is set either on "PI continuous, 0 – 100%", "PI PWM, On/Off“
or "Fan coil".
10.24.20 Control of additional heating stage - P-component
Options:
Setting option between 1 - 25
The P-component stands for the proportional range in a control. It fluctuates around the setpoint
value and can be used to influence the control speed of a PI controller. The smaller the value
set, the faster the control reacts. However, the value should not be set too small because
otherwise there may be a risk of an overshoot. A P-component from 1 to 25 K can be set.
Notice
This parameter is only available when "Control value type" parameter for the
additional stage is set either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or
"Fan coil". The "Additional heating type" parameter must be set on "Free
configuration".
10.24.21 Control of additional heating stage - I-component
Options:
Setting option between 0 - 600
The I-component refers to the readjust time of a control. The integral component has the effect
of moving the room temperature slowly toward, and ultimately reaching, the setpoint value.
Depending on the type of system used, the reset time has to have different values. In general,
the more inactive the overall system, the greater the readjust time.
Notice
This parameter is only available when "Control value type" parameter for the
additional stage is set either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or
"Fan coil". The "Additional heating type" parameter must be set on "Free
configuration".
10.24.22 Control of additional heating stage - Temperature difference to basic stage
Options:
Setting option between 0 - 25
The setpoint temperature of the additional stage is defined as a function of the current setpoint
temperature of the base stage and is expressed as a difference. The value represents the
setpoint value starting at which the additional stage will operate.
10.24.23 Control of additional heating stage - Extended settings
Options: Deactivated
Содержание SmartTouch B/graphite
Страница 57: ...Commissioning via ABB free home Product manual 2CKA001473B5343 57 ...
Страница 59: ...Commissioning via ABB free home Product manual 2CKA001473B5343 59 Abb 33 Other settings Part 2 ...
Страница 84: ...Commissioning of the KNX function via ABB DCA SmartTouch 10 from ETS5 Product manual 2CKA001473B5343 84 ...
Страница 121: ...KNX control elements and application parameters Switch control element Product manual 2CKA001473B5343 121 ...
Страница 302: ...KNX communication objects Application Internal RTC Product manual 2CKA001473B5343 302 Pa ...
Страница 309: ...Operation Product manual 2CKA001473B5343 309 12 2 2 Additional basic principles Fig 46 Basic principles ...