KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5343
│
253
10.24.62 Settings of basic load
Notice
Only available when the "Control function" parameter is set either on "Heating
with additional stage," "Cooling with additional stage," "Heating and cooling" or
"Heating and cooling with additional stages".
10.24.63 Settings of basic load — Minimum control value for basic load > 0
Options: Always
active
Activate via object
The function finds application when in the desired area, e.g. with floor heating, the floor is to
have a basic warmth. The size of the minimum control value specifies the volume of heating
medium that flows through the controlled area, even when the calculation of the control value of
the controller would indicate a lower value.
–
Always active
: Here it is possible to define whether this basic load will be permanently active
or whether it will be switched via the "Basic load" object.
–
Activate via object
: When this parameter is selected, the basic load function, which means
the minimum control value with a value higher than zero, can be activated (1) or deactivated
(2). If it is activated, then the heating medium will always be fed through the system with at
least the minimum control value. If it is deactivated, the control value can be reduced to zero
with the controller.
10.24.64 Basic load settings — Basic load active when controller is off
Options: Yes
No
– This parameter switches the basic load active when the controller is off.
Notice
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or "Fan coil".
Содержание SmartTouch B/graphite
Страница 57: ...Commissioning via ABB free home Product manual 2CKA001473B5343 57 ...
Страница 59: ...Commissioning via ABB free home Product manual 2CKA001473B5343 59 Abb 33 Other settings Part 2 ...
Страница 84: ...Commissioning of the KNX function via ABB DCA SmartTouch 10 from ETS5 Product manual 2CKA001473B5343 84 ...
Страница 121: ...KNX control elements and application parameters Switch control element Product manual 2CKA001473B5343 121 ...
Страница 302: ...KNX communication objects Application Internal RTC Product manual 2CKA001473B5343 302 Pa ...
Страница 309: ...Operation Product manual 2CKA001473B5343 309 12 2 2 Additional basic principles Fig 46 Basic principles ...